GEK-113032A
W650 Wind Generator Protection System
5-107
5 SETTINGS
5.7 TESTINGS
5
5.7TESTINGS
5.7.1 FORCE IO –INPUT TESTING
The input testing can only be performed in relay with graphical display, see the human interfaces section in this manual for
more detailed information.
5.7.2 FORCE IO –OUTPUT TESTING
Output testing can be performed via HMI in models with graphical display and via communications through EnerVista 650
Setup in all models.
Setpoint > Inputs/Outputs > Force Outputs
This menu allows activating each contact output in the relay, to facilitate maintenance testing. In the screen, the user can
select the I/O board to be tested, and also select which output is to be forced (operated).
After selecting the desired output, clicking on the checkbox on the left, the user must press on the
Force Output
button to
activate the selected output.
In order to refresh the real status of outputs, according to the information received by the relay processor, the
Refresh
button must be pressed.
The following figure shows the output-testing screen:
Figure 5–33: FORCE IO
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...