GK600E User Manual
Chapter 6 List of Parameters
- 95 -
Parameter
Designation
Scope
Factory
default
Attr
coefficient Kp
E0-06
V/F current integral
coefficient Ki
0~60000
200
×
E0-07
V/F torque r
0: Disabled
1: Enabled
0
×
E0-08
Torque sampling time
0.00s~6.00s
0.20s
×
E0-09
Reserved
Reserved
Reserved ×
E0-10
Reserved
Reserved
Reserved ×
E0-11
Reserved
Reserved
Reserved ×
Group E1 Protection Parameters
E1-00
Overvoltage stall
0: Prohibited
1: Allow ed
0
×
E1-01
Overvoltage stall protection
voltage
120%~150%
135%
×
E1-02
Undervoltage stall
0: Disabled
1: Enabled
0
×
E1-03
Overload alarm
Ones place: detection option:
0: Alw ays detect
1: Detect at constant speed only
Tens place: compared w ith:
0: Motor rated current
1: Drive rated current
Hundreds place: drive action
0: Alarm but run continued
1: Alarm and coast to stop
100
×
E1-04
Overload alarm threshold 20.0%~200.0%
120.0%
△
E1-05
Overload alarm activation
time
0.1s~60.0s
7.0s
△
E1-06
Protection action 1
Ones place: reserved
Tens place: action at IGBT
temperature measurement circuit
fault (OH3):
0: Coast to stop
1: Alarm but run continued
Hundreds place: abnormal EEPROM
(EPr) :
0: Coast to stop
1: Alarm but run continued
Thousands place: abnormal terminal
communication (TrC):
0: Coast to stop
1: Alarm but run continued
0000
×