8.4.7 IEEE 32-bit channel con
fi
guration data
The following tables show the hexadecimal addresses for the speci
fi
ed 32-
bit
fl
oating-point values, for channels 1 to 12.
Generally, Parameter address for channel N = Parameter address for channel 1 + 36(N-1) (decimal). The word
channel is used as an umbrella term for input channels, maths channels, totalisers etc.
CHANNEL 1
Note: A/B Switching:
B values are not accessible via modbus
for this software version. Span, Zone,
Colour etc. are therefore all setting A
Notes
1. For
maths
,
totalisers
and
counters
, see the relevant option description.
2. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value re-
turned will be the previously con
fi
gured constant value.
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Ch1 span high
Upper span value (Display full scale)
Float
Read only
D4E7 (54503)
2
Ch1 span low
Lower span value (display ‘zero’)
Float
Read only
D4E9 (54505)
2
Ch1 Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
D4EB (54507)
2
Ch1 Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
D4ED (54509)
2
Ch1 Alarm 1 setpoint
Trigger setpoint (Note 2) for alarm 1 (Note 2)
Float
Read/Write D4EF (54511)
2
Ch1 Alarm 2 setpoint
Trigger setpoint (Note 2) for alarm 2 (Note 2)
Float
Read/Write D4F1 (54513)
2
Ch1 Alarm 3 setpoint
Trigger setpoint (Note 2) for alarm 3 (Note 2)
Float
Read/Write D4F3 (54515)
2
Ch1 Alarm 4 setpoint
Trigger setpoint (Note 2) for alarm 4 (Note 2)
Float
Read/Write D4F5 (54517)
2
Spare
D4F7
(54519)
20
CHANNEL 2
Ch2 span high
Upper span value (display full scale)
Float
Read only
D50B (54539)
2
Ch2 span low
Lower span value (display ‘zero’)
Float
Read only
D50D (54541)
2
Ch2 Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
D50F (54543)
2
Ch2 Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
D511 (54545)
2
Ch2 Alarm 1 setpoint
Trigger setpoint for alarm 1 (Note 2)
Float
Read/Write D513 (54547)
2
Ch2 Alarm 2 setpoint
Trigger setpoint for alarm 2 (Note 2)
Float
Read/Write D515 (54549)
2
Ch2 Alarm 3 setpoint
Trigger setpoint for alarm 3 (Note 2)
Float
Read/Write D517 (54551)
2
Ch2 Alarm 4 setpoint
Trigger setpoint for alarm 4 (Note 2)
Float
Read/Write D519 (54553)
2
Spare
D51B
(54555)
20
CHANNEL 3
Ch3 span high
Upper span value (display full scale)
Float
Read only
D52F (54575)
2
Ch3 span low
Lower span value (display ‘zero’)
Float
Read only
D531 (54577)
2
Ch3 Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
D533 (54579)
2
Ch3 Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
D535 (54581)
2
Ch3 Alarm 1 setpoint
Trigger setpoint for alarm 1 (Note 2)
Float
Read/Write D537 (54583)
2
Ch3 Alarm 2 setpoint
Trigger setpoint for alarm 2 (Note 2)
Float
Read/Write D539 (54585)
2
Ch3 Alarm 3 setpoint
Trigger setpoint for alarm 3 (Note 2)
Float
Read/Write D53B (54587)
2
Ch3 Alarm 4 setpoint
Trigger setpoint for alarm 4 (Note 2)
Float
Read/Write D53D (54589)
2
Spare
D53F
(54591)