Chapter 6 List of Parameters GK600E User Manual
- 96 -
Parameter
Designation
Scope
Factory
default
Attr
E1-07
Protection action 2
Ones place: abnormal pow er supply
w hen running (SUE):
0: Coast to stop
1: Alarm but run continued
Tens place: current detection circuit
failed (CtC)
0: Coast to stop
1: Alarm but run continued
Hundreds place: abnormal contactor
(CCL):
0: Coast to stop
1: Alarm but run continued
Thousands place: input supply fault
/output phase loss (ISF, oPL):
0: Protection for neither input supply
fault nor output phase loss
1: No protection for input supply fault,
protection enabled for output phase
loss
2: Protection enabled for input supply
fault, no protection for output phase
loss
3: Protection enabled both for input
supply fault and output phase loss
1001
×
E1-08
Fault memory after pow er
loss
0: Not memorized after pow er loss
1: Memorized after pow er loss
0
×
E1-09
Fault auto-reset times
0~20
0
×
E1-10
Auto-reset interval
2.0s~20.0s
2.0s
×
E1-11
Relay action on drive fault
Ones place: w hen undervoltage fault
occurs
0: No action
1: Action enabled
Tens place: w hen fault locked
0: No action
1: Action enabled
Hundreds place: at interval of auto-
reset
0: No action
1: Action enabled
010
×
E1-12
Cooling fan control
0: Auto run
1: Alw ays run after pow er up
0
△