B-100
W650 Wind Generator Protection System
GEK-113032A
B.7 MEMORY MAP
APPENDIX B
B
ADDRESS BIT
NAME
FORMAT STEP MODE LENGTH MISCELLANEOUS
Ajustes Unidad Direccional de Tierra Sensible Grupo 1 - Sensitive Ground Directional 1
0x2E59
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E5A
MTA
F003
1
R/W
2
[-90 , 90] Deg
0x2E5C
Direction
F012
1
R/W
1
0=REVERSE
1=FORWARD
0x2E5D
Block
Logic
F012
1
R/W
1
0=PERMISSION
1=BLOCK
0x2E5E
Pol V Threshold
F003
1
R/W
2
[0 , 500] V
0x2E60
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E73
Confirmation
address
W
1
Ajustes Unidad Direccional de Tierra Sensible Grupo 2 - Sensitive Ground Directional 2
0x2E74
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E75
MTA
F003
1
R/W
2
[-90 , 90] Deg
0x2E77
Direction
F012
1
R/W
1
0=REVERSE
1=FORWARD
0x2E78
Block
Logic
F012
1
R/W
1
0=PERMISSION
1=BLOCK
0x2E79
Pol V Threshold
F003
1
R/W
2
[0 , 500] V
0x2E7B
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E8E
Confirmation
address
W
1
Ajustes Unidad Direccional de Tierra Sensible Grupo 3 - Sensitive Ground Directional 3
0x2E8F
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2E90
MTA
F003
1
R/W
2
[-90 , 90] Deg
0x2E92
Direction
F012
1
R/W
1
0=REVERSE
1=FORWARD
0x2E93
Block
Logic
F012
1
R/W
1
0=PERMISSION
1=BLOCK
0x2E94
Pol V Threshold
F003
1
R/W
2
[0 , 500] V
0x2E96
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2EA9
Confirmation
address
W
1
Ajustes Demanda - Demand
0x2F07
Demand
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x2F08
CRNT Demand Method
F012
1
R/W
1
0=THERMAL EXPONENTIAL
1=BLOCK
INTERVAL
2=ROLLING
DEMAND
0x2F09
POWER Demand Method
F012
1
R/W
1
0=THERMAL EXPONENTIAL
1=BLOCK
INTERVAL
2=ROLLING
DEMAND
0x2F0A
Demand Interval
F012
1
R/W
1
0=5 Minutes
1=10
Minutes
2=15
Minutes
3=20
Minutes
4=30
Minutes
5=60
Minutes
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...