Installation Instructions
Page 78 Panda_AGT-DC_5000_12V_s01285_Operation manual.R03 - Chapter 5: Installation Instructions
22.3.11
Electrical fuses
It is absolutely essential that the electrical system installation is inspected by a qualified electrical
technician. The generator should have its own AC input electrical fuses. The fuses should be
sized such that the rated current of the generator on each of the individual phases is not excee-
ded by more than 25%.
Data for gensets with power output greater than 30kW on request!
The fuses must be of the slow type. A 3-way motor protection switch must be installed to protect
the electrical motor.
Required cable cross-sections
The following recommended electrical cable dimensions (cross sections) are the minimum requi-
red sizes for a safe installation. (see section 8.2, “Technical Data Engine,” on page 117.)