GEK-113032A
W650 Wind Generator Protection System
5-89
5 SETTINGS
5.6 INPUTS/OUTPUTS
5
5.6.2 CONTROL SETTINGS FOR INPUTS/OUTPUTS
Configuration of settings relative to inputs and outputs can only be accessed through the EnerVista 650 Setup
software, and not via the HMI
. For this purpose, the user must access
Setpoint > Inputs/Outputs > Contact I/O > Board
X
, being X the corresponding I/O board.
settings relative to I/O boards are described in Table 5–77:
Table 5–77: I/O BOARD SETTINGS
The snapshot event setting enables or disables the snapshot event generation for this element.
Being:
X
F or G, the I/O board name, depending on the Relay model.
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STE
P
RANGE
I/O board type (available only for CIO modules)
I/O Board Type_H
NONE
N/A
[NONE,
16 INP + 8OUT,
8 INP + 8OUT + SUPV
32 INP
16 INP + 8 ANA]
Input activation voltage threshold
Group A
Voltage Threshold A_
X
80
1 V
[20 : 230]
Input activation voltage threshold
Group B, C and D
Voltage Threshold B_X
80
1 V
[20 : 230]
Debounce time for Group A
Debounce Time A_X
15
1 ms [1 : 50]
Debounce time for Group B, C and D
Debounce Time B_X
15
1 ms [1 : 50]
Input type
Input Type_
X
_CC
Y
(CC
Y
)
POSITIVE
N/A
[POSITIVE-EDGE,
NEGATIVE-EDGE,
POSITIVE,
NEGATIVE]
Input signal time delay
Delay Input Time_
X
_CC
Y
(CC
Y
)
0
1 ms [0 : 60000]
Output logic type
Output Logic_
X
_0
Z
POSITIVE
N/A
[POSITIVE,
NEGATIVE]
Output type
Output Type_
X
_0
Z
NORMAL
N/A
[NORMAL,
PULSE,
LATCH]
Output pulse length
Pulse Output Time_
X
_0
Z
10000
1 ms [0 : 60000]
Analog Inputs Range
Range_X-02
None
N/A
[NONE,
-1 to 0mA,
0 to 1 mA,
-1 to 1 mA,
0 to 5 mA,
0 to 10 mA]
Minimum Value
Min_Value_X_0X
0.00
0.01
[ -9999.99 : 9999.99]
Maximum Value
Max_Value_X_0X
0.00
0.01
[ -9999.99 : 9999.99]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...