5-24
Pattern operation cycle operation completed
(TO)
Value 17:
After the seven stages of a pattern operation
have been completed, this function outputs a one-shot,
100 ms ON signal to report the completion of all stages.
Pattern operation stage number
(STG1)(STG2)(STG4)
Value 18, 19, 20:
During pattern operation, this function
reports the stage (operation process) being operated.
Pattern
Operation
Stage No.
STG1
STG2
STG4
Stage 1
on
off
off
Stage 2
off
on
off
Stage 3
on
on
off
Stage 4
off
off
on
Stage 5
on
off
on
Stage 6
off
on
on
Stage 7
on
on
on
Output Terminal
When pattern operation is not activated (i.e., no stage has
been selected), the terminals do not output a signal.
Alarm detail (AL1)(AL2)(AL4)(AL8)
Value 21, 22, 23, 24:
This function reports the operating
status of the drive protective function.
Alarm Detail
(Drive Protective Function
AL1 AL2 AL4 AL8
Overcurrent, ground fault, blown fuse
on
off
off
off
Overvoltage
off
on
off
off
Undervoltage shortage, input phase
failure
on
on
off
off
Motor 1 and Motor 2 overload
off
off
on
off
drive overload
on
off
on
off
Heat sink overheating, drive
overheating internally
off
on
on
off
External alarm input, braking resistor
overheating
on
on
on
off
Memory error, CPU error
off
off
off
on
Keypad panel communication error,
option communication error
on
off
off
on
Option error
off
on
off
on
Output wiring error
off
off
on
on
RTU communication error
on
off
on
on
Overspeed, PG disconnection
off
on
on
on
Output Terminal
Under normal operation, terminals do not output a signa
Cooling fan operating (FAN)
Value 25:
When used with H06 Cooling fan ON/OFF
control, this function outputs a signal while the cooling fan
is operating.
Retry function operating (TRY)
Value 26
: When H04 Retry operating is set to 1 or higher,
the signal is output during the retry operation, if the drive
protective function has been activated.
Universal DO(U-DO)
Value 27:
Assigning a value of 27 to a transistor output
terminal renders the terminal a universal DO terminal.
This function enables ON/OFF through the RS485 and
BUS option.
This function serves only to turn the transistor output on
or off through communication and is not related to drive
operation.
Heat sink overheat early warning (OH)
Value 28:
This function outputs an early warning signal
when the heat sink temperature (overheat detection level)
is within 10
°
C of the overtemp trip point.
2nd Freq. level detection (FDT2)
Vallue 31:
This function sets the 2nd Freq. level detection.
See the explanation of Function Code E36 and E37
Hysteresis width is same as FDT1 (E32).
2nd OL level early warning (OL2)
Value 32:
This function sets the 2nd overload early
warning. See the explanation of “overload early warning
(OL)”, E37.
Terminal C1 off signal (C1OFF)
Value 33:
This function outputs an ON signal, when the
C1 current input is smaller than 2mA.
Y1-Y5 SETTINGS WHEN SHIPPED FROM THE FACTORY
Digital Output
Value
Description
Terminal Y1
0
Operating (RUN)
Terminal Y2
1
Frequency arrival (FAR)
Terminal Y3
2
Frequency detection (FDT)
Terminal Y4
7
Overload early warning (OL)
Terminal Y5
15
Terminal AX function (AX)
Factory Setting at Shipment
E25 Y5 Ry operation mode
E 2 5
Y 5 R Y
M O D E
This function specifies whether to excite the Y5 relay at
“ON signal mode” or “OFF signal mode”
Set Value
Operation
0
At “OFF signal mode” Y5A - Y5C: OFF
At “ON signal mode” Y5A - Y5C: ON
1
At “OFF signal mode” Y5A - Y5C: ON
At “ON signal mode” Y5A - Y5C: OFF
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...