12-6
Data subject to change without notice 7/07. © 2007 GE Drives
BUSY
WR RL ALM DEC ACC IL VL TL NUV BRK INT EXT REV FWD
RST 0 0 0 0
X9 X8 X7 X6 X5 X4
X3 X2 X1 REV FWD
0 0 0 0 0 0 0 0 0 0 0 Y5 Y4 Y3 Y2 Y1
Data format [13]
Pattern operation
0: FWD
1: REV
Example) If C22 (Stage1) = 10.0s R2 (10s, reverse rotation, acceleration time 2/deceleration time 2)
Since 10.0 = 0.1 X
100 > 9000
H
+ 0400
H
+ 0064
H
= 9464
H
Data format [14]
Operation command
(All bit are ON by 1)
Example If S06 (operation command) = FWD, X1 and X5 = ON
0000 0000 0100 0101
b
= 0045
H
Data format [15]
Universal output terminal
(All bit are ON by 1)
Example) If M15 (Universal output terminal)=Y1 and Y5 = ON
0000 0000 0001 0001
b
= 0011
H
Data format [16]
Operating state
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Direction
of rotation
0 Time
Index portion Data portion
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0: 1
st
ACC/DEC time
0: 0.01 X
001–999
(0.00–9.99)
1: 2
nd
ACC/DEC time
1: 0.1
X
100–999
(10.0–99.9)
2: 3
rd
ACC/DEC time
2: 1
X
100–999
(100–999)
3: 4
th
ACC/DEC time
3: 10
X
100–999
(1000–9990)
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...