5-34
H03 Data initializing
H 0 3
D A T A
I N I T
Setting rnage:
0: Disabled
1: Initializes data
This function returns all function data changed by the
customer to the original factory settings (initialization).
To perform initialization, press the STOP and ^ keys
together to set H03=1, then press the FUNC/DATA key.
The values for all functions are initialized. The set value
in H03 automatically returns to 0 following the end of
initialization.
H04 Auto-reset (Times)
H05 Auto-reset (Reset interval)
H 0 4
A U T O – R E S E T
H 0 5
R E S E T
I N T
Set the protective function release count and waiting time
from its startup to release.
Setting range:
(Count) : 0, 1 to 10
(Waiting time) : 2 to 20 seconds
When a drive protective function which invokes the retry
operation is activated, these functions release operation
of the protective function and restarts operation without
issuing an alarm or terminating output.
To disable the retry function, set H04 Retry (count) = 0.
Drive protective functions that can invoke the retry
function:
OC1, OC2, OC3:
dBH:
Overcurrent
braking resistor overheating
OV1, OV2, OV3:
OL1:
Overvoltage
Motor 1 overload
OH1:
OL2:
Heat sink overheating
Motor 2 overload
OH3:
OLU:
Drive overheating
Drive overload
internally
If the value of H04 Retry (count) is set from 1 to 10, a
drive run command is immediately entered following the
wait time set in H05 Retry (wait time) and the startup of
the retry operation. If the cause of the alarm has been
removed at this time, the drive starts without switching to
alarm mode. If the cause of the alarm still remains, the
protective function is reactivated according to the wait
time set in H05 Retry (waiting time). This operation is
repeated until the cause of the alarm is removed. The
restart operation switches to alarm mode when the retry
count exceeds the value set in H04 Retry (count). The
operation of the retry function can be monitored from
terminals Y1 to Y5.
WARNING
When the retry function is selected, operation will
automatically restart, depending on the cause of
the stop. (The machine should be designed to
ensure safety during a restart.) When the retry
function is selected, GE start software
(F02 set 3 or 4) does not work.
H06 Fan stop operation
H 0 6
F A N
S T O P
Setting range:
0: ON/OFF control disabled
1: ON/OFF control enabled
This function specifies whether ON/OFF control for the
cooling fan is automatic. While power is applied to the
drive, the automatic fan control detects the temperature of
the heatsink and turns the fan on or off. When this control
is not selected, the cooling fan rotates continuously.
The cooling fan operating status can be monitored from
terminals Y1 to Y5.
H07 ACC/DEC (Mode select) pattern
H 0 7
A C C
P T N
Setting range:
0: Inactive (linear acceleration and
deceleration)
1: S-shape acceleration and deceleration (mild)
2: S-shape acceleration and deceleration (sharp)
3: Curvilinear acceleration and deceleration
This function selects the acceleration and deceleration
pattern.
H: High Performance function
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...