11-16
W650 Wind Generator Protection System
GEK-113032A
11.12 DIRECTIONAL ELEMENTS (67P, 67N, 67G, 67SG)
11 COMMISSIONING
11
11.12.4 67SG ELEMENT
Activate only protection elements 50SG and 67SG and set the relay as follows:
Configure one of the outputs to be activated only by unit 50SG.
Apply the following tests:
67SG SETTINGS
50SG SETTINGS
Function
ENABLED
Function
ENABLED
MTA
-45 Deg
Input
PHASOR (DFT)
Direction
FORWARD
Pickup Level
0.50 A
Polarization
VO
Trip Delay
0.30
Block Logic
PERMISSION
Reset Delay
0.00
Pol V Threshold
10 V
ELEMENTS
PHASE UNDER TEST
POLARIZATION PHASE
ELEMENT TRIP
CHANNE
L
MAGNITUDE
CHANNEL
MAGNITUDE
MOD
ARG
MOD
ARG
50SG/67SG
ISG
2 A
0º
VI
60 V
0º
NO
60 V
180º
YES
VII
0 V
0º
VIII
0 V
0º