12-5
Data subject to change without notice 7/07. © 2007 GE Drives
Code
Code
0
No alarm
—-
22
Overheat, DB resistor
dbH
1
Overcurrent, during acceleration (INV output )
OC1
23
Overload, motor 1
OL1
2
Overcurrent, during deceleration (INV output )
OC2
24
Overload, motor 2
OL2
3
Overcurrent, during steady state operation
(INV output )
OC3
25
Overload, drive
OLU
5
Ground fault
EF
27
Overspeed
OS
6
Overvoltage, during acceleration
OU1
28
PG wire break
Pg
7
Over voltage, during deceleration
OU2
31
Memory error
Er1
8
Overvoltage, during steady state operation
OU3
32
Keypad error
Er2
10
DC undervoltage
LU
33
CPU error
Er3
11
Power supply open phase
Lin
34
Option comm error
Er4
14
Blown DC fuse
FUS
35
Option error
Er5
16
Output wiring error
Er7
36
PL error
Er6
17
Overheat, heat sink, inverter
OH1
37
Output wiring error
Er7
18
Overheat, outside thermal
OH2
38
RS485 comm error
Er8
19
Overheat, unit inside temp
OH3
Description
Description
Data format [11]
Capacity code
Code
Capacity (HP)
Code
Capacity (HP)
Code
Capacity (HP)
7
0.07 (spare)
2000
20
17500
175
15
0.15 (spare)
2500
25
20000
200
25
0.25
3000
30
25000
250
50
0.5
4000
40
30000
300
100
1
5000
50
35000
350
200
2
6000
60
40000
400
300
3
7500
75
45000
450
500
5
10000
100
50000
500
750
7.5
12500
125
60600
600
1000
10
15000
150
60700
700
1500
15
60800
800
Data format [12]
Index data (ACC/DEC time, display coefficient)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0: Positive (+),
Polarity 0
0
0
Index
portion
Data portion
1: Negative ( - )
0: 0.01 X
1: 0.1
X
2: 1
X
3: 10
X
001–999
(0.00–9.99)
00–999
(10.0–99.9)
100–999
(100–999)
100–999
(1000–9990)
Example: If F07 (acceleration time 1) = 20.0 s
10.0 < 20< 99.9
➞
index =1
20.0 = 0.1 X
200
➞
0400
H
+ 00C8
H
= 04C8
H
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...