Chapter 5 Elev ator Dedicated Parameters
- 59 -
0: No binding
1: Digital setting (b0-02) +
∧
/
∨
adjustment on control panel
2: Digital setting (b0-02) + terminal UP/DOWN adjustment
3: Analog input AI1
4:Aanalog input AI2
5: Analog input EAI (on IO option board)
6: X6/DI pulse input
7: Process PID output
8: Simple PLC
9: Multi-step frequency
A: Communication input
Refer to parameter b0-01 for details regarding above-mentioned sources of frequency setting.
Tens place: frequency setting bundled under terminal control (same as ones place)
Hundreds place: frequency setting bundled under communication control (same as ones
place)
ATTENTION:
Different run command sources can be bundled w ith the same frequency setting source. The
priority of frequency setting sources bundled w ith run command overrides Group b0.
b1-02
Run direction
Range: 0~1
Factory default: 0
This parameter applies to run command controlled by control panel, and disabled under
terminal and communication control.
0: Forw ard
1: Reverse
b1-05
Start method
Range: 0~3
Factory default: 1
This parameter takes effect during the process of transition from stop status to run status.
0: From start frequency
When drive starts to run from stop status, it starts from start frequency (b1-06) and keeps this
frequency for a period of time set by b1-07, and then accelerated to set frequency in
accordance w ith the Accel method and time.
1: DC injection brake start
To make the motor stop completely before a new start, the drive w ill perform DC braking w ith
a certain period of time, as specified by b1-08 and b1-09, then start from start frequency
(b1-06), keeping a period of time as specified by b1-07, and then Accelerate to set frequency.
2: Flying start 1
3: Flying start 2
b1-06
Start frequency
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz