4-6
Data subject to change without notice 7/07. © 2007 GE Drives
The function code consists of alphanumeric characters with unique letters assigned to each function group.
Table 4-3-1
Function Code
Function
Remarks
F00 - F42
Fundamental functions
E01 - E47
Terminal Extension Functions
C01 - C33
Frequency Control Functions
P01 - P09
Motor Parameters
H03 - H39
High Performance Functions
A01 - A18
Alternative Motor Parameters
o01 - o29
Optional Functions
Can only be selected with an option connected
To scroll the Function Select screen rapidly, use
+
or
+
to move the screen as a unit sorted
alphabetically.
Select the desired function and press
FUNC
DATA
to switch to the Data Setting screen.
On the Data Setting screen, the data values on the LCD can be increased or decreased in the smallest possible unit by
pressing
or
. Holding down
or
causes the values to increase or decrease more rapidly. Other-
wise, select the digit to be modified using
and then set data directly. When data is modified, the value before
modification will be displayed at the same time for reference purpose. To save the data, press
FUNC
DATA
. Pressing cancels
the changes made and returns control to the Function Select screen. The modified data will be effective in inverter
operation after the data has been saved by
FUNC
DATA
. If the data is not saved, there is no change to the inverter operation.
When data setting is disabled in the case of “Data protected” or “Data setting invalid during inverter running,” make the
necessary changes as indicated in Table 4-3-2 below.
Table 4.3.2
Display
Reason for No Modification
Release Method
LINK ACTIVE
Currently writing from RS-485 / RTU option to
function is being made
Send a cancel command to function writing from RS-
485 RTU. Stops a “write” operation from the link
communication option.
NO SIGNAL(WE)
The edit enabling command function is selected
using a general-purpose input terminal
For functions E01 to E09, turn data terminal 19 (edit
enabling command selection) ON
DATA PRTCTD
Data protection is selected for function F00.
Change function F00 to 0
INV RUNNING
An attempt was made to change a function that
cannot be changed during inverter operation.
Stop inverter operation
FWD/REV ON
An attempt was made to change a function that
cannot be changed with the FWD/REV command
on.
Turn FWD/REV command off
F00
DATA PRTC
F01 FREQ CMD 1
F02 OPR METHOD
F03 MAX Hz-1
F00
DATA PRTC
F01
FREQ CMD 1
F02 PPR METHOD
F03 MAX Hz-1
F42 TRQ VECTOR 1
E01
X1 FUNC
E02 X2 FUNC
E03 X3 FUNC
A18 SLIP COMP 2
F00
DATA PRTC
F01 DATA PRTC
F02 OPR METHOD
+
+
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...