GEK-113032A
W650 Wind Generator Protection System
5-45
5 SETTINGS
5.4 PROTECTION ELEMENTS
5
Table 5–43: BLOCK AND OPERATION SIGNALS FOR THE PHASE DIRECTIONAL ELEMENT
Signals provided by the directional element are, block and operation signals. Signals used to block overcurrent elements
are configured at
Setpoint > Relay Configuration > Protection Elements.
Operation signals are active when operation and polarization magnitudes meet conditions given by the settings.
Block signals indicate blocked elements by an external block input or by polarization voltage loss. Using the "Block logic"
setting, the user can select how the directional element responds in case of a block. When the "Block" option is selected,
the operational signal will not be activated in a block condition. When the "Permission" option is selected, the operation
signal will be activated in a block condition.
Figure 5–7: shows the default configuration for the phase overcurrent block input. When the "Block logic" setting is set as
"Block", this input will be active in case of a block in the directional element, avoiding any phase overcurrent trip.
When the "Block logic" setting is set as "Permission", the phase overcurrent element is enabled to trip as the block input is
not active in case of polarization voltage loss.
BLOCK AND OPERATION FOR 67P
PHASE DIR1 BLOCK A
PHASE DIR1 A OP
PHASE DIR1 BLOCK B
PHASE DIR1 B OP
PHASE DIR1 BLOCK C
PHASE DIR1 C OP
PHASE DIR2 BLOCK A
PHASE DIR2 A OP
PHASE DIR2 BLOCK B
PHASE DIR2 B OP
PHASE DIR2 BLOCK C
PHASE DIR2 C OP
PHASE DIR3 BLOCK A
PHASE DIR3 A OP
PHASE DIR3 BLOCK B
PHASE DIR3 B OP
PHASE DIR3 BLOCK C
PHASE DIR3 C OP
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...