Installation Instructions
Page 76 Panda_AGT-DC_5000_12V_s01285_Operation manual.R03 - Chapter 5: Installation Instructions
22.3.11
5.7.2 The speed sensor
Speed sensor
Fig. 5.7.2-1: Speed sensor
Installation of the speed sensor
The speed sensor tip must have between 0.3 to 0.8mm of clearance (air gap) from the gear tooth
tips. In order to achieve this clearance: the speed sensor tip should be aligned with the tip of a
gear tooth and screwed in until it touches the tip of the tooth. (ATTENTION! Ensure that when
inserting the sensor, that the sensor tip is not screwed into the root of the gear tooth). The
screw is subsequently turned anticlockwise by half a turn (0.3 to 0.8mm) and held by a counter
nut.
1. Speed sensor on threaded seat
2. Engine Flywheel (with gear teeth)
3. Generator housing
4. Retention/tightening nut
1. Speed sensor on threaded seat
2. Engine Flywheel (with gear teeth)
Fig. 5.7.2-2: Installation speed sensor
5.7.3 Electronic starter control unit
If there is an automatic starting requirement and if the remote control panel is switched off, then
this automatic starting requirement is ignored. Automatic starting is only possible if after switching
on of the remote control panel the automatic starting requirement takes place.
2
3
1
4
1
1
2
2