11 COMMISSIONING
11.8 INPUTS AND OUTPUTS
11
11.8INPUTS AND OUTPUTS
During all tests, the screw on the rear of the relay must be grounded.
11.8.1 DIGITAL INPUTS
During this test, the user will determine the activation/deactivation points for every input in the relay for the set voltage value
of 30 Volts.
Verify that the error does not /- 10% (+10% on activation, -10% on deactivation)
Default board settings for the input test can be modified in EnerVista 650 Setup software in:
Settings>Inputs/Outputs>Contact I/O>Board X
X, will be substituted by the corresponding board:
F for board in first slot
G for board in second slot
Test settings for mixed board (type 1:16 inputs and 8 outputs) :
The inputs test is completed by groups of 8 inputs, as this type of board has 2 groups of 8 inputs with the same common.
For the first 8 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 8 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC16) must also be set to POSITIVE.
Test settings for mixed board (type 2: 8 digital inputs, 4 blocks for supervision and 8 outputs) :
The inputs test is completed by groups of 4 inputs, as this type of board has 2 groups of 4 inputs with the same common.
For the first 4 inputs, the voltage threshold setting is determined by Voltage Threshold A. For the next 4 inputs, the setting
is Voltage Threshold B. Inputs (or contact converters, CC1 – CC8) must also be set to POSITIVE.
If the relay incorporates more input modules, this test must also be applied to them.
I/O BOARD TYPE 1 (MIXED)
Voltage Threshold A_X
30 V
Voltage Threshold B_X
40 V
Debounce Time A_X
5 ms
Debounce Time B_X
5 ms
Input Type_X_CC1 (CC1)
POSITIVE
...
...
Input Type_X_CC16 (CC16)
POSITIVE
I/O BOARD TYPE 2 (SUPERVISION)
Voltage Threshold A_X
30 V
Voltage Threshold B_X
40 V
Debounce Time A_X
5 ms
Debounce Time B_X
5 ms
Input Type_X_CC1 (CC1)
POSITIVE
...
...
Input Type_X_CC8 (CC8)
POSITIVE
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...