GK600E User Manual
Chapter 4 Operation and Run Instructions
- 53 -
BIT0 and BIT1 in ones place of L1-02. If BIT0=1, setting frequency w ill be displayed. The bits
that correspond to the parameters w hich are not required to display shall be set to 0. Therefore,
the value in ones place should be 0011, corresponding to 3 in a hexadecimal number. Set the
ones place to 3.
Set the value in tens place:
As show n in Fig. 4-14, since it is required to display "AI1", the binary set value of tens place is
0001, corresponding to 1 in a hexadecimal number. Thus, bit of tens place shall be set to 1.
Set the value in hundreds place:
As show n in Fig. 4-14, the parameter required to display does not involve hundreds place, so
the hundreds place shall be set to zero.
Set thousands place:
As show n in Fig. 4-14, since required to display "running linear speed" and "setting linear
speed", the binary set value of thousands place shall be 0011 that corresponds to 3 in a
hexadecimal number.
To sum up, L1-02 should be set to 3013.
Fig. 4-14 Setting of hexadecimal parameter L1-02
Under parameter setting status, the parameter value cannot be modified if the value has no
flashing digit. Possible causes include:
1) The parameter cannot be modified, such as actual detection parameters, running recording
parameters, etc;
2) This parameter cannot be modified in run status but can be changed w hen motor stopped;
3) Parameter under protection. When parameter A0-02 is set to 1, parameters cannot be
modified as the parameter protection against misoperation enabled. To edit parameter in
such a circumstance, it is necessary to set A0-02 to 0 as first step.
4.1.4.4 Lock/Unlock Control Panel
Lock control panel
All or some keys of CONTROL PANEL can be locked by any of the follow ing three
methods. See the definition of parameter L0-01 for further information.
Method 1: set the parameter value of L0-01 to non-zero, then press
+
+
simultaneously.