4.6.4 Master Comms Diagnostics
This menu item is concerned only with Master comms diagnostics, and is fully described in
Section 4.3.16
.
4.6.5 Ethernet Diagnostics
This screen (fi gure 4.6.5) allows the user to test the status of the connection with a host computer, and if
Modbus comms is enabled, the connections with local and remote Modbus slaves. The page is available
to any access level with ‘Full Confi guration’ enabled in Security/Access confi guration (
section 4.4.1
).
Host
Ping Status
149.121.131.78
Host Reachable
Ping Now
Local Modbus Client 1
Local Modbus Client 2
Remote Modbus Client 1
Remote Modbus Client 2
Remote Modbus Client 3
Remote Modbus Client 4
127.0.0.1
Offline
149.121.130.242
Offline
Offline
192.168.189.89
Unconnected Message Manager (UCMM)
Implicit I/O Messaging
Explicit Messaging (TCP 1)
Explicit Messaging (TCP 2)
Explicit Messaging (TCP 3)
Explicit Messaging (TCP 4)
Offline
Offline
149.121.129.141
Offline
Offline
Offline
Appear only if Master
comms option enabled
Appear only if EtherNet/IP
comms option enabled
EtherNet/ IP Clients:
IP address remains for five
seconds after message
activity ceases, after which
‘Offline’ appears instead.
Waiting
In Progress
Host Reachable
Ping (Error in value)
Request Timed Out
Host Unreachable
Unknown error
The default status displayed on power up.
Displayed whilst waiting for a response from the host
A device was found at the specified address.
Host refused to allow socket connection on the defined Ping Port.
Unable to reach a host at the specified network address.
Unable to reach a host at the specified network address.
An unknown internal error has occurred.
Displayed Status
Interpretation
Figure 4.6.5 Ethernet Diagnostics display
Host
Allows the IP address, or DNS Name of the host to be ‘Pinged’.
Ping Status
Indicates the latest status returned - see table 4.6.5, below for details.
Table 4.6.5 EtherNet diagnostics display
Ping Now
Operating this button causes an Internet Control Message Protocol (ICMP) com-
mand to be sent to the host. If the host receives the message, it returns a message
to the sender within a few seconds.
Local Modbus Client
Appears only if the ‘Master Comms’ option is enabled. Indicates that the local
Modbus Master is connected.
Remote Modbus Client Appears only if the ‘Master Comms’ option is enabled. Displays the IP address of
connected Modbus TCP/IP clients. Otherwise ‘Offl ine’ is displayed.