Tables
22.3.11
Panda_AGT-DC_5000_12V_s01285_Operation manual.R03 - Chapter 8: Tables Page 113
8. Tables
8.1
Troubleshooting
GENERATOR OUTPUT VOLTAGE TOO LOW
If the generator delivers less than 12V current ("undervoltage"), there can be various reasons for this:
Cause
Solution
Generator is overloaded.
Reduce the electrical load. (Switch off load)
Motor is not reaching the rated rpm.
Refer to "motor faults" section.
Actuator is not in maximum position.
Check actuator resp. renew.
VCS-voltage controler defective or wrong adjusted.
Check resp. renew.
GENERATOR VOLTAGE TOO HIGH (MORE THAN 12V)
The following reasons may be the cause, if the generator delivers more than 12V ("overvoltage"):
Cause
Solution
The engine is running at the wrong speed.
Check the speed of the motor with a rev or frequency
counter, set the correct speed.
VCS-voltage controler defective or wrong adjusted.
Check resp. renew.
Actuator defective.
Check resp. renew.
GENERATOR VOLTAGE FLUCTUATES
Cause
Solution
1. Fault or defect on the load side.
2. A motor fault.
1. Check if the power requirement of the load fluctua-
tes.
2. See "Motor running irregularly".
MOTOR DOES NOT TURN OVER WHEN STARTING
Cause
Solution
Battery main switch is switched off.
Check the position of the battery main switch, if neces-
sary switch on..
Battery voltage not sufficient.
Check that connection is firm and whether corrosion
has occurred..
Starting current fault.
The voltage of full batteries fall to a maximum of 11V.
The wiring is severed if the voltage does not drop. The
battery is discharged if the voltage drops further.