4.3.11 Alarm Information
Select 7. Alarm Information (ALM INF) on the Program Menu screen. A variety of operating data at the time the latest
alarm occurred is displayed. Use UP and DOWN to switch between the nine screens of alarm information data.
60.00
1.DATA SETTING
2.DATA CHECK
3. OPR MNTR
4. I/O CHECK
5. MAINTENANCE
6. LOAD FCTR
> 7. ALM INF
60.00
OC1
Fout=xxxx.xHz
Iout=x.xxA
Vout=xxxV
TRQ=xxx%
Code of latest alarm
(High speed blinking during alarm
mode only)
Output frequency at alarm
Output current at alarm occurence
Output voltage at alarm occurence
Torque calculation value at alarm
occurence
RUN
PRG > PRG MENU
F/D > LED SHIFT
FWD
OC1
TIME=xxxxxh
EDC=xxxV
TMPI=xxxx
°
C
TMPF=xxxx
°
C
Cumulative operating hours at alarm occurence
DC link circuit voltage at alarm occurence
Temperature inside drive at alarm occurence
Heat sink temperature at alarm occurence
Fref=xxxx.xHz
xxx xx xx xx
OC1
Setting frequency at alarm occurence
Operating status at alarm occurence
FWD/REV: Rotating
IL:
Current limiting
VL:
Voltage limiting
LU:
Under voltage
TL:
Torque limiting
OC1
REM
X2 X6
FWD
X3 X7
REV
X4 X8
X1
X5 X9
SIGNAL OFF,
SIGNAL ON
Input terminal status at a alarm
occurence (terminals)
No. of communication errors at
alarm occurence: Keypad panel
No. of communication errors at
alarm occurence: RS 485
No. of communication errors at
alarm occurence: Options
OC1
NRK=xxxxx
NRR=xxxxx
NRO=xxxxx
Input terminal status at a alarm
occurence (communication)
SIGNAL OFF,
SIGNAL ON
OC1
COM
X2 X6
FWD
X3 X7
REV
X4 X8
X1
X5 X9
Output terminal status at a alarm
occurence
SIGNAL OFF,
SIGNAL ON
OC1
Y1
Y5
Y2
Y3
Y4
OC1
0/1 =xxx
xxx
-1
=xxx
xxx
-2
=xxx
xxx
-3
=xxx
xxx
Previous alarm
Before previous alarm
Two times before previous
No. of occurences
Alarm history
No. of occurences
Updated at alarm occurence. If the
cause of an alarm is the same as the
previous one, only the number og
occurences is incremented.
Multiple alarms
(Simultaneously
occuring alarms)
Alarm code
Up to four alarm codes can be dosplayed simultaneously.
OC1
5=xxx
4=xxx
3=xxx
2=xxx
Lastest alarm
PRG
FUNC
DATA
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...