58
5 Parameter description
5.1 Basic setting commands
The commands listed here are used for the configuration of basic setting parameters.
5.1.1 Commands for special operating modes
Command
Argument
Function
Description
SOR
0 – 3
Source For Velocity Source for velocity presetting
0: Serial interface (default)
1: Voltage at analog input
2: PWM signal at analog input
3: Current target value via analog input
CONTMOD
–
Continuous Mode Switch back to normal mode from an enhanced mode
STEPMOD
–
Stepper motor
mode
Change to stepper motor mode
APCMOD
–
Analog Position
Control Mode
Change to position control via analog voltage
ENCMOD
–
Encoder Mode
Change to encoder mode (not for MCDC) An external encoder serves as
position detector (the current position value is set to 0)
HALLSPEED –
Hall sensor as
speed sensor
Speed via Hall sensors in encoder mode (not for MCDC)
ENCSPEED
–
Encoder as speed
sensor
Speed via encoder signals in encoder mode (not for MCDC)
GEARMOD
–
Gearing Mode
Change to gearing mode
VOLTMOD
–
Set Voltage Mode Activate Voltage Regulator Mode
IXRMOD
–
Set IxR Mode
Activate IxR control (MCDC only)
5.1.2 Parameters for basic setting
Command
Argument
Function
Description
ENCRES
Value
Load Encoder
Resolution
Load resolution of external encoder (4 times pulse/rev).
Value: 8 to 65 535
MOTTYP
0 – 9
BL motor type
Set to connected BL motor (MCBL only).
0: BL special motor according to KN and RM
1: 1628T012B K1155
2: 1628T024B K1155
3: 2036U012B K1155
4: 2036U024B K1155
5: 2444S024B K1155
6: 3056K012B K1155
7: 3056K024B K1155
8: 3564K024B K1155
9: 4490H024B K1155
KN
Value
Load Speed Con-
stant
Load speed constant K
n
in accordance with information in the data
sheet.
Unit: rpm/V. (Only necessary for MOTTYP0 or DC motor)
Value: 0…16 383
RM
Value
Load Motor Resist-
ance
Load motor resistance RM according to specification in data sheet.
Unit: m
. (Only necessary for MOTTYP0 or DC motor)
Value: 10…320 000
STW
Value
Load Step Width
Load step width for step motor and gearing mode
Value: 1…65 535
STN
Value
Load Step Number Load number of steps per revolution for step motor and gearing mode
Value: 1…65 535
MV
Value
Minimum Velocity Presetting of minimum velocity in rpm for specification
via analog voltage (SOR1, SOR2)
Value: 0…30 000
MAV
Value
Minimum Analog
Voltage
Specify minimum start voltage in mV for speed specification via analog
voltage (SOR1, SOR2)
Value: 0…10 000
ADL
–
Analog Direction
Left
Positive voltages at the analog input result in anticlockwise rotation of
the rotor (SOR1, SOR2)
ADR
–
Analog Direction
Right
Positive voltages at the analog input result in clockwise rotation of the
rotor (SOR1, SOR2)
SIN
0 – 1
Sinus commutation 1: No block commutation within the upper velocity range (default)
0: Block commutation within the upper velocity range (full modulation)
(not for MCDC)