Page 313
Note: PV access is Read/Write for any point con
fi
gured with ‘Slave Comms’ as its Type or Function.
Otherwise PV access is Read only.
8.4.8 IEEE AREA CHANNEL RUN-TIME DATA (Cont.)
CHANNEL 11
Channel 11 value
Current process value (PV)
Float
See note
F8EB (63723)
2
Channel 11 status
Channel status
Enum
Read only
F8ED (63725)
1
0 = Good PV
5 = Ranging error
1 = Channel off
6 = Over
fl
ow
2 = Over range
7 = Bad PV
3 = Under range
8 = No data
4 = Hardware error
Channel 11 Alarms
Alarm information
Uint16
-
F8EE (63726)
1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active
Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required
Read only
Bit 2: 1 = Acknowledge alarm 1
Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active
Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required
Read only
Bit 6: 1 = Acknowledge alarm 2
Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active
Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required
Read only
Bit 10: 1 = Acknowledge alarm 3
Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active
Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required
Read only
Bit 14: 1 = Acknowledge alarm 4
Read/Write
Bit 15: Spare
CHANNEL 12
Channel 12 value
Current process value (PV)
Float
See note
F8EF (63727)
2
Channel 12 status
Channel status
Enum
Read only
F8F1 (63729)
1
0 = Good PV
5 = Ranging error
1 = Channel off
6 = Over
fl
ow
2 = Over range
7 = Bad PV
3 = Under range
8 = No data
4 = Hardware error
Channel 12 alarms
Alarm information
Uint16
-
F8F2 (63730)
1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active
Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required
Read only
Bit 2: 1 = Acknowledge alarm 1
Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active
Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required
Read only
Bit 6: 1 = Acknowledge alarm 2
Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active
Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required
Read only
Bit 10: 1 = Acknowledge alarm 3
Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active
Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required
Read only
Bit 14: 1 = Acknowledge alarm 4
Read/Write
Bit 15: Spare
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length