General operation
Seite/Page 144 Panel Generator Control P6+ RE0703_Kunde_eng.R06.1 - Kapitel/Chapter 11: General operation
22.3.11
11.7.3 Terminal connections
Connection for the automatic adapter X2 (row with odd pin numbers // I/O viwe from operating panel)
Fig. 11.7.3-1: Terminal connections automatic adapter
Pin-no.
Pin-name
I / O
Description
1
VBF
O
power (operation voltage behind fuse)
3
GND
O
power supply - (ground)
5
VBFS
O
power switched (voltage Pin 1, with panel switched on)
7
12V
O
power switched, at 12V-operation over closed soldered jumper J101 connected with
VBFS (at optional 24V-operation: VBFS over internal voltage regulator at 12,9V regulated)
9
GND
O
power supply - (ground)
11
GND
O
power supply - (ground)
13
/Heat-signal
I
Heat is active, if the input is switched to GND
15
/Start-signal
I
Start is active, if the input is switched to GND
17
GND
O
power supply - (ground)
19
GND
O
power supply - (ground)
21
GND
O
power supply - (ground)
23
GND
O
power supply - (ground)
25
GND
O
power supply - (ground)
27
/Stop-signal
I
The Fuel pump signal is switched off, as long as the input is switched to GND, (also when star-
ting)
29
FP-Int
O
Fuel pump signal internally, decoupled over diode from external signal
31
/Fault-signal
O
Output is switched to GND, if an error is present (inputs 3, 4, 5, 11 and 12, if configured and ge-
nerally for 2s, after switching on the panel)
33
GND
O
power supply - (ground)