Tables
Page 114 Panda_AGT-DC_5000_12V_s01285_Operation manual.R03 - Chapter 8: Tables
22.3.11
MOTOR TURNS OVER BUT DOES NOT START
Cause
Solution
Stop solenoid valve not opening.
Check wire connections and circuitry to solenoid valve.
(ref. DC wiring diagram: Relay K2, Fuse)
Fuel pump does not operate.
Check fuel-filter and pump: clean if necessary.
Lack of fuel.
Check fuel supply.
Glow-plugs not working correctly.
Check glow plugs and heating time.
Too much air in fuel lines.
Test fuel system for leakage. Bleed air from fuel system
(refer to section "Air-bleeding of the Fuel System").
Fuel filter blocked.
Replace fuel filter.
Low compression pressure.
See Kubota motor-manual.
MOTOR DOES NOT TURN OVER AT THE NORMAL SPEED DURING THE STARTING PROCESS
Cause
Solution
Starter battery voltage insufficient.
Check battery.
Damaged bearing(s) piston (seized).
Repairs need to be carried out by Kubota-Service.
(refer to Kubota motor-manual)
Cooling water in combustion chamber.
1. Turn generator "OFF" at control panel.
2. Remove the glow plug (see Kubota-manual).
3. Rotate the motor by hand carefully.
4. Check if there is water in the oil and change both oil
and filter if necessary.
5. Determine cause for excess water in the combustion
chamber. The excess water can be caused by a defec-
tive air vent in the cooling water system, which should
be checked and cleaned, or replaced if faulty.
MOTOR RUNS IRREGULARLY
Cause
Solution
Faulty centrifugal injector governor.
Have the centrifugal governor inspected by a Kubota-
Service technician.
Too much air in fuel lines.
Bleed air from fuel system.