5-44
W650 Wind Generator Protection System
GEK-113032A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
5.4.3.3 PHASE DIRECTIONAL ELEMENT (67P)
The Phase directional element (67P) provides independent elements for each phase, and determines the direction of the
current both in permanence and in fault condition.
Its main function is to apply a blocking signal to the overcurrent elements to prevent their operation when the current is
flowing in a certain direction. In order to determine the direction of the current, the element uses phase current values as
operation magnitude, and phase-to-phase voltage values as polarization magnitude. This means that in order to polarize a
phase, we use the phase-to-phase voltage of the other two phases, known as crossed polarization.
The following table describes the phase directional element settings.
Table 5–42: PHASE DIRECTIONAL ELEMENT SETTINGS
Function:
This setting allows enabling or disabling the corresponding directional element.
MTA:
The MTA setting corresponds to the Torque angle, which is the rotation applied to
phase-to-phase crossed voltage.
Direction:
This setting allows selecting the area for the directional element to operate, either
forward or reverse.
Block Logic:
This setting allows selecting either permission or block, depending on the logic to be
applied in the event of directional element block.
Polarization Voltage Threshold:
This is the minimum voltage considered for the direction calculation. Under this setting,
the element will be blocked.
Snapshot Events:
The snapshot event setting enables or disables the snapshot event generation for the
phase directional elements.
Phase directional element is an independent Protection element that provides block and Operation signals for each phase.
These signals can be monitored both through the relay HMI or using EnerVista 650 Setup at “
Actual > Status > Protection
> Phase Current
”
SETPOINT > PROTECTION ELEMENTS > PHASE CURRENT > PHASE DIRECTIONAL >
PHASE DIRECTIONAL 1> PHASE DIRECTIONAL 2 > PHASE DIRECTIONAL 3
SETTING DESCRIPTION
NAME
DEFAULT VALUE STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Maximum Torque Angle
MTA
45º
1 Deg
[-90 : +90]
Operation Direction
Direction
FORWARD
N/A
[FORWARD – REVERSE]
Block logic
Block Logic
PERMISSION
N/A
[BLOCK – PERMISSION]
Polarization voltage threshold
Pol V Threshold
50
1 V
[0 : 850]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...