GEK-113032A
W650 Wind Generator Protection System
5-103
5 SETTINGS
5.6 INPUTS/OUTPUTS
5
Table 5–84: SUPERVISION ALGORITHM WITH DOUBLE VOLTAGE SUPERVISION SCHEME
There is a possibility to monitor the trip circuit continuity not only via its auxiliary contact 52/a, but also with auxiliary contact
52/b. This avoids the need to install a resistance in parallel with auxiliary 52/a. The correct connection is shown on Figure
5–30:
The circuit works in a similar way to the one described in the previous section, but it uses both supervision inputs F15-F16
and F17-F18.
The advantage in this case is that circuit supervision with 52 open is more complete, as input V 52/b is used through
contact 52/b, (that is closed when the breaker is open).
We must point out that in this scheme, the tripping contact, shown in the example as the W650 trip relay, can be the one in
the relay (terminals F35 and F36), or be provided by another protection or by the parallel of several protections. This
provides high flexibility in the use of this circuit.
The battery voltage can also be monitored, by using one of the standard digital inputs.
STATUS OF INVOLVED ELEMENTS
INPUTS TO 650
DECISION
CIRCUIT
STATUS
OUTPUT
STATUS
(F35-F36)
BREAKER STATUS
OPERAND
CONT IP_X_CC11
(VA_COIL2)
V 52/A (F15-F16)
OPERAND
CONT IP_X_CC12
(VB_COIL2)
V 52/B (F17-F18)
OPERAND
CONT IP_X_CC16
(SUP_COIL2)
Healthy
Open
52 closed
ON
OFF
ON
Healthy
Open
52 open
ON
ON
ON
Healthy
Closed
52 closed
OFF
OFF
ON (if t < 500 ms)
OFF (if t > 500 ms)
Healthy
Closed
52 open
OFF
ON
ON (if t < 500 ms)
OFF (if t > 500 ms)
Defective
Open
52 closed
OFF
OFF
OFF (500 ms delay)
Defective
Open
52 open
OFF
OFF
OFF (500 ms delay)
Defective
Closed
52 closed
OFF
OFF
OFF (500 ms delay)
Defective
Closed
52 open
OFF
OFF
OFF (500 ms delay)
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...