GEK-113032A
W650 Wind Generator Protection System
7-21
7 IEC 61850 PROTOCOL
7.2 IEC 61850 PROFILE FOR W650
7
NDRDIR: 3 NEUTRAL DIRECCIONAL ELEMENTS.
RDIR CLASS
Attribute
Name
Attr.
Type
Explanation
M/O
Notes
RDIR
Directional Element
DATA
ATTRIBUTE NAME
Common Logical Node Information
Mod
geModINC
Mode
M
Beh
geINS
Behaviour
M
Health
geINS
Health
M
NamPlt
geLPL
Name plate
M
Status Information
Dir
geNeutACD
Direction
M
Op
geNeutACT
Operate
P
Neutral Dir OP
Blk
geNeutACT
Block
P
Neutral Dir Block
BlkIn
geNeutACT
Neutral Dir Blk Inp
P
Neutral Dir Blk Inp
Settings
ChrAng
geFloatASG
Characteristic Angle
O
(-90, 90) MTA
BlkValV
geIntASG
Minimun operating current
O
(0, 500) Pol V Threshold
PolOpMod
geING_3
Direction
P
(Forward, Reverse)
BlkMod
geING_4
Block Logica
P
(Permission, Block)
RDIREna
geSPG
Function Permission
P
(Enable, Disable)
PolQty
geING_5
Polarisation
O
(VO,IP,VO+IP,VO*IP)
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...