5.5.4.6 LOGIC FOR BLOCKING PROTECTION FUNCTIONS DURING THE RECLOSING CYCLE
The W650 autoreclose generates a series of internal signals that allow performing block logics for Protection elements
during the reclosing cycle. These signals are blocks after autoreclose shots (
BLK AFTER SHOT
). For example, if the user
wants to block a protection element during the complete reclosing cycle, it is necessary to configure a signal as an OR of
the four blocking signals provided after each reclosing cycle in the logic configuration tool
Setpoint > Logic Configuration
,
and then use it to block the desired protection elements at
Setpoint > Relay Configuration > Protection Elements
.
Figure 5–18:shows an example of the logic configuration for the block signal during the reclosing cycle.
Figure 5–18: BLOCK SIGNAL DURING THE RECLOSING CYCLE
Figure 5–19: shows an example of the autoreclose initiation and protection element block signals after the different trips.
The autoreclose initiate signal is configured to the relay general trip that corresponds to virtual output 83 configured in the
logic configuration tool, and a physical contact to generate an external autoreclose initiation.
In the example shown on the figure, the 50PH element block signal is configured as a combination of block by digital input,
block by non-trip permission of the directional element, and finally the element will remain blocked during the reclosing
cycle. This means that only the first trip can be executed by the phase instantaneous overcurrent element; after the first
reclose trip, the element will remain blocked until the end of the cycle.
Figure 5–19: CONFIGURATION EXAMPLE OF THE RECLOSE INITIATION AND BLOCK SIGNALS
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...