12-6
W650 Wind Generator Protection System
GEK-113032A
12.2 EXAMPLE 2: TOC PROT RECLOSING SETTINGS PROCEDURE
12 APPLICATION EXAMPLES
12
12.2.4 PROCEDURE TO SET THE RECLOSER
Under
SETPOINT
⇓
PROTECTION ELEMENTS
⇒
⇓
OTHER FUNCTIONS
⇒
⇓
RECLOSER
12.2.5 PROCEDURE TO SET THE SYNCHRO CHECK
Under
SETPOINT
⇓
PROTECTION ELEMENTS
⇒
⇓
OTHER FUNCTIONS
⇒
⇓
SYNCHROCHECK
The synchrocheck function and its permission to close is a condition in the present exercise to allow the recloser to give the
different programmed shots. Should not this condition be required these settings are non relevant, but if does like in the
present case the synchrocheck function must be set as follows
Additional Comments on Scheme
The programmed operation of a TOC protection with reclosing and synchrocheck features for the W650 relay is shown in
Figure 12–1: Some conclusions follows:
The recloser cycle ends at lockout status since a permanent fault remains after two unsuccessful reclosing trials.
The holding time for reclosing conditions can be very low since the processor internal time to check them is instantaneously
if they are present at this moment. Depending in the application reclosing conditions might come later especially when
commands are sent from dispatching center. If does then this timing must be set properly.
NAME
VALUE
Function
Enabled
Max. Number of shots
2
Dead Time 1
2.0s
Dead Time 2
4.0s
Dead Time 3
---
Dead Time 4
---
Reclaim Time
0.05s
Condition Permission
Enabled
Hold Time
0.1s
Reset Time
1.9s
NAME
VALUE
Function
Enabled
Dead Bus Level
10V
Live Bus Level
50V
Dead Line Level
10V
Live Line Level
50V
Max. Volt Difference
10
Max. Angle Difference
10º
Max. Freq. Difference
20mHz
Breaker Closing Time
0.07s
DL-DB Function
Disabled
LL-DB Function
Disabled
DL-LB Function
Disabled
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...