2-12
Data subject to change without notice 7/07. © 2007 GE Drives
Digital input
FWD
Forward operation /
Used for forward operation (when FWD-CM is on) or
Stop command
deceleration and stop (when FWD-CM is opened)
REV
Reverse operation /
Used for reverse operation (when REV-CM is on) or
Stop command
deceleration and stop (when REV-CM is opened)
X1
Digital input 1
The coast-to-stop command, external alarm, alarm reset, multi-
step frequency selection, and other functions (from an external
circuit) can be assigned to terminals X1 to X9. For details, see
"Setting the Terminal Functions E01 to E09" in Section 5.2
Function Explanation.
<Specifications of digital input circuit>
X2
Digital input 2
X3
Digital input 3
X4
Digital input 4
X5
Digital input 5
X6
Digital input 6
X7
Digital input 7
X8
Digital input 8
X9
Digital input 9
P24
Control Unit power Supply
+24VDC power supply for control input. Maximum output current 100mA
PLC
PLC signal power
Used to connect PLC power supply for output signals; rated nominal
voltage = 24 VDC (22 to 27 V DC range) at sink logic operation.
CM
Digital input common
Common terminal for digital input signals and P24
Analog output
FMA
Analog monitor
Outputs monitor signal using analog DC voltage 0 to +10V DC.
The signal indicates one of the following:
(11: common
- Output frequency (before slip compensation)
terminal)
- Load factor
- Output frequency (after slip compensation)
- Power consumption
- Output current
- PID feedback value
- Output voltage
- PG feedback value
- Output torque
- DC link circuit voltage
* Connectable impedance: min. 5k ohms
Pulse output
FMP
Frequency monitor
Outputs a monitor signal using the pulse waveform.
(CM: common
(pulse waveform output)
This signal has the same function as the FMA signal.
terminal)
Item
min.
typ.
max.
Operating voltage
ON
0V
–
2V
OFF
22V
24V
27V
Maximum load current
ON
–
3.2mA 4.5 mA
Leakage current
OFF
–
–
0.5 mA
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...