SETPOINT > CONTROL ELEMENTS > OVERFREQUENCY
OVERFREQUENCY 1 > OVERFREQUENCY 2 > OVERFREQUENCY 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
50.50
0.01 Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
50
1 V
[30 : 500]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Maximum Number of shots
Max Number Shots
1
N/A
[1 : 4]
Dead time 1
Dead Time 1
0.00
0.01 s
[0.00 : 900.00]
Dead time 2
Dead Time 2
0.00
0.01 s
[0.00 : 900.00]
Dead time 3
Dead Time 3
0.00
0.01 s
[0.00 : 900.00]
Dead time 4
Dead Time 4
0.00
0.01 s
[0.00 : 900.00]
Reclaim time or reset lockout delay
Reclaim Time
0.00
0.01 s
[0.00 : 900.00]
Reclose conditions permission
Cond. Permission
DISABLED
N/A
[DISABLED – ENABLED]
Hold time
Hold Time
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Time
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > VT FUSE FAILURE
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...