GEK-113032A
W650 Wind Generator Protection System
5-65
5 SETTINGS
5.4 PROTECTION ELEMENTS
5
5.4.8.2 PHASE OVERVOLTAGE ELEMENT (59P)
The Phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a Definite
Time element. The input voltage is the phase-to-phase voltage, either measured directly from Delta-connected VTs or as
calculated from phase-to-ground (wye) connected VTs. The time delay can be set from instantaneous to 900 seconds. The
element reset can be delayed up to 900 seconds.
As in the case of the undervoltage element, this element generates independent pickup and trip signals for each phase.
The general signal is selectable by setting to be an OR or an AND of the phase signals.
Table 5–62: 59P ELEMENT SETTINGS
Phase overvoltage element settings are:
Function Permission (Function):
This setting indicates whether the phase overvoltage element is enabled or disabled.
Pickup Level:
This is the voltage threshold over which the overvoltage element will operate.
Trip time (Trip Delay):
setting of the Protection element operation time.
Reset time (Reset Delay):
Reset time of the Protection element.
Operation logic (Logic):
This setting allows the element operation logic selection:
ANY PHASE
The element will operate under an overvoltage condition in any of the
three phases.
TWO PHASES
The element will operate under an overvoltage condition in at least
two phases.
ALL PHASES
The element will operate under an overvoltage condition in the three
phases.
Snapshot Events:
The snapshot event setting enables or disables the snapshot event generation for this
element.
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS > PHASE OV >
PHASE OV 1> PHASE OV 2 > PHASE OV 3 > PHASE OV 4
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup Level
Pickup Level
50
1 V
[3 : 850]
Trip time
Trip Delay
10.00
0.01 s [0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s [0.00 : 900.00]
Operation logic
Logic
ANY PHASE
N/A
[ANY PHASE – TWO PHASES – ALL PHASES]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...