Chapter 5 Elevator Dedicated Parameters GK600E User Manual
- 62 -
b2-12
Accel/Decel curve
Range: 0~5
Factory default: 5
0: Linear Accel/Decel
1: Broken-line Accel/Decel
2: S-curve Accel/Decel A
3: S-curve Accel/Decel B
4: S-curve Accel/Decel C
5: Elevator dedicated S-curve
b2-15
S-curve acc start time
Range: 0.00s~60.00s
Factory default: 1.00s
b2-16
S-curve acc end time
Range: 0.00s~60.00s
Factory default: 1.00s
b2-17
S-curve dec start time
Range: 0.00s~60.00s
Factory default: 1.00s
b2-18
S-curve dec end time
Range: 0.00s~60.00s
Factory default: 1.00s
Group C0 Digital Input
C0-01 Function of terminal X1 (Default: Enable) Range: 0~99
Factory default: 71
C0-02 Function of terminal X2 (Default: FWD)
Range: 0~99
Factory default: 3
C0-03 Function of terminal X3 (Default: REV)
Range: 0~99
Factory default: 4
C0-04 Function of terminal X4 (Default: MSS1)
Range: 0~99
Factory default: 15
C0-05 Function of terminal X5 (Default: MSS2)
Range: 0~99
Factory default: 16
C0-06 Function of terminal X6 (Default: MSS3)
Range: 0~99
Factory default: 17
C0-07
Function of terminal X7
(on IO option) (Default: Emergency)
Range: 0~99
Factory default: 18
When grid pow er supply is lost, elevator controller is sw itched to UPS pow er supply and output
emergency signal to the drive. Immediately after receiving this emergency signal, the drive w ill
go into emergency mode. GK600E supports UPS pow er supply 220V single phase input or
380V three phase input. In emergency mode, the drive w ill run at emergency frequency set by
F1-17 (default: 5Hz), and run via acceleration time b2-07 or deceleration time b2-08. As default,
the digital input X7 at option board is used as emergency signal input (C0-07 =18). If users
w ould like to use other terminal input like X5 as emergency signal input, corresponding
parameter C0-05 have to be set to 18: emergency.
Follow ing are the meanings of different parameter values. For more please refer to the
complete parameter list in Chapter 6.
3:
Run forw ard (FWD)
4:
Run reverse (REV)
5:
Three-w ire control
6:
Run suspended
7:
External stop
8:
Emergency stop
15:
Multi-speed selector 1
16:
Multi-speed selector 2
17:
Multi-speed selector 3
18:
Emergency Speed
22:
External fault input
23:
Fault reset (RESET)
71:
Enable