GEK-113032A
W650 Wind Generator Protection System
4-27
4 HUMAN INTERFACES.
4.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE
4
Table 4–16: GENERAL OVERVIEW OF STATUS MENU:
Table 4–17: DIFFERENT CONTROL ACTUAL VALUES INCLUDED IN THE CONTROL ELEMENTS MENU
STATUS
Operation bits
Up to 24 elements. OPERATION BIT XX is (0) when the configured time
out for the operation XX expires or when success conditions are met.
And it is (1) if operation XX is executed and interlocks are fulfilled.
Breaker
Breaker status (open, closed or undefined). The rest of the status signals
corresponding to the switchgear XX configured as breaker are in the
“
Status>Switchgear Status>Switchgear XX
” menu.
Protection
Status of all the protection units in the device.
Control Elements
Status of all the control units available in the device.
Protection Summary
This screen shows a complete list of all protection and control elements
in the relay, showing their status (enabled or not).
Snapshots events
summary
Summary of the snapshot events status (enabled or disabled) for
protection, control, inputs and outputs boards and switchgear.
ModBus User Map
Up to 256 elements. Value in SIGNED INT 16 BIT format of the reading
for the selected address configured in “
Setpoint>Product
Setup>ModBus User Map
”
Switchgear Status
Up to 16 blocks of switchgear status signals for the 16 configurable
devices. Status signals such as inputs for A and B contacts, status for A
and B, open and close status, error 00 and error 11, open init and close
init, fail to open and fail to close signals.
Calibration
Internal states for calibration. Factory calibration and calibration error
signals.
Flex Curves
Flex curve status for A, B, C and D user curves. (0) if it is not configured,
(1) if it is configured. To configure a flex curve go to “
Setpoint>System
Setup>Flex Curves
” menu.
System Info
This screen can monitor the system parameters and the internal status of
the Relay operative system. Not enabled by default, password required
Records Status
Information related to the different records stored in the Relay, such as:
Fault reports, control events, oscillography, data logger, demand, energy,
and breaker maintenance.
SNTP-IRIG-B
Information related to synchronization via IRIG_B or SNTP
CAN Open
Information related to OPENcan protocol
CONTROL
ELEMENTS
Frequency
Status signals (pickups and operations) for under and overfrequency
units.
Autoreclose
Status signals for autoreclose function (79). Close signal, recloser status
(ready, lockout, etc), block signals after each shot.
Breaker Failure
Status signals for breaker failure function (50BF).
VT Fuse Failure
Fuse failure detection signal.
Setting Groups
Status signals (activations and blocks) for the relay setting group change.
By default the “setting group” setting is disabled and all the grouped
elements can be enabled at the same time.
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...