5-130
W650 Wind Generator Protection System
GEK-113032A
5.9 LOGIC CONFIGURATION (PLC EDITOR)
5 SETTINGS
5
5.9.6 EXAMPLE OF APPLICATION
In this section a simple logic application is described step by step, a logic is such that keeping one digital input activated,
several outputs will be activated and deactivated in a time window (outputs will remain activated for 200 ms and
deactivated for 5 ms). See the following figure:
Figure 5–48: LOGIC EXAMPLE
Go to the main menu and select
File >New project
, create a new project and select an input in the icons toolbar on the top
of the window.
This input will be selected as a digital input among the several options for inputs that can be selected.
This input is the SET input for the first timer to launch the output activation signal. Click on the icon related to the timer
to insert the timer on the project. The timer has three inputs (S=set, R=reset and T=timing input)
The reset signal of the first timer is a virtual output called output_deactivation that has been created as an output of another
second timer. This signal is selected as an output
The timing signal for the first timer is a mask provided by the application, in which the time in milliseconds must be entered
in order to configure the timer time delay.
After creating the first timer, the second one for output deactivation is made. The set signal will be the virtual output created
as an output of the first timer (VO_100_OUTPUT_ACTIVATION), the reset signal will be the output of the second timer
(VO_100_OUTPUT_DEACTIVATION), the time delay is set as 200 ms.
Once the timing logic (timer 1 + timer 2) has been created, the activation signal (VO_100_OUTPUT_ACTIVATION) is linked
to several virtual outputs. Therefore, virtual outputs (VO_102_OUTPUT_1, VO_103_OUTPUT_2, VO_104_OUTPUT_3,
VO_105_OUTPUT_4) will be activated if the CONT IP_G_CC1(CC1) variable is set to 1. Once the
VO_100_OUTPUT_ACTIVATION is active, it will be deactivated after 200 ms, and will remain deactivated for 5 seconds.
This process will be repeated while the digital input is active.
To finish the process the logic must be compiled (
Run >Compile
) and the equations sent to the relay (
Run >Send
Equations to relay
) to start working with the new logic.
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...