Data subject to change without notice 7/07. © 2007 GE Drives
12.5 Drive Function Code Access
All of the drive function codes are accessible through the RS485 serial interface. Drive function codes are mapped to
RTU holding registers. A drive function code RTU address is 2 bytes in length. The high byte corresponds to a code that
represents the drive parameter sort (F–M). The low byte corresponds to the drive parameter number within the sort (0 -
99).
Code
Sort
Name
Code
Sort
Name
0
F
Basic function
5
A
Motor 2 function
1
E
Terminal function
6
o
Option function
2
C
Control function
7
S
Command/function data
3
P
Motor 1 function
8
M
Monitor data
4
H
High level function
For example, drive function code M11, output current, is addressed as RTU parameter number 080B hexadecimal or
2059 decimal.
12.6 Command and Monitor Data Registers
The command and monitor function codes are used to control the operation of the drive and monitor the status variables
through the serial interface. The command and monitor function codes are not
accessible from the drive keypad
interface. Drive parameter H30 and digital input signal LE must be enabled to operate the drive from the Modbus
interface. If LE is not assigned to a digital input (X1-X9), the signal will default to ON.
Frequency Setting Registers
Read/
Data
Address Code
Name
Unit
Variable Range
Min. unit
Write
Format
1793
S01
Frequency command
-
-20000–20000
(max. frequency at ± 20000)
1
R/W
2
1797
S05
Frequency command
Hz
0.00–400.00
0.01
R/W
5
Note:
1) If both S01 and S05 are set, the drive will ignore the setting of S05.
2) A data setting that exceeds the setting range is possible, but the actual action will be limited by the drive configura-
tion.
Operation command data Registers
Address Code
Name
Unit
Variable Range
Min. unit
Read/
Data
Write
Format
1798
S06
Operation command
-
Refer to the data format [14]
-
R/W
14
1799
S07
Universal Do
-
Refer to the data format [15]
-
R/W
15
1804
S12
Universal Ao
-
-20000–20000
1
R/W
2
(100% output at ± 20000 )
Note:
1) Since X1–X9 are configurable input commands, it is necessary to set the functions by E01–E09.
2) The alarm reset is executed, when RST signal changes from ON to OFF even if there are no alarms.
3) Universal Do is a function that utilizes the drive’s digital outputs via communication.
Function data Registers
Address Code
Name
Unit
Variable range
Min. unit
Read/
Data
Write
Format
1800
S08
Acceleration time F07
s
0.1–3600.0
0.1
R/W
3
1801
S09
Deceleration time F08
s
0.1–3600.0
0.1
R/W
3
1802
S10
Torque limit level 1
(driving) F40
%
-20.00 –200.00, 999
1
R/W
5
1803
S11
Torque limit level 2
(braking) F41
%
0.00, 20.00–200.00, 999
1
R/W
5
Note:
1)
The writing of data out of range is treated as out of range error.
2)
Use a value of 7FFF
H
to enter 999 for torque limit functions.
high byte
low byte
drive parameter sort code
drive parameter number
Summary of Contents for AF-300 P11
Page 1: ...GE Consumer Industrial AF 300 P11 User s Guide ...
Page 35: ...2 18 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 37: ...3 2 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 53: ...4 16 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 62: ...5 9 Frequency Setting Block Diagram ...
Page 66: ...5 13 ...
Page 84: ...5 31 Notes ...
Page 99: ...5 46 Notes ...
Page 109: ...7 8 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 115: ...8 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...
Page 123: ...10 6 Data subject to change without notice 7 07 2007 GE Drives Notes ...