12-1
Data subject to change without notice 7/07. © 2007 GE Drives
The serial interface supports operation, configuration and monitoring of drive functions through an EIA/RS485 connec-
tion. The serial interface is based on Modbus RTU protocol. This protocol allows the drive to function as an RTU slave
on an industrial network.
12.1 Transmission Specification
Item
Specification
Physical level
EIA/RS485
Transmission distance
500 m max.
Number of nodes
32 total
Transmission speed
19200, 9600, 4800, 2400 [bits/s]
Transmission mode
Half duplex
Transmission protocol
Modbus RTU
Character code
Binary
Character length
8 bits
Error check
CRC
12.2 Connection
Connection method
Use shielded wire and connect to the control terminals (DX-, DX+ and SD). A termination resistor should be added
between the data lines on the each end of the network. The value of the termination resistor depends on the character-
istic impedance of the cable. A common value for termination resistors is 120 ohms.
Control terminals
Terminal
marking
Terminal name
Function description
DX+
RS485 communication data (+)
Input/output terminals for RS485
DX-
RS485 communication data (–)
communication.
SD
Cable shield
Electrically floating
12.3 Serial Interface Configuration
Drive function codes H30 to H39 are used to configure the serial interface parameters, such as device address, baud
rate and error response.
12.4 Modbus RTU Functions
The following RTU functions are supported. The maximum number of consecutive parameters for function 03 and 16
messages is 16.
Code
Description
03
Read Holding Registers (16 registers maximum)
06
Preset Single Register
16
Preset Multiple Registers (16 registers maximum)
12. RS485 Modbus RTU Serial Communications
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...