GEK-113032A
W650 Wind Generator Protection System
11-7
11 COMMISSIONING
11.7 VERIFICATION OF MEASUREMENT
11
11.7VERIFICATION OF MEASUREMENT
Set the relay as follows
NOTE:
ALL ANGLES INDICATED ARE LAGGING ANGLES
ALL VALUES OBTAINED IN THIS TEST MUST BE THE ONES CORRESPONDING TO THE DFT
11.7.1 VOLTAGES
Apply the following current and frequency values to the relay:
Verify that the relay measures the values with an error of +/-1 % of the applied value plus 0,1% of full scale (275V).
11.7.2 PHASE CURRENTS
Apply the following voltage and frequency values to the relay:
Verify that the relay measures the values with an error lower than +/-0.5% of the test value or+/- 10 mA, whichever is
greater, for phases and ground.
Verify that the relay measures the values with an error lower than +/-1.5% of the test value or+/- 1 mA, whichever is greater,
for sensitive ground (SG).
GENERAL SETTINGS
NAME
VALUE
UNITS
RANGE
PHASE CT RATIO
1.0
0.1
1.0-6000.0
GROUND CT RATIO
1.0
0.1
1.0-6000.0
STV GROUND CT RATIO
1.0
0.1
1.0-6000.0
PHASE VT RATIO
1.0
0.1
1.0-1500.0
PHASE VT CONNECTION
WYE
N/A
WYE – DELTA
NOMINAL VOLTAGE
690 V
0.1
1-850 V
NOMINAL FREQUENCY
50 Hz
1 Hz
50-60 Hz
PHASE ROTATION
ABC
N/A
ABC – ACB
FREQUENCY REFERENCE
VI
N/A
VI-VII-VIII
AUXILIARY VOLTAGE
VX
N/A
VX – VN
CHANNEL
ANGLE
FREQUENCY
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
VI
0º
0
5
50
100
150
275
VII
120º
0
5
50
100
150
275
VIII
240º
0
5
50
100
150
275
VX
0º
0
5
50
100
150
275
CHANNEL
ANGLE
FREQUENCY
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Ia (A)
45º
0
15
10
5
1
0.1
Ib (A)
165º
0
15
10
5
1
0.1
Ic (A)
285º
0
15
10
5
1
0.1
IG(A)
0º
0
15
10
5
1
0.1
ISG(A)
0º
0
5
1
0.1
0.01
0.005
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...