DROP IN THE SPEED OF THE MOTOR
Cause
Solution
Too much oil.
Drain oil.
Lack of fuel.
Check fuel supply system:
- fuel filter, renew if necessary
- check fuel pump
- check fuel lines (bleed if necessary)
Lack of intake air.
Check air intake paths.
Check and clean air filter (and intake muffler if instal-
led).
Generator overloaded by too many load.
Reduce the electrical load (switch off load).
Generator overloaded by over-energizing.
Check that the proper capacitor type is installed and
that they are connected correctly.
Defective generator (windings, bearings, or other).
Generator must be sent to manufacturer for repair of
damaged bearings or winding.
Damaged engine.
Repair of bearing damage, etc., by Kubota-Service.
MOTOR SWITCHES ITSELF OFF
Cause
Solution
Fuel solenoid valve or throttle shut solenoid is not swit-
ching off.
Check wire connections to solenoid. Check valve
functions as in the "Inlet Fuel Solenoid Valve" or in the
trottle shut off solenoid sections. Replace if necessary.
MOTOR STOPS BY ITSELF
Cause
Solution
Lack of fuel.
Check fuel supply system.
Excess heat in cooling system (thermo switch tripped)-
lack of cooling water. Is indicated on the remote control
panel.
Check cooling water system flow: water pump, inlet
water filter, extra heat exchanger coolant flow.
Lack of oil (oil pressure sensor tripped).
Check oil-level and if necessary top up.
Check motor's oil-pressure and have repaired by
Kubota-Service if necessary.