W650 Wind Generator Protection System
GEK-113032A
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.4.4 OSCILLOGRAPHY FILES RETRIEVAL
Oscillography files can be retrieved using the EnerVista 650 Setup software, or the web server at “http:\\relay IP address”.
To obtain the oscillography records using the EnerVista 650 Setup software, go to “
Actual>Records>Waveform capture
”.
The top of the window shows the number of the last oscillography record stored by the device (Newest Record Number),
followed by the maximum number of oscillos available (Available Records in Device). Clicking on the “View header” button,
the system will show the header of the record selected at “Select Record”.
Clicking on the “Download” button, the three files (*.DAT, *.HDR, *.CFG) that form the oscillography record in the
COMTRADE standard will be retrieved, and they will be viewed automatically if the GE-OSC software is installed in the
computer. Retrieved oscillographies can be viewed using any Comtrade viewer. The EnerVista 650 Setup software stores
by default oscillography records in the folder “.\EnerVista 650 Setup\files\osc”, in the same directory where the program is
installed. The file names are “OSCxxx.DAT”, “OSCxxx.CFG”, “OSCxxx.HDR”, where xxx is the corresponding record
number. The oscillography retrieval can be done using serial communication (ModBus RTU) or Ethernet (ftp, tftp).
5.2.5 DATA LOGGER
The W650 data logger can store information of up to 16 analog channels, among all channels available in the relay, with a
sampling rate selectable by setting. The memory of the data logger is fixed, 64 Kbytes. Two bytes are needed per channel.
The selected channels will take all the available memory space. Therefore, the storage days will depend on the selected
number of channels and sampling rate.
5.2.5.1 DATA LOGGER SETTINGS
Data logger settings can be found at “
Setpoint>Product Setup>Data Logger
”.
Table 5–14: DATA LOGGER SETTINGS
Function permission (Function):
This must be enabled to start storing information.
Data Logger Rate:
the data logger can be configured in rates of 1 second, and 5, 10, 15,
20, 30 and 60 minutes
Data Logger Analog Channel X (Data Logger Chnl X):
Analog Channels programmable in the data logger. The
X
value
has a range from 0 to 16.
Any setting change in the Data Logger will erase all the stored information.
SETPOINT > PRODUCT SETUP > DATA LOGGER
Setting Description
Name
Default Value
Step Range
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Data logger Rate
Data Logger Rate
1 s
N/A
[1 s, 5 min, 10 min, 15 min, 20 min, 30 min, 60 min.]
Data Logger analog channels X
Data Logger Chnl X
None
N/A
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...