GEK-113032A
W650 Wind Generator Protection System
7-31
7 IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR W650
7
c) PROTECTION ACTIVATION INFORMATION (ACT)
ACT CLASS (PROTECTION ACTIVATION INFORMATION)
GEPHSACT
Attribute
Name
Attribute Type
FC
TrgOp
Value/Value Range
M/O/C
DATAATTRIBUTE
control and status
general
Boolean
ST
Dchg
M
phsA
Boolean
ST
Dchg
O
phsB
Boolean
ST
Dchg
O
phsC
Boolean
ST
Dchg
O
q
Bvstring13
ST
Qchg
M
t
Utctime
ST
M
configuration, descripcion and extension
d
Vstring255
DC
O
GENEUTACT
Attribute
Name
Attribute Type
FC
TrgOp
Value/Value Range
M/O/C
DATAATTRIBUTE
control and status
general
Boolean
ST
Dchg
M
neut
Boolean
ST
Dchg
O
q
Bvstring13
ST
Qchg
M
t
Utctime
ST
M
configuration, descripcion and extension
d
Vstring255
DC
O
GEGENERALACT
Attribute
Name
Attribute Type
FC
TrgOp
Value/Value Range
M/O/C
DATAATTRIBUTE
control and status
general
Boolean
ST
Dchg
M
q
BVstring13
ST
Qchg
M
t
Utctime
ST
M
configuration, descripcion and extension
d
Vstring255
DC
O
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...