12-4
W650 Wind Generator Protection System
GEK-113032A
12.1 EXAMPLE 1: COMMUNICATION & PROTECTION SETTINGS PROCEDURE
12 APPLICATION EXAMPLES
12
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
LEDS
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OPERATIONS
Select
Operation 0
Command Text
Reset C Output 00
Interlock Type
None
Interlocks
---
Final State Type
None
Final States
---
Frontal Key
F1
Contact Input
None
Virtual Output
None
Time Out
500 (default)
MMI
---
Com1
---
Com 2
---
ETH-Master 1
---
ETH Master 2
---
ETH Master 3
---
ETH Mastef 4
---
Under
SETPOINT
⇓
RELAY CONFIGURATION
⇒
OSCILLOGRAPHY
12.1.4 TEST
Apply 7.5 A in phase A (terminals B1-B2) until contact 00 on Board F operates (terminals F19-F21 should be and remain
closed), and LED 5 should be lit. Check that operating time is in the order of 1.7 seconds.
Remove current from terminals B1-B2
Press pushbutton F1 and check that contact 00 on Board F has been open.
Check that LED 5 in the front of the relay has been turned off.
Repeat the process for phase B (terminals B3-B4) and for phase C (terminals B5-B6)
Under
Actual
⇓
Waveform Capture
menu retrieve the last oscillography recording stored, open it using GE_OSC program
and check that the two digital signals as well as the current signal were kept.
SELECT
NAME
SOURCE
Led 5
C Output Op 00
C Output_00_00
SELECT
NAME
SOURCE
Digital Channel 1
C Output Op_00_00
C Output Oper_00_00
Digital Channel 2
C Output_00_00
C Output_00_00
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...