Generator Failure
Page 112 Panda_AGT-DC_5000_12V_s01285_Operation manual.R03 - Chapter 7: Generator Failure
22.3.11
To prevent such a shut down period the generator can be started in the normal way while pres-
sing the Failure bypass button is depressed. This by-passes any faults thus allowing the genera-
tor to run.
Before pressing the bypass button and starting the generator, a manual check of the engine oil
level must be carried out as it is possible that the oil pressure switch caused the generator to cut
out. Once it has been ascertained that the reason for the engine cutting out is over- heating and
not lack of oil, the generator can be started and run for several minutes without load, so that the
engine is returned to normal operating temperature.
CAUTION:
If temperature is the reason for the generator cutting out when it is running under load, then an
immediate investigation should be made to determine the cause. It could be a fault with the inter-
nal cooling system, the fan, the radiator air-intake or dirty radiator.
Repeated use of the failure bypass switch should be avoided, if the generator repeatedly cuts out
during operation without determining the cause of the engine cut-outs.
The generator should always be run without load for several minutes before being switched off,
so that temperature stabilisation occurs. Residual heat can cause the generator to overheat, even
after it has been switched off.
Should the overheating alarm be activated after the generator has been switched off, then this
can also be bypassed using the switch.
7.2.6 Troubleshooting Table
For Troubleshooting see section 8.1, “Troubleshooting” on page 113.