5-46
W650 Wind Generator Protection System
GEK-113032A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
Figure 5–7: OVERCURRENT ELEMENTS BLOCK CONFIGURATION BY THE DIRECTIONAL ELEMENT
Directional elements can also be blocked with signals coming from other relays, PLCs, or through signals configured in the
relay PLC Editor (Logic configuration tool). The signal used in that case is PHASE DIR BLK INP. Figure 5–8: shows an
example of the default block configuration of directional elements by digital input. There is one block signal per input for
each setting group.
Figure 5–8: DIRECTIONAL ELEMENT BLOCK CONFIGURATION BY INPUT
The main component of the phase directional element is the angle comparator with two inputs: the operation magnitude
(phase current) and the polarization magnitude (phase-to-phase voltage rotated the angle set in MTA setting), which is the
torque angle.
The Polarization type used in the directional element is crossed, this means that in case of a fault in phase A, the Operation
magnitude will be Ia, and the polarization magnitude will be Vbc, rotated by the torque angle. In case of a fault in phase B,
the operation magnitude will be Ib, and the polarization magnitude will be Vca rotated by the torque angle. Finally, in case
of a fault in phase C, the operation magnitudes will be Ic, and Vab.
Table 5–44: OPERATION AND POLARIZATION MAGNITUDES FOR DIRECTIONAL UNITS
POLARIZING SIGNAL VPOL
PHASE
OPERATING SIGNAL
ABC PHASE SEQUENCE
ACB PHASE SEQUENCE
A
IA angle
VBC angle x 1 MTA
VCB angle x 1 MTA
B
IB angle
VCA angle x 1 MTA
VAC angle x 1 MTA
C
IC angle
VAB angle x 1 MTA
VBA angle x 1 MTA
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...