5-41
H25 PID control (Feedback filter)
H 2 5
F B
F I L T E R
Setting range: 0.0 to 60.0 seconds
This filter is for feedback signal input from Terminals 12 or
C1. This filter stabilizes operation of the PID control
system. A set value that is too large, however, deterio-
rates response.
H26 PTC thermistor (mode select)
H 2 6
P T C
M O D E
Setting range:
0: Inactive
1: Active
Set this function active when the motor has a PTC
thermistor for overheat protection
Connect the PTC thermistor as shown in the figure below.
Turn on switch PTC on the control PCB. The trip mode is
activated by OH2: External thermal relay tripped.
Note:
Must be 0 setting when using 4-20mA reference or
feedback signal and the PTC switch must be off.
H27 PTC thermistor (level select)
H 2 7
P T C
L E V E L
Setting range: 0.00 to 5.00V
The voltage input to Terminal C1 is compared to the set
voltage level. If the input voltage is equal to or greater
than the set voltage, H26 PTC thermistor (Mode select)
starts.
The PTC thermistor has its own alarm temperature. The
internal resistance value of the thermistor largely changes
at the alarm temperature. The operation voltage level is
set using this change in the resistance value.
The figure above for H26 PTC thermistor (Mode select)
shows that a 250W resistor and the thermistor (resistance
value Rp) are connected in parallel. Hence, voltage Vc1 at
Terminal C1 can be calculated using the following formula:
Vc
1
X 10 [V]
250 • Rp
250 + Rp
1000+
250 • Rp
250 + Rp
The operation level can be set by bringing Rp in the Vc1
calculation formula into the following range.
Rp1 < Rp < Rp2
To calculate Rp, use the following formula:
Rp
Rp
1
+ Rp
2
[Ohm]
2
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...