GEK-113032A
W650 Wind Generator Protection System
B-103
APPENDIX B
B.7 MEMORY MAP
B
ADDRESS BIT
NAME
FORMAT STEP MODE LENGTH MISCELLANEOUS
Ajustes Sobreintensidad Temporizada de Fases Nivel Alto Grupo 3 - Phase TOC Low 3 (cont.)
10=IAC Mod Inv
11=ANSI Ext Inv
12=ANSI Very Inv
13=ANSI Norm Inv
14=ANSI Mod Inv
15=I2t
16=Definite
Time
17=Rectifier
Curve
18=User Curve A
19=User Curve B
20=User Curve C
21=User Curve D
0x32E4
TD Multiplier
F003
1
R/W
2
[0.00 , 900.00] s
0x32E6
Reset
F012
1
R/W
1
0=INSTANTANEOUS
1=LINEAL
0x32E7
Voltage
Restraint
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x32E8
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x32FB
Confirmation
address
W
1
Ajustes Aparamenta (16 elementos) - Switchgear (16 items)
0x32FC
CONTACTS TYPE_01
F012
1
R/W
1
0=52a + 52b
1=52a
2=52b
3=NONE
0x32FD
CONTACTS TYPE_02
F012
1
R/W
1
0=52a + 52b
1=52a
2=52b
3=NONE
...
...
...
...
...
...
...
...
0x330B
CONTACTS TYPE_16
F012
1
R/W
1
0=52a + 52b
1=52a
2=52b
3=NONE
0x330C
FAIL TO OPEN 01 t
F004
1
R/W
1
[0 , 30000] ms
0x330D
FAIL TO OPEN 02 t
F004
1
R/W
1
[0 , 30000] ms
...
...
...
...
...
...
...
...
0x331B
FAIL TO OPEN 16 t
F004
1
R/W
1
[0 , 30000] ms
0x331C
FAIL TO CLOSE 01 t
F004
1
R/W
1
[0 , 30000] ms
0x331D
FAIL TO CLOSE 02 t
F004
1
R/W
1
[0 , 30000] ms
...
...
...
...
...
...
...
...
0x332B
FAIL TO CLOSE 16 t
F004
1
R/W
1
[0 , 30000] ms
0x332C
Snapshot Events SWGR 1
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x332D
Snapshot Events SWGR 2
F012
1
R/W
1
0=DISABLED
1=ENABLED
...
...
...
...
...
...
...
...
0x333B
Snapshot Events SWGR 16
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x334C
Confirmation address
W
1
Summary of Contents for Multilin W650
Page 2: ......
Page 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Page 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Page 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Page 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Page 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Page 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...