background image

100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE

HA029324
Issue 11  Oct 14

User Guide

Page 270

Byte 0

Transaction

identifier

Transaction

identifier

Protocol

identifier

Protocol

identifier

Byte 1

Byte 2

Byte 3

Byte 4

Number of

bytes fol-

lowing (hex)

Byte 5

Always 00

Byte 6

Recorder

Modbus

address

Byte 7

Modbus
function

code (hex)

00

00

00

00

00

13

01

Byte 8

Byte 9

Byte 10

Byte 11

Byte 12

Byte 13

Byte 14

Byte 15

Byte 16

Byte 17

Byte 18

Byte 19

Byte 20

Byte 21

Byte 22

Byte 23

10

CC

Start

address

high

Start

address low

No. of regis-

ters high

No. of reg-

isters low

Byte count

30

ASCII

E (Hex)

45

Null

Password

High
Byte

0C

00

06

ASCII

n (Hex)

6E

ASCII

g (Hex)

67

ASCII

i (Hex)

69

ASCII

n (Hex)

6E

ASCII

e (Hex)

65

ASCII

e (Hex)

65

ASCII

r (Hex)

72

00

HH

User name (as configured in instrument.  Must be followed by null character (Hex 00)

Byte 24

Null

00

Password

Low

Byte

HH

HH

Null character inserted only, if
otherwise, the Byte count in
Byte 12 would be Odd.

Byte 6

Slave

identifier

MODBUS

function

code (hex)

00

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

10

CC

Start

address

high

Start

address low

No. of regis-

ters high

No. of reg-

isters low

30

00

06

Byte 7

Byte 8

Byte 9

Byte 10

Byte 11

Byte 12

Byte 13

Byte 14

Byte 15

Byte 16

Byte 17

Byte 18

Byte 19

Byte 20

Byte count

(excluding

CRC)

ASCII

E (Hex)

45

0C

ASCII

n (Hex)

6E

ASCII

g (Hex)

67

ASCII

i (Hex)

69

ASCII

n (Hex)

6E

Null

Password

High
Byte

ASCII

e (Hex)

65

ASCII

e (Hex)

65

ASCII

r (Hex)

72

00

HH

Null

00

Password

Low

Byte

HH

HH

Null character inserted only if
without it, the Byte count in
Byte 6 would be Odd.

CRC low

Byte

HH

HH

CRC high

Byte

8.2.4  SECURITY (Cont.)
TO SEND A LOGIN REQUEST

Request

Figure 8.2.4a shows data transmission sequence for sending a login request to a recorder with Modbus address 

1, using the Ethernet network connection.  Figure 8.2.4b is the same message for use with serial communica-

tions 

Figure 8.2.4a  Login request via Ethernet (Modbus TCP)

Figure 8.2.4b  Login Request using a serial transmission line.

Notes:
1  The high and low password bytes are entered using the result of the encryption program above. If 

the password is blank, both High and Low Bytes must be 00 (null).

2  For successful login, the ‘Connect from remote’ item must be enabled (ref. ‘Access levels in 

section 4.4.1

).

Summary of Contents for 6100

Page 1: ...6100 6180 XIO User Guide 6100 6180XIO Distributed graphic recorder Versions 5 4 and later HA029324 11 October 2014 ...

Page 2: ......

Page 3: ...e document relates without the prior written permission of Eurotherm Limited Eurotherm Limited pursues a policy of continuous development and product improvement The specifi cations in this document may therefore be changed without notice The information in this document is given in good faith but is intended for guidance only Eurotherm Limited will accept no responsibility for any losses arising f...

Page 4: ...EUROT H ERM ...

Page 5: ... DISPLAY 8 4 SETTING UP THE RECORDER 45 5 FILE 226 6 BRIDGE 229 7 SCREEN BUILDER 238 8 MODBUS TCP SLAVE COMMS 265 ANNEX A SPECIFICATION 317 ANNEX B REFERENCE 321 ANNEX C WEB SERVER DETAILS 349 INDEX 353 EFFECTIVITY This manual refers to recorders fitted with software version 5 4 To determine the software version fitted to the recorder the About screen in the System menu may be accessed as described ...

Page 6: ...TTERY 11 DISK ICON 11 FTP ICON 12 CONFIGURATION LOCKED INDICATOR 12 TRIAL MODE INDICATOR 12 3 1 4 Summary menu 13 INSTRUMENT ALARM SUMMARY 13 ACK ALL ALARMS 13 ALARM SUMMARY PAGE 14 ALARM ACKNOWLEDGEMENT 15 BATCH SUMMARY 16 MESSAGE LOG 18 REMOVE MEDIA 21 3 2 NAVIGATION KEYS 22 3 2 1 Key functions 22 ROOT MENU KEYS 22 ALARM SUMMARY 24 MESSAGE LOG 24 3 3 FIRST SWITCH ON 25 3 3 1 Access to Configurati...

Page 7: ...R DISPLAY 57 SAVE AFTER 57 MODBUS ADDRESS 57 MODBUS SECURITY DISABLED 57 COMMS CHANNEL TIMEOUT 57 PRESET HOUR 58 PRESET MINUTE 58 DISABLE WARNING DIALOGS 58 SHOW OPERATOR NOTES LIST 58 4 3 2 Group configuration 59 GROUP NUMBER 60 TREND UNITS 60 DESCRIPTOR 60 TREND TYPE 60 A B SWITCHING 61 TREND SPEED TREND INTERVAL 61 CIRCULAR SETTINGS 61 CIRCULAR SPEED 61 CIRCULAR CHART FULL 61 START AT 61 GRID TY...

Page 8: ... SHOW 78 MEDIA 78 ARCHIVE TO MEDIA 78 MEDIA FILE FORMAT FTP FILE FORMAT 79 ON MEDIA FULL 79 MEDIA SIZE 79 REMOVABLE MEDIA CAPACITY 79 MEDIA FULL EVENT LIMIT 79 ARCHIVE TO REMOTE 79 REMOTE PATH 79 PRIMARY REMOTE HOST 80 PRIMARY LOGIN NAME PASSWORD 80 SECONDARY REMOTE HOST LOGIN PASSWORD 80 CSV FILES 80 4 3 6 Event configuration 82 EVENT NUMBER 82 SOURCE TYPES 82 EVENT SOURCES Cont 83 SOURCE 1 SENSE ...

Page 9: ...145 DETECT THIS SLAVE 146 DETECT ALL SLAVES 147 SHARE SOCKET 149 MASTER COMMS CHANNEL CONFIGURATION 150 STATUS BITS 156 MASTER COMMS CHANNEL CONFIGURATION EXAMPLE 158 MASTER CHANNEL 1 SETUP 159 MASTER CHANNEL 2 SETUP 160 MASTER OUTPUT 1 SETUP 161 SLAVE INPUT CHANNEL 1 SETUP 161 MASTER COMMS DIAGNOSTICS 162 4 3 17 Output channels 163 4 3 18 Demand Writes 164 DEMAND WRITE CONFIGURATION 164 WRITING T...

Page 10: ...N 1 190 EVENT PERMISSION 2 TO 5 190 EDIT OUTPUT CHANNEL DEFAULT 190 ACTION DEMAND WRITES 191 FORCE CHANGE OF PASSWORD 191 ENTER BATCH DATA 191 ALLOW WEB SERVER 191 4 4 2 Management option 192 CHANGES NOT RECORDED 192 CONFIGURABLE PARAMETERS 192 4 4 3 Add user 197 NEW USER ID 197 NEW FULL USER NAME 197 NEW DOMAIN NAME 197 NEW PASSWORD RETYPE PASSWORD 197 BASED ON 197 4 4 4 Remove user 198 4 4 5 Cha...

Page 11: ...ON 217 SUPPORT FILE 217 4 7 JOBS 218 4 7 1 No Action 218 4 7 2 Totaliser category 218 4 7 3 Message category 219 4 7 4 Maths category 219 4 7 5 Clock category 220 4 7 6 Counter category 220 4 7 7 Timer category 221 4 7 8 Batch category 221 4 7 9 Recording category 222 4 7 10 Trend category 223 4 7 11 Output category 224 4 7 12 Demand Writes category 224 4 7 13 Alarm category 225 4 7 14 Archive cat...

Page 12: ...orting Exporting screens 240 IMPORTING SCREENS 241 EXPORTING SCREENS 241 7 2 DISPLAY CREATION 241 7 2 1 Before starting 241 7 2 2 Screen components 242 7 2 3 The properties page 243 KEY DESCRIPTIONS UPPER KEYS 243 KEY DESCRIPTIONS LOWER KEYS 244 OPTIONS PAGE ITEMS 245 7 2 4 Screen creation example 246 PROCEDURE 246 7 3 PARAMETER DEFINITIONS 249 7 3 1 Basic parameters 249 7 3 2 Advanced parameters ...

Page 13: ...270 8 2 5 Text messages 272 LONG MESSAGES 272 8 3 ADDRESS MAP 274 8 4 ADDRESS ALLOCATION 276 8 4 1 Instrument data 276 8 4 2 Channel configuration data 277 CHANNEL 1 277 CHANNEL 2 278 CHANNEL 3 279 CHANNEL 4 280 CHANNEL 5 281 CHANNEL 6 282 CHANNEL 7 283 CHANNEL 8 284 CHANNEL 9 285 CHANNEL 10 286 CHANNEL 11 287 CHANNEL 12 288 8 4 3 Channel Run Time data 289 CHANNEL 1 289 CHANNEL 2 289 CHANNEL 3 290 ...

Page 14: ... Permanent ID table 314 8 5 DATA TRANSMISSION 314 FUNCTION CODES AND EXCEPTION CODES 314 TEXT STRINGS 314 8 5 1 Function code 03 315 REQUEST 315 RESPONSE 315 EXCEPTION RESPONSES 315 8 5 2 Function code 04 316 8 5 3 Function code 06 316 REQUEST 316 RESPONSE 316 EXCEPTION RESPONSES 316 8 5 4 Function code 08 316 8 5 5 Function code 16 Hex 10 317 REQUEST 317 RESPONSE 317 EXCEPTION RESPONSES 317 9 ASC...

Page 15: ... DEGREE 330 Installation category II 330 Pollution degree 2 330 A1 TECHNICAL SPECIFICATION Recorder 331 Annex B REFERENCE 334 B1 DIAGNOSTICS DISPLAY 334 B1 1 Main diagnostic display 334 B1 2 SPECIAL MODES 335 B1 3 DISPLAY TEST 335 B1 4 TOUCH CALIBRATION 335 B1 4 1 Touch screen calibrate 336 B1 4 2 Touch screen verify 336 B1 4 3 Main menu 336 B1 5 SYSTEM SUMMARY 337 B1 6 DIAG SUMMARY 337 B1 6 1 MAC...

Page 16: ... B9 MENU STRUCTURE 348 Annex C WEB SERVER DETAILS 362 C1 INTRODUCTION 362 C2 INTERNET LINKS 362 C3 ACCESS TABS 362 C3 1 INSTRUMENT 362 C3 1 1 Instrument alarms 362 C3 1 2 Global channel alarm 362 C3 2 TRENDS 363 C3 2 1 Horizontal trend 363 C3 2 2 Vertical trends 364 C3 2 3 Numeric display 364 C3 3 MESSAGE LOGS 364 C3 4 HISTORY 365 C3 5 ABOUT 365 Index 366 ...

Page 17: ...guous indication e g a flashing alarm whenever the value is over range or under range 2 Where conductive pollution e g condensation carbon dust is likely adequate air conditioning fil tering sealing etc must be installed in the equipment enclosure 3 The equipment is designed for process monitoring and supervision in an indoor environment If the equipment is used in a manner not specified by the manuf...

Page 18: ...ER The recorder is despatched in a special pack designed to give adequate protection during transit Should the outer box show signs of damage it should be opened immediately and the recorder exam ined If there is evidence of damage the instrument should not be operated and the local representative contacted for instructions After the recorder has been removed from its packing the packing should be...

Page 19: ... 0 mm 144 0 mm 87 7 mm 137 0 mm Fixing Clip one each side 137 5 mm 154 5 mm 170 5 mm 6 7 mm Sealing gasket Panel thickness Max 22 mm Min 2 mm PANEL MOUNTING DETAILS Installed panel angle Vertical panels only Minimum inter unit spacing 50 mm vertical or horizontal Note where multiple units are mounted in close proximity with one another steps must be taken to ensure that the resulting ambient tempe...

Page 20: ... side Sealing gasket 288 0 mm 288 0 mm Panel cutout 282 mm x 282 mm both 0 1 3mm PANEL MOUNTING DETAILS Installed panel angle Vertical panels only Minimum inter unit spacing 50 mm vertical or horizontal Note where multiple units are mounted in close proximity with one another steps must be taken to ensure that the resulting ambient temperature does not exceed the speci fied maximum operating tempe...

Page 21: ...NING Pins 1 and 2 are internally connected together as are pins 3 and 4 POWER REQUIREMENTS Voltage range 19 2 to 28 8 V dc 24V dc 20 Permissible ripple 1 V max Maximum power requirements at 24 V Small frame 20 Watts Large frame 24 Watts Inrush current 10A Internal fusing Not user replaceable Figure 2 2 1 a Supply voltage wiring view on underside of instrument Figure 2 2 1b Supply voltage connectio...

Page 22: ...wire Master 5 wire Slave 3 Wire Master Slave 1 2 3 4 5 6 7 8 pin 1 pin 8 RJ 45 plug View on underside Figure 2 2 2b Serial communications hardware configuration Small frame shown large frame similar Table 2 2 2b Communications DIP switch settings ON 1 2 3 4 ON 1 2 3 4 BR2330 Ethernet connector Serial communications ports Port 1 Port 2 Cover retaining screw location 120 Ohm terminating resistor fitt...

Page 23: ...he card is removed by a double operation of the eject button See details in figure 2 4 below Caution Removal of the memory device whilst archiving is in progress causes irreparable damage to the fil ing structure on the device rendering it unusable For this reason archiving should be suspended section 4 1 wait for the green area of the disk icon section 3 1 3 to go white before the device is removed...

Page 24: ... of space on the display page is insufficient to display the full width of the process variable or scale value then the displayed value is rounded down and the number of decimal places reduced If the width is still too restricted the value is displayed in scientific format or if this is still too wide the final visible character of the integer part of the value is replaced by a as depicted in figure 3...

Page 25: ...ibed below 3 1 1 Current access level There are four access levels available Logged out Operator Engineer and Service and the current level is displayed in this key at the top left hand corner of the display Touching this key calls the login page as described in section 3 3 1 Access to configuration below If a user has been added using the Add User part of the Security setup section 4 4 3 below the...

Page 26: ...f the recorder fails after two attempts to establish communications with the primary server as defined in Archive Con figuration section 4 3 5 After the second attempt has failed the Secondary server is tried FTP Secondary Server Failure This error is set if the recorder fails after two attempts to estab lish communications with the secondary server as defined in Archive Configuration section 4 3 5 Se...

Page 27: ...ex B The indicator does not appear if the battery is not fitted DISK ICON This shows the free space available on whatever mass storage medium is fitted if any and selected for Archive destination note 1 The disk icon appears soon after the device is inserted but see note 2 During archiving the colour of the central area of the disk changes to green see note 3 No other disk activity e g save restore ...

Page 28: ...ON LOCKED INDICATOR This symbol appears only when Bridge software is being used in the following situations 1 Whilst units are synchronising configuration changes 2 Whilst configuration is taking place If the reconfiguration is taking place at the host pc Bridge Full only then the symbol appears at the target instrument and vice versa TRIAL MODE INDICATOR This symbol is displayed whilst the recorder ...

Page 29: ...el Failure Printer Error Ack all Alarms Yes No Confirm acknowledge of alarms Figure 3 1 4a Summary pop up menu INSTRUMENT ALARM SUMMARY Figure 3 1 4b Typical Instrument alarm summary display This contains a list of the currently active instrument alarms For a list of possible alarms and their defini tions see section 3 1 3 above ACK ALL ALARMS Figure 3 1 4c Ack all Alarms display Yes confirms all ac...

Page 30: ...d See section 4 3 3 for a description of alarm types and actions 3 There are no time or history components associated with the Alarm Summary If Alarm mes sages have been enabled in the relevant group s configuration section 4 3 2 then alarm initia tion acknowledgement times and dates can be found from the trend and trend history displays described in section 3 4 or in Message log described later in...

Page 31: ...ons key section 3 2 the Ack Group Alarms key and finally Yes in the resulting pop up confirmation box Figure 3 1 4e below attempts to show this process Alarm Summary Group 1 1 1 Water temp 1a 60 0000 C 68 5277 2 1 Water temp 1b 30 0000 C 23 4531 2 2 Water temp 1b 10 0000 C 23 4531 3 1 0il pressure 250 000 PSI 260 3425 4 1 Transfer 15 3678 Yes No Confirm acknowledge of alarms Batch Note Ack Group Ala...

Page 32: ...ield 1 Group 11 00 00 00 00 00 00 Batch field 1 Add Inputs 00 00 00 00 00 00 Batch field 1 Batch running indicator Click to highlight Full Details Batch Control Sort ON Highlight OFF Exit Mix2 3 1 4 SUMMARY MENU Cont BATCH SUMMARY If the Batch option is fitted section 4 3 10 a Batch Summary key appears in the Summary menu Note The following description shows the situation where batch Scope is config...

Page 33: ... SORT If Sort is Off default the groups appear in Group number order with Group 1 at the top and group 12 at the bottom The key legend is Sort ON If Sort is On those groups with batches running appear in group number order at the top of the list fol lowed by any remaining groups also in group number order The key legend is Sort OFF HIGHLIGHT If Highlight is Off default then all groups text appears...

Page 34: ...Message Log Group name All Messages All History 05 04 06 09 06 18 Alarm s on 1 1 05 04 06 09 06 18 Operator s name Andrew 05 04 06 09 06 18 Customer FishesRus 05 04 06 09 06 18 Batch number 020205A12 05 04 06 09 06 18 Config Revision 682759 Security Revision 746261 05 04 06 09 06 18 Batch start Engineer 05 04 06 08 50 30 Configuration revision 682 759 was 682 758 05 04 06 08 50 28 Batch Name files...

Page 35: ...s only batch messages including Config and Security Revisions if either Auditor option is enabled Logins Lists only changes in login Signings This list contains only notes messages etc that have been signed and authorized This category is used only when Require Signing and Require Authorization is are enabled in the Security Management menu see section 4 4 for more details Audit trail This list con...

Page 36: ...l History Group name Batch number 060405A12 09 06 22 05 04 06 Option Menu Batch Note Enter History Full Details Refresh To call Option Menu touch message highlights yellow or Option key Figure 3 1 4h Message Log options menu Batch See section 4 3 10 Note See section 3 5 Enter history Operating the Enter History key causes the recorder to display that page of history which includes the highlighted ...

Page 37: ...Touching the key results in either an OK to remove archive media or a DO NOT REMOVE Archive Me dia message as appropriate See figure 3 1 4i Caution Removal of memory devices whilst archiving is taking place can lead to permanent irreparable damage to the device rendering it unusable OK to remove archive media Ok Will advise when OK to remove Cancel Archive Media DO NOT REMOVE Archive Media Figure 3...

Page 38: ...t functions such as entering quitting history turning channel cycling on and off etc according to context Root Calls the Root Menu as described below To quit the Root menu touch the root key again ROOT MENU KEYS Home Causes a return to the Home page from any page in the recorder As delivered the Home page is the Group 1 vertical trend display as depicted in figure 3 but this can be edited in Config ...

Page 39: ...groups in ascending group number order The left arrow key can be used to scroll through groups in descending group number order Home Operator File Goto View Goto Group Message Log Horizontal Trend Vertical Bargraph Alarm Summary Vertical Trend Circular Trend Numeric Page User Screen 2 Horizontal Bargraph User Screen 1 User Screen 3 More A display mode appears only if it is enabled for the current ...

Page 40: ...enu but in this case the user must select an alarm summary group from a pop up Goto Group menu See section 3 1 4 for more details of the alarm summary page MESSAGE LOG The Root menu Goto View Message log key calls the Message Log page for the current group to the screen Alternatively Message Log can be selected from the Alarm Message and Media menu but in this case the user must select a Group for...

Page 41: ...nly Archive Login security and the System About functions can be accessed via the root menu Limited or full access can be permitted from Engineer level Operator No access to recorder configuration is possible until access permissions have been set up Section 4 4 1 describes how limited or full access can be permitted by an operator with En gineer level access Engineer Accessed initially by entering...

Page 42: ...be edited in Security as described in sec tion 4 4 1 The screen reverts to the home page with the new access level dis played in the Current access level key 0 0000 1 0000 Channel 1 0 0237V 0 2000 0 4000 0 6000 0 8000 1 2 3 Figure 3 3 1a Access to configuration Notes 1 For units which have the Auditor 21CFR11 Option enabled the default Operator password is 100 Otherwise no password is required for ...

Page 43: ...ck ground colour changes to yellow for as long as the key is active Shift Once the shift key has been pressed the next entered letter appears as a capital subsequent let ters are in lower case Caps When pressed all subsequent letters appear as capital letters until the Caps key is operated again BSpc This backspace key deletes character to the left of the cursor Ovr If selected the next entered ch...

Page 44: ... Symbols Numeric Text String Alphabet Shift Caps BSpc Ok Cancel Alphabet 2 Ovr Symbols Numeric Text String Alphabet Shift Caps BSpc Ok Cancel Alphabet 2 Ovr Numeric Text String Alphabet Shift Caps BSpc Ok Cancel Alphabet 2 Ovr Symbols Ä Å Á À Æ Ç É È a Ë Ê Í Ì Ï Ó Ò Ô Î Ö º Ü Ú Ù Û Ñ ÿ β Γ δ α τ φ Ω Σ θ μ π η ε _ 3 2 7 8 9 4 5 6 1 2 3 0 E The E key is used to enter exponents ...

Page 45: ...nt channel touch the faceplate 4 Group faceplates are not displayed in trend history mode 5 Operation of the Root Goto View Message Log key section 3 2 1 when in history mode dis plays a message log page containing messages which occurred at or near the selected cursor time 6 With A B switching selected traces are displayed with the A or B span zone colour settings etc obtaining at the cursor time...

Page 46: ...scale being displayed on a faceplate across the full width of the screen above the chart If a channel is included in the display group but its status is not good for some reason then its pen icon is hollow Faceplates for all the group channels can be displayed by using the Faceplates On Off key in the option menu If selected On faceplates showing colour descriptor digital value and units for all t...

Page 47: ...larms s on 3 1 11 07 06 11 51 33 Alarms s off 3 1 Home Trend display mode Engineer Preparing History please wait 11 07 06 11 49 54 Cursor time date Touch faceplate to increment channel 800 00 720 00 560 00 480 00 Faceplate for current channel Touch and release face plate to increment channel or touch pen to select channel If Channel Cycle On Current channel incre ments every 10 seconds Press arrow...

Page 48: ...faceplates associated with this display mode one above the chart showing the current channel s descriptor and its digital value the other to the right of the chart showing a bargraph rep resentation of the current channel s value together with a scale showing the low and high range values for the channel Touching either of these faceplates causes the current channel number to increment To select a...

Page 49: ... 800 14 16 20 06 04 05 14 13 40 06 04 05 14 11 00 06 04 05 11 07 06 12 02 20 Alarm s off 2 1 View Messages 11 07 06 12 02 20 Batch Number 050406 3 11 04 06 11 11 41 Config Revision 218 Security Revision 3 11 07 06 11 11 34 Batch start Engineer 11 07 06 11 09 34 Alarm s on 1 1 11 07 06 11 09 26 Alarm s off 1 2 11 07 06 11 07 41 Alarm s on 1 2 11 07 06 11 07 34 Alarm s off 1 1 11 07 06 11 05 34 Alar...

Page 50: ... 3 2 The user can select Rotate or New Chart ROTATE In the following description the word segment is used interchangeably with Major chart division The number of Major chart divisions is a function of the selected chart speed as described in Group Configu ration section 4 3 2 With Rotate selected the traces start one major chart division anti clockwise from the top of the chart and trace clockwise ...

Page 51: ...7 52 Engineer Restarted 11 07 Furnace 1 Te 1125 0956 C Furnace 1 Te 1113 9806 C Furnace 1 Te 1200 9456 C Flow 1 1365 21l hr Flow 2 1299 65l hr Flow 3 989 54l hr Chart zero Chart Full scale Scale for left half of chart 1 hr rev Chart Speed Scale for right half of chart 897 3476 C Figure 3 4 3a Circular trend New chart mode NORMAL VIEW Normal view is available only for large frame recorders also sma...

Page 52: ...sage bar at the bottom of the screen displays the latest message If an up ar row appears at the right hand end of the bar there is more than one message Touch ing the message bar calls a View Messages window detailing previous messages See the description in section 3 4 2 for more details FULL SCREEN DISPLAY As shown in figure 3 4 3c below this maximizes the chart diameter leaving only the chart ch...

Page 53: ...the chart All other chart divisions are identified by time only OTHER NOTES 1 Adaptive recording results in two traces per trend as in other trend display modes 2 For successful circular trend display Circular Settings must be enabled for the relevant group sec tion 4 3 2 and Circular Trend must be enabled for the group in Views configuration section 4 3 4 If Circular Trend is enabled but Circular S...

Page 54: ... feature is available for vertical trend circular trend and vertical bargraph displays only To call the horizontal bargraph display mode use the down arrow key Alternatively any one of the ena bled display modes section 4 3 4 can be selected using the Root Menu Goto View key Trend history mode is not available from this display mode FACEPLATES ABOVE THE BARS See figure 3 4 4a As the number of chann...

Page 55: ... 1 0 0 0 1 0 0 0 80 40 80 40 40 0 0 40 0 0 1 0 0 0 1 0 0 0 500 0 500 0 500 0 500 0 500 0 500 0 100 0 100 0 100 0 100 0 100 0 100 0 Group name 11 49 37 11 07 06 Logged out 487 39 C 235 68 C 378 99 C 0 49V Channel 6 0 85V Channel 7 689 43 C Channel 8 483 72 C Channel 9 255 81 C Channel 10 375 01 C Channel 11 0 53V Channel 12 0 79V Channel 13 235V 700 87 C Channel 2 Channel 3 Channel 4 Channel 5 Chan...

Page 56: ... the display group double column for more than 12 channels For small frame recorders only the single column mode is employed with a scroll bar when necessary 2 For large frame recorders up to 26 points can be displayed simultaneously for small frame recorders the maximum is 5 points In either case if more points are enabled than can be displayed within the height of the screen a vertical scroll ba...

Page 57: ...hannel 15 0 500 700 87 C Channel 16 0 500 Channel 17 0 500 700 87 C Channel 18 0 500 Channel 19 0 100 700 87 C Channel 20 0 100 Channel 21 0 100 700 87 C Channel 22 0 100 Channel 23 0 100 700 87 C Channel 24 0 100 700 87 C 235 68 C 0 49V 689 43 C 255 81 C 0 53V 235V 235V 316A 64 26 56 487 39 C 378 99 C 0 85V 483 72 C 375 01 C 0 79V 235V 320A 332A 54 47 81 0 00 1 00 0 00 400 00 Group name 11 58 08 ...

Page 58: ...isplay mode A further operation of the down arrow key returns to Vertical Trend Display mode described in section 3 4 1 above or if user screens are fitted and enabled to the first user screen section 7 Alternatively any one of the enabled display modes section 4 3 4 can be selected using the Root Menu Goto View key Figure 3 4 6a Numeric display mode 1 to 5 channels example Note Figures 3 4 6a b and...

Page 59: ... name Channel 1 700 87 C Channel 2 487 39 C Channel 3 235 68 C 12 04 13 11 07 06 Logged out Channel 4 378 99 C Channel 5 0 49V Channel 6 0 85V Channel 7 689 43 C Channel 8 483 72 C 255 81 C Channel 10 375 01 C Channel 11 0 53V Channel 12 0 79V Channel 13 235V Channel 14 235V Channel 15 235V Channel 16 320A Channel 17 316A Channel 18 331A Channel 19 64 Channel 9 Figure 3 4 6b Numeric display mode e...

Page 60: ...ine A Tube 1 To enter a message 1 Press the Option key then the Note key 2 If necessary enter Signature and Authorization passwords Auditor 21CFR11 option only see section 4 4 2 3 Touch the note area of the resulting pop up display see note below 4 Enter the required text of up to 120 characters spaces are also counted as characters Press Ok when finished 5 View the note and a press the Ok button t...

Page 61: ... word holders New users can be added with their own user names passwords and access level permissions Network Section 4 5 This area sets up the IP address host names etc used in FTP transfer Bridge and SNTP applications System Section 4 6 Allows a Time and date to be set Clock b Language date time format time zone and daylight saving start and finish dates to be set Locale c Software upgrades to be...

Page 62: ...hat it is safe to remove the memory device Figure 4 1 1 Local archive configuration Local archive allows the user to initiate data transfer to the device defined in the Media picklist for all groups with Archive to Media enabled Group configuration section 4 3 2 Archiving is initiated by touching the relevant archive period key e g Last Day The memory device can be selected as mediac ard the integral...

Page 63: ...g to change media without losing data by operating the Suspend Archiving Resume Archiving button Any archiving in progress is allowed to complete before the Suspend Archiving request takes effect Transfer activity is indicated in the Archive transfer window Below the selection buttons are a number of status windows relating to the selected memory device Media Full is an estimate based on the curre...

Page 64: ...ays Archive Last 31 days Archive All Cancel Archive Bring Archive Up To Date 08 09 2005 12 00 00 Inactive Local Remote Figure 4 1 2 Remote archive strategy configuration Additionally a user on a remote PC has full viewing capabilities can extract recorder files at any time and can access those items of recorder configuration that are associated with the user s login For successful connection Connect ...

Page 65: ...e menu Where a file name is required then if the displayed file name is suitable operation of the Save Restore Import or Export key will initiate the action If instead a file name has to be entered this is carried out as follows Touching the filename window causes a pop up menu to appear giving a list of Volumes in the Flash memory or on the memory device if inserted Figure 4 2b shows an imaginary Vol...

Page 66: ...y sec tion 4 1 above can be used to speed up the Restore process at the cost of losing the archive data 3 If Centralised Security is active part of Security Management configuration section 4 4 2 Security Data is not selectable either for Restore or for New below 4 If the file to be restored has been created using C Edit software each of the characters used in the file name must lie within the unicod...

Page 67: ... directly from the host PC Touching the User Linearisation field allows the user to select which of UserLin1 to UserLin12 is to con tain the imported file Touching the File Name field calls a popup menu similar to that shown in figure 4 2b This allows the user to select the table to be imported The file must be comma separated ASCII as follows n X1 Y1 X2 Y2 X3 Y3 Xn Yn where n is the total number of XY...

Page 68: ...meter is displayed in red in stead of the normal black until the Apply Discard key has been operated For example in channel con figuration if the Scale High value is edited Scale High appears in red until the Apply key is operated Should an attempt be made to leave configuration with unsaved changes a warning message appears allowing the user to apply the changes to discard the changes or to return ...

Page 69: ...1 8 Days 100 Archive to Media Compression Normal Flash Size 9 9 2 5 Mb Shortest Trend History G r o u p 1 Show Local settings Duration 2 6 9 5 Days None Media file format Binary Media mediacard Groups Section 4 3 2 Views Section 4 3 4 Home Time out Home Group Scope Group Display Enable Home Page Vertical Trend Horizontal Trend Vertical Bargraph Horizontal Bargraph Numeric Page User Screen 1 User S...

Page 70: ... Discard User Linearisations Section 4 3 9 Archive System Save Restore Config Security Network Event Buttons Section 4 3 7 Apply Discard Function fValue Fvalue of Sterilizing Temp 121 1 Low cut off Descriptor Fo 1 Scale Low 0 Mins Scale Type None Zone low 0 Zone high Max Decimal Digits 2 Colour Alarm Number 1 Enable Off Job Number 1 Category No Action 26 Channel 1 75 100 Maths Number 1 Fo 1 Value ...

Page 71: ...up 4 Group 5 Group 6 19200 1 None 8 ms 0 13 Link Error Count 0 0 10 Reset Error Count Protocol ASCII input Port Serial 1 Connection EIA4XX Stop Bits ASCII Input Apply Discard Baud Rate Stop Bits Parity Timeout ms Enable error code B Enable Talk Through Protocol Link Error Count Reset Error Count Connection Port 19200 1 None 1000 Modbus Master 0 EIA232 Serial 1 Modbus Master Apply Discard Baud Rate...

Page 72: ...Apply Discard Write number Demand Write Slave Parameter Point Type Point Number Descriptor Source Default Allow Constant Edits Disable Retries Send On Power Up On Error Write Default Master Comms 1 Write 1 OK 1 Furn 1 Recorder Alarm setpoint 2 Channel 1 Write 1 Channel 1 0 Report Descriptor Number of Fields Field 1 Type Style 1 Report 1 1 Date Time Normal Report 1 Apply Discard Demand Writes Secti...

Page 73: ...d er without its first having to supply a valid User name and Password This box must be checked if this unit is acting as a Modbus slave in order for the unit to be detected Once communications have been es tablished Modbus security can be enabled providing that the Slave s Remote user name and password have been entered at the Master See also section 8 2 4 COMMS CHANNEL TIMEOUT Allows a number of ...

Page 74: ... alarm messages from appearing on the screen SHOW OPERATOR NOTES LIST Enabling this field produces a list of 13 entries which can be used in Operator Notes The first entry is the MAC address of the recorder and is not editable The remaining 12 entries of up to 60 characters each are freely editable Any one of these predefined notes can be selected as described in section 3 5 by touching the Opera tor...

Page 75: ...scard Alarm Message Recording Speed Recording Interval Archive to Media Enable Archive via FTP Enable Trend History Duration Recording Enable Ack Message TurbineTempA TurbineTempB Enabled Etc 1 1 200 mm hr s List of all available points input channels maths channels totalisers etc 314 36 Days Editable only if Recording Enable is enabled Trend Units Descriptor Trend Speed Trend Interval Group Numbe...

Page 76: ... two traces are pro duced for each channel in the group The faceplates and pen positions are still updated every second as normal Notes 1 During the period between updates the maximum and minimum values are shown on the trend as a horizontal line just beneath the pen where the ends of the line represent the mini mum and maximum values so far This line is removed at trend update time 2 Adaptive rec...

Page 77: ...uration but Circular Trend is enabled for the group in Views configuration section 4 3 4 then although the circular chart will appear it is unlikely that the chart will contain any trends CIRCULAR SPEED This field allows the chart speed to be selected from a pick list as detailed in table 4 3 2 below The table also shows the number of major and minor chart divisions CIRCULAR CHART FULL This allows N...

Page 78: ...or groups with Number of decades 5 FROM POINT This allows the chart grid to be aligned with the scale of a particular point selected in the from field which appears if From Point is selected as Grid Type Figure 4 3 2c Typical chart grid definitions RECORDING ENABLE This tick box allows the logging of this group s data to the flash memory to be enabled disabled When disabled a The recording speed inte...

Page 79: ...ed Interval A Changing the contents of one group may affect the Trend History Duration of other groups This hap pens because the recorder attempts to store as nearly as possible the same amount of history for all groups regardless of how many points there are in the groups For empty groups or if Recording is not enabled for a group the Trend History Duration is displayed as 0 Days ARCHIVE TO MEDIA...

Page 80: ...licable For example an entry of 1 3 6 9 11 would cause points 1 2 3 6 9 10 and 11 to be added or removed from the group contents Only numeric characters commas and hyphens minus signs are accepted If any other character including space s is included in the list the edit will fail with a message Invalid Selection appearing when the Enable or Disable key is operated 3 Ranges must be complete 1 is no...

Page 81: ... Scale Low Scale High Units Offset Scale Type Scale Divisions Major Scale Divisions Minor Descriptor Spanned V V V Off Slave comms Test Master comms Select None Linear or Log Log available only if Scaled is ticked Select Alarm number V V V V s These fields vary according to the selected job category These fields appear only if Spanned is selected These fields vary according to Alarm Type selection...

Page 82: ...c scales are to be used SCALE LOW Enter the scale value to correspond with input range low e g 0 SCALE HIGH Enter the scale value to correspond with input range high e g 100 SCALE UNITS Enter up to five characters of unit descriptor e g Note User linearisation tables units To set user linearisation table units to temperature units C for example the Range Units selection box can be used To enter cus...

Page 83: ... values 2 to 9 Examples are shown in figure 4 3 3b1 Because of the nature of logarithms neither negative values nor the value 0 can be used as scale zero Linear inputs are traced as exponental curves figure 4 3 3b2 LOG LINEAR For some input type selections this appears only if Scaled is ticked Channels with Scale Type Log Linear appear with logarithmic scales These scales have major divisions at eac...

Page 84: ...0000 50 0000 60 0000 70 0000 80 0000 90 0000 100 0000 41 6667V 4 minute triangle Linear Scale Linear Grid 11 57 21 25 05 06 11 56 00 25 05 06 11 54 40 25 05 06 11 53 20 25 05 06 1 0000 Channel 47 10 0000 100 0000 41 4250 V 4 minute triangle Log Scale Log Grid 12 13 21 25 05 06 12 12 00 25 05 06 12 09 20 25 05 06 12 10 40 25 05 06 1 0000 Channel 47 10 0000 100 0000 6 4158V 10 44 18 25 05 06 10 42 5...

Page 85: ...hing is enabled a second set of zone low and zone high values can be entered A values are used during normal operation B values are switched to by job action as described in section 4 7 PV FORMAT This allows the PV value alarm setpoints hysteresis values etc to be displayed as normal numeric val ues Numeric or in Scientific format Scientific When Scientific is selected values are displayed and entere...

Page 86: ... below Threshold minus hysteresis If a dwell value is defined the alarm does not become effective until this dwell time has been exceeded Absolute Low As shown in figure 4 3 3d an absolute low alarm becomes active when the channel value falls below the threshold value The alarm remains active until the channel value exceeds Threshold hysteresis If a dwell value is defined the alarm does not be come e...

Page 87: ...ed the Amount value entered in the preceding field in order for the alarm to become active See Rate of Change example below for more details Average time For rate of change alarms this allows an average period to be entered for signal smoothing HYSTERESIS EXAMPLE Threshold 100 units Hysteresis 5 units With the above settings an absolute high alarm would become active if its input were to rise above...

Page 88: ...ime A rate of change alarm is active if the channel value changes by more than 1 amount unit in less than 1 time unit Dwell delays the alarm on time Averaging removes the effects of spurious spikes Rate of change rise active Rate of change fall active Reference Deviation Hysteresis no Dwell 0 secs alarm active D is in seconds up to 999999 Hysteresis is in engineering units Hysteresis no Dwell D se...

Page 89: ...e duration for which continuous jobs run the down arrows show trigger points for one shot jobs See section 3 1 4 for details on how to acknowledge alarms Alarm trigger Active Inactive While active While inactive While unacknowledged latching alarm While unacknowledged non latching alarm While unacknowledged non latching alarm Job goes inactive even if alarm not yet acknowledged While unacknowledge...

Page 90: ...d er option Section 7 is fitted Bridge user screens are accessible only from a remote PC which has Bridge software installed and running 0 Figure 4 3 4a Views Configuration menu HOME TIMEOUT The recorder returns to the specified home page after the timeout value of minutes has elapsed since the last touch on the display Timeout action is inhibited if a configuration is incomplete there are changes wh...

Page 91: ...ens Group N selection and is skipped when using the right left arrow keys It is not possible to disable the Home group HOME PAGE Allows a particular display mode to be selected as the default display either for all groups Scope in strument or on a group by group basis Scope group DISPLAY MODE ENABLING A series of tick boxes allow the various display modes to be added to or removed from the up down...

Page 92: ...accessed only by using Bridge Full software can be specified The number selected should be kept to the minimum necessary in order to reduce the number of Goto View More displays Once created a Bridge screen can be copied to one or more recorder screens 1 to 24 if required making it accessible from the recorder Root Menu Goto Group Goto View Group 1 Home Operator File Goto View Goto Group Message Lo...

Page 93: ... ac cess level must have Connect from remote enabled in the Security Access menu section 4 4 1 Apply Discard On Media Full Media Size 30 4746094 Mb Overwrite Media Full event limit Select Overwrite or Stop Removable Media Capacity 3 3 1 8 Days 100 Archive to Media Compression Automatic Select archive frequency Normal Flash Size 9 9 2 5 Mb Shortest Trend History G r o u p 1 Select Normal or High Sh...

Page 94: ...2 above CSV CHECK BOXES DATE TIME FORMAT These appear only if the Media File Format or FTP file format are set to either CSV or Binary and CSV Refer to CSV Files at the end of this subsection 4 3 5 SHOW This allows the fields which are to appear below Show to be applicable to the local memory device Lo cal Settings or to the setting up of a remote host path for archiving purposes Remote settings The...

Page 95: ... and on the exact nature of the data Rapidly changing values use more space than static slowly changing values When archiving to Floppy disks via USB port this field remains empty until after the first archive has taken place MEDIA FULL EVENT LIMIT For Local setting only this allows the user to specify a percentage full value for the storage medium at which the event source Archive media full is tri...

Page 96: ...st computer Apply Discard On Media Full Media Size Mb Media Full event limit Disk Archive Capacity Days Archive to Media Compression Flash Size Mb Shortest Trend History Binary format only Show Duration Days Media file format CSV include Values CSV include Messages CSV include Header details CSV include Column headings CSV Date Time format CSV use Tab delimiter 30 4746094 Overwrite 3 3 1 8 100 Non...

Page 97: ...decimal part of the value represents the latest 6 hours so DDD DDD 25 represents 0600 hrs DDD DDD 5 repre sents noon etc Numeric format is more easily interpretable by some spreadsheets than Text format is Tank1 Temp1 Tank1 Temp2 Tank1 Temp3 Tank2 Temp1 Tank2 Temp2 Tank2 Temp3 Group Name Difference Tank Temps Date Time Mac Address Name Tank1 Temp1 Tank1 Temp1 Tank1 Temp1 Tank2 Temp1 Tank2 Temp2 Ta...

Page 98: ...st any one or more alarms is active Global Unack d alarm The event is active as long as there is an unacknowledged alarm present Comms channel timeout The event is set if no communication has been made with Comms channels within the Comms channel timeout period set in Instrument configuration sec tion 4 3 1 The source is reset when the next communication occurs Timer active The event is triggered w...

Page 99: ...rchive medium has reached the fullness defined in Ar chive configuration section 4 3 5 Invalid Password Entry Transient event at the point of an invalid password entry attempt User Login Account Disabled Transient event at the point when an account is disabled because the number of password re tries has been exceeded Section 4 4 2 Available only if the Audi tor 21CFR11 option is fitted User Logged In...

Page 100: ...ilst the batch is running With Source 2 Sense Not Source 2 the event is active whilst the batch is not running DESCRIPTOR Allows a text string to be entered as the event title See section 3 3 1 for text entry techniques JOB NUMBER Select the required job number for this event CATEGORY Select the required job to be carried out when the channel is in alarm e g Enable recording See section 4 7 for a ...

Page 101: ...ove Text For unlatched buttons this allows entry of the legend which is to appear on the button when displayed For latched buttons this is the legend which appears when the but ton is in its non active off state Latched Text This field appears only if Type Latched and allows entry of the legend which is to appear on the button when in its active on state Require Signing If this field is enabled then...

Page 102: ...e 5 with Select embedding source Replace 6 with Select point whose descriptor value etc is to be inserted Select message to be con figured Apply Discard 1 The value of The value of 1 2 3 4 5 Source Descriptor Source Value Totaliser 1 Specified Descriptor Totaliser 1 Specified Value Config Revision Blank Absolute Enable Type high or low Threshold Status Deviation Enable Type in or out Reference Dev...

Page 103: ...for Group mode Instrument Name Allows the Instrument Name as entered in Configuration Instru ment section 4 3 1 to be included in the message Instrument Number Causes the instrument number Network Address Section 4 5 1 to be embedded Config Revision Embeds the Config File Version number System About section 4 6 9 in the message Local User Embeds the currently logged in user e g Engineer John W etc n ...

Page 104: ...eric keyboard and insert 1 2 3 4 within the braces to give 1 2 3 4 4 Access the Alphabet keyboard and insert text and spaces The value of 1 2 3 4 5 Set Replace 1 to Source Descriptor 6 Set Replace 2 to Source Value 7 Set Replace 3 to Specified Descriptor 8 Set 3 source to Tot one 9 Set Replace 4 to Specified Value 10 Set 4 source to Tot one The result of this is that should the channel 2 alarm go ac...

Page 105: ... The import export Linearisation tables feature described in Save Restore section 4 2 offers an alterna tive way of entering linearisation tables Figure 4 3 9a shows the default configuration page Figure 4 3 9b shows a simple table for relating water depth to water volume for a cylindrical tank with a conical bottom User Linearisation Descriptor Format Number of Points X1 Y1 X2 3 UserLin3 Numeric 2...

Page 106: ...o the table where N is the Number of Points entered above Y1 to YN The resulting corresponding output values from the look up table Figure 4 3 9b Sample User Linearisation table 6 5 metres 3 metres 2 metres 10 20 30 40 50 60 Volume cubic metres 0 1 2 3 4 5 6 7 8 9 Depth metres 0 1 0 0 0 0 0E0 0 0E0 2 0 5 0 074 0 5E0 7 4E 2 3 1 0 589 1 0E0 5 89E 1 4 1 5 1 988 1 5E0 1 988E0 5 2 4 712 2 0E0 4 712E0 6...

Page 107: ...created for each batch For each batch start a start message is printed DD MM YY HH MM SS Batch start User Full Name Where DD MM YY is the date HH MM SS is the time and User Full name is either the current user name the security level e g Engineer or Automatic if the batch has been initiated by job or Modbus if trig gered remotely A similar message is printed at Batch Stop There are no stop message...

Page 108: ...ditable The remaining 12 entries of up to 60 characters each are freely editable This is a different list from that entered for Operator notes in Instrument configuration section 4 3 1 ENABLE Allows the batch function to be switched on or off BATCH MODE Allows batch mode to be selected as Continuous or Start Stop Enable Batch mode Batch Fields Field 1 On start log 4 On stop log On new clear 1 1 Nam...

Page 109: ...Use Counter is selected only Counter 1 be used as the batch initiator Other counters may be selected but operation is not guaranteed FIELDS 2 TO 10 Fields 2 to 10 are also used as headings for batch information Values for these headings must be en tered by the operator prior to Batch initiation See also On new clear below Headings can be up to 20 characters long including spaces ON START LOG This ...

Page 110: ...RATOR INITIATION This section describes how the operator initiates a new batch Batches can be initiated from any of the trend bargraph or numeric display modes but the start stop and other messages appear only on the Vertical Trend screen in the trend history display and in Message Log Batch information and status are retained whilst power is off Option Menu Batch Enter History Channel Cycling Off...

Page 111: ... the Start button initiates batch recording Operation of the Store button saves the configuration for later initiation by job by counter or via MODBUS TCP The Values entry page is replaced by the batch status page figure 4 3 10c this time showing details of the batch in progress This page allows the batch to be stopped or a new one triggered Note Text may also be entered using a suitable keyboard co...

Page 112: ...ig Revision 48 Security Revision 1 11 07 06 12 14 31 Batch start Automatic Operator entries Batch start message 480 00 560 00 Touching this area calls the batch status page Date and time automatically printed Batch trigger source Figure 4 3 10c Status page Batch running BATCH MESSAGE DISPLAY The messages are displayed on the Graph Trend display as shown in figure 4 3 10d below This figure uses the e...

Page 113: ...have been entered as described above for Operator initiation then the Store button touched The On new clear setting is ignored the stored values being used each new batch Batch start messages are of the form DD MM YY HH MM SS Batch start Automatic Batch recording cannot be stopped by Counter action MODBUS INITIATION In order to initiate batch recording via MODBUS TCP a Batch Start flag has to be se...

Page 114: ...r 26 Channel 1 75 100 Maths Number 1 Fo 1 Select maths channel number Value Current value 32 65 Reset now Mins Reset button appears only for resettable functions PV Format Numeric Select Alarm number Temperature interval 10 Units Mins Scale high 60 Select Numeric Elapsed Time Scientific Time or Date A B Switching Mins Figure 4 3 11a Maths configuration menu typical varies from function to function ...

Page 115: ... the minimum of the remaining channels Group maximum The highest value of any of the channels in the source group For example in a group of four channels whose instantaneous values are 4 8 2 and 6 the group maximum is 8 The required source group is selected by picklist Should a channel return a non valid value it is excluded from the calculation and the result of the function is the maximum of the...

Page 116: ...y of the points in a selected source group since last reset The function ignores points that are not producing valid PV A disable job stops the function reading its input A reset job sets the func tion to the current minimum value within the group Note that for proper opera tion the maths function must be in a group which is not the source group If this is not the case it will always see itself as...

Page 117: ...ous Emissions Monitoring applications Relative Humidity This uses wet and dry bulb temperatures and atmospheric pressure inputs to produce a percentage Relative Humidity reading Zirconia probe Allows oxygen concentration and oxygen potential to be determined by solving the Nernst oxygen equation Timestamp When triggered by an event or alarm job this causes the current number of mil liseconds since...

Page 118: ...10 To enter a value of 0 0004196 the entry would be 4 196E 4 Time date For timestamp functions displays the timestamp as time or date as selected instead of a number of milliseconds as would be displayed in numeric format Notes 1 Strictly this is a number less than 10 as 10 would be 1 0E1 2 There must be at least one number after the decimal point REMAINING CONFIGURATION ITEMS The remaining configu...

Page 119: ...ired Figure 4 3 11c shows the configuration fields for measuring Fo using channel 1 as the temperature input channel Fo values for target temperature 121 1 C and z value 10 C and 75 C as the low cut off value below which killing credits are not to be counted Function fValue F value of Sterilizing Temp 121 1 Temperature interval Low cut off Channel 1 75 Maths Number 2 Math 2 Value OFF Reset now 10 Fi...

Page 120: ...9 296 8 296 4 4116 0 518 4 296 8 259 8 188 5 461 4 RG J kg K Gas where QMt Mass flow in kg sec at time t K Scaling factor see below Rg Specific gas constant in J kg K see below Z Compressibility factor see below Flowt Measured value from the flow meter at time t AbsPt Absolute pressure of the fluid at time t in kPa A Temp Temperature of the fluid in Kelvins SCALING FACTOR This is determined from an ass...

Page 121: ...t channel measuring the flowmeter output to be entered Temperature Allows the input channel measuring the fluid temperature Kelvins to be entered Absolute Pressure Allows the input channel measuring the absolute gas pressure kPa A to be entered Scale o p Full scale output from the flowmeter in flowmeter units S Ma Full scale input range set for Flow channel in flowmeter units mamax Gas Constant the rel...

Page 122: ...e up stream tapping at time t in kPa A Temp Temperature of the fluid at the up stream tapping in Kelvins SCALING FACTOR This is determined from an assumed value of Qm at a known DeltaP AbsP and Temp The value is chosen to give an output within the range low scale to high scale SPECIFIC GAS CONSTANT The specific gas constant for any gas is available from published tables For convenience the value for...

Page 123: ...Units 1 Math 1 123 4567 Channel 2 Channel 3 Figure 4 3 11e Root mass flow menu Delta Pressure Allows the input channel measuring the differential pressure output from the orifice plate to be entered Temperature Allows the input channel measuring the fluid temperature Kelvins at the upstream tapping to be entered Absolute Pressure Allows the input channel measuring the absolute gas pressure kPa A to b...

Page 124: ...esponds to the kinetic effects of time tempera ture distribution The recorder calculates MKT using the equation below where Tk The required mean kinetic temperature in Kelvins H The heat of activation R The universal gas constant T1max The highest temperature reached during the first measurement period in Kelvins T1min The lowest temperature reached during the first measurement period in Kelvins TNm...

Page 125: ...since the last sam ple are entered into the equation Heat of Activation The default value is an average value based on many common organic reactions Al lows the user to enter an alternative value if known EXAMPLE 1 To Produce a 4 weekly value of MKT taking samples every day Number of samples 28 Sample interval No of seconds in a day 24 x 60 x 60 86 400 EXAMPLE 2 To produce an annual value of MKT t...

Page 126: ...ssure AppearsonlyifUse Pressure Select Constant orthenumberofthechannelsupplyingthesteam pressure If Constant is selected a further box allows a value for the constant to be entered Table 4 3 11b below gives multipliers for converting some common pressure units to MPa More details may be found at websites http www ex ac uk trol scol ccpress htm and http www on lineconversion com pressure htm among...

Page 127: ...2 0 009 807 Tons UK ft2 0 1 073 Tons US ft2 0 09 576 Water feet of 0 002 989 Water inches of 0 0 002 491 Water mm of 0 000 009 807 Pressure units Multiplier for MPa Function Multiply by Constant Value Units Maths Number Value Units Apply Discard Descriptor Scale low Scale high MPa MPa Multiply Channel 3 0 006895 MPa 2 Steam Pressure 0 0348 Constant Steam Pressure 0 1 Table 4 3 11b Pressure unit co...

Page 128: ...s only if Use Pressure Select Constant or the number of the channel supplying the steam pressure If Constant is selected a further box allows a value for the constant to be entered Dryness Enter a value between 0 and 100 to represent the dryness of the steam 0 no vapour 100 no liquid Notes 1 The units of kg sec and m3 sec are used above for simplicity In fact any time unit can be used For example ...

Page 129: ...e used For example if the measured flow is in m3 hour then the Mass flow will be in kg hour 2 ASME Steam tables 1999 from IAPWF IF97 where QEt Heat energy consumed in kJ sec at time t Note 1 Flowt Measured flow in m3 sec Note 1 VLT1 Volume of liquid per kg of steam m3 kg at temperature T1 C ΔVT1 VVT1 VLT1 where VVT1 is the volume of vapour per kg of steam at temperature T1 C d Dryness factor between ...

Page 130: ...ly if Use Temperature Select Constant or the number of the channel supply ing the steam temperature If Constant is selected a further box allows a value for the constant to be entered Inlet Pressure Appears only if Use Pressure Select Constant or the number of the channel supplying the steam pressure If Constant is selected a further box allows a value for the constant to be entered Inlet Dryness ...

Page 131: ...me Int P Input value last time i e this time P P Sample period i e this time last time in seconds Only periods that are a multiple of 0 125 seconds are accepted R Scaling factor Generally R is the number of seconds in the required per unit time value For example if R 1 the rate is per second if R 60 the rate is per minute if R 3600 the rate is per hour Note For channels being read over Modbus the ...

Page 132: ... prescribed for the particular process Measured O2 measured oxygen entered as a channel number gas analyser input See application note below Measured Gas the measured gas entered as a channel number gas analyser input APPLICATION NOTE Some Authorities allow Oxygen correction to be made ONLY if the Measured Oxygen value is above a limit specified by such Authorities For the oxygen correction functio...

Page 133: ...er Value Units Units Apply Discard Relative Humidity 6 66E 4 Channel 1 1 Math 1 0 0000 Channel 2 Channel 3 Units Geometric height metres Pressure Bar 1 04365 1 01325 0 983576 0 954612 0 926346 0 898762 0 845596 0 795014 250 0 250 500 750 1000 1500 2000 Table 4 3 11 c Height versus atmospheric pressure Where RH Percentage relative humidity A0 6 17204663 x 10 3 A1 4 28096024 x 10 4 A2 1 53342964 x 1...

Page 134: ...r than 973K 700 C The equation solved by the maths function is Function Probe temperature Probe emf Reference Partial Pressure Maths Number Value Units Units Apply Discard Zirconia Probe Channel 1 1 Math 1 0 0000 Channel 2 Units 20 95 Figure 4 3 11r Zirconia probe function configuration menu To obtain a useful result it is necessary to scale correctly The channel which is measuring the probe output...

Page 135: ...ont ZIRCONIA PROBE Cont 200 180 160 140 120 100 80 60 40 20 0 0 01 0 1 1 10 100 1 8 6 4 2 1 8 6 4 2 1 8 6 4 2 1 8 6 4 2 1 Probe EMF mV Percent Oxygen 1 3 0 0 C 1 1 0 0 C 5 0 0 C 1 0 0 0 C 6 0 0 C 7 0 0 C 8 0 0 C 1 2 0 0 C 1500 C 1400 C 9 0 0 C 4 0 0 C 3 0 0 C Figure 4 3 11s Probe emf versus temperature ...

Page 136: ...calories T Probe temperature in Kelvins Op Partial pressure of oxygen in the reference atmosphere in atmospheres It can be shown that because the oxygen potential of air is essentially constant over the range 870 to 1450 kelvins the zirconia probe output is proportional to the oxygen potential of an atmosphere accord ing to E 10 84 T 40 mV in the range 870 to 1450 K Thus it is possible to measure ...

Page 137: ...2 2H2 O2 2H2O T T M m M M M M M M M T T t T m m t 50 100 150 200 250 0 500 1000 1500 2000 B Degrees Celsius Oxygen potential kilocalories milliVolts 2Zn O 2 2ZnO 2C O 2 4Cr 3O2 2Cr2 O3 2Mn O2 2MnO 4V 3O2 2V2 O3 Si O2 SiO2 Ti O2 TiO2 T 4Al 3O 2 2Al 2 O 3 Zr O2 ZrO2 2Mg O 2 2MgO 2Be O2 2BeO Th O2 ThO2 4Cu O2 2Cu2O 6FeO O2 2Fe3O4 S2 2O2 2SO2 4Ta 5O2 2Ta2 O5 Change of state Element Oxide Melting point...

Page 138: ... min temp User defined descriptor 1 Group 1 minimum 234 67 Group Minimum 1 Furnace 1 Minimum Channel Descriptor Temp 1 Figure 4 3 11u Group minimum configuration page User Defined Descriptor This allows a descriptor to be entered in the normal way For example Furnace 1 min temp This de scriptor is copied to the Maths Number field at the top of the display page Minimum Channel Descriptor This selectio...

Page 139: ... 1 Minimum resulting in a message such as 12 07 06 14 22 06 Lowest temperature is 790 00 Units at chan Temp 3 where Units is the text entered in the Group Minimum maths channel configuration not that for the input channel although typically they would be the same Note The Group configuration checkboxes for maths channels with Minimum Channel Descrip tor selected are greyed thus preventing such chann...

Page 140: ...ts that are to be used 25 max Inst cal temp n The nth calibration point where n 1 to the Inst calibration points value Inst cal corr n The correction value for the nth calibration point T C calibration points Enter the number of Thermocouple calibration points that are to be used 25 max T C cal temp n The nth calibration point where n 1 to the T C calibration points value T C cal corr n The correc...

Page 141: ...ing_8 Read only 3005 12293 4 Spare 3009 12297 4 Ch1 Descriptor Channel descriptor up to 20 characters String_20 Read only 300D 12301 10 Spare 3017 12311 10 Ch1 No of alarms Number of alarms on this channel Uint16 Read only 3021 12321 1 Ch1 PV format Enum Read only 3022 12322 1 0 Numeric 1 Digital strings Spare 3023 12323 60 Ch1 Alarm 1 enable Alarm 1 enable Enum Read only 305F 12383 1 0 Off 2 Latc...

Page 142: ...Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare IEEE 32 BIT CHANNEL CONFIGURATION DATA The following table shows addresses for the specified 32 bit floating point values for Maths channel 1 Generally Parameter ...

Page 143: ...m 1 inactive 1 Alarm 1 active Read only Bit 1 0 No alarm 1 Ack required 1 Ack required Read only Bit 2 1 Acknowledge alarm 1 Read Write Bit 3 Spare Bit 4 0 Alarm 2 inactive 1 Alarm 2 active Read only Bit 5 0 No Alarm 2 Ack required 1 Ack required Read only Bit 6 1 Acknowledge alarm 2 Read Write Bit 7 Spare Bit 8 0 Alarm 3 inactive 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack re...

Page 144: ...in Annex A for details CONFIGURATION Figure 4 3 12 below shows a typical enabled totaliser configuration page Totaliser Number Allows any of the available totalisers to be selected from the picklist for configura tion Enable Allows the user to enable disable the totaliser Value Shows the dynamic current value of the selected totaliser Total of Allows an input channel or a maths channel to be selecte...

Page 145: ... hour then the period scaler would have to be the number of seconds in an hour 3600 Unit Scaler If for example the input channel is in litres per hour the totalised value will be in litres unless the unit scaler is set to a value other than 1 If it is more convenient the totalised value can be in thousands of litres by setting the unit scaler to 1000 Setting the unit scaler negative causes the tot...

Page 146: ...mal places Number of decimal places 0 to 9 Uint16 Read only 6F3E 28478 1 used by all scaled parameters except where stated Colour Channel colour 0 to 55 See Annex B for definitions Enum Read only 6F3F 28479 1 Units Units string up to five characters String_5 Read only 6F40 28480 3 Spare 6F43 28483 2 Open string Open Digital Input string up to eight characters String_8 Read only 6F45 28485 4 Spare 6F...

Page 147: ... required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare IEEE 32 BIT CONFIGURATION DATA The following table gives addresses for the specified 32 bit floating point values for Totaliser 1 Gener ally Parameter...

Page 148: ...or 1 Channel off 6 Overflow 2 Over range 7 Bad PV 3 Under range 8 No data 4 Hardware error Totaliser 1 Alarms Alarm information Uint16 FB82 64386 1 Bit 0 0 Alarm 1 inactive 1 Alarm 1 active Read only Bit 1 0 No alarm 1 Ack required 1 Ack required Read only Bit 2 1 Acknowledge alarm 1 Read Write Bit 3 Spare Bit 4 0 Alarm 2 inactive 1 Alarm 2 active Read only Bit 5 0 No Alarm 2 Ack required 1 Ack req...

Page 149: ...cale High Units Units Zone Low Zone High Colour Scale Type Select None or Linear None A B Switching Select Job number 1 Counter 1 1 Off 1 No Action OFF Units 0 Counter 1 0 1 0 100 0 Figure 4 3 13 Typical Counter configuration menu CONFIGURABLE PARAMETERS Counter number Allows any of the available counters to be selected for configuration Enable Allows the user to start stop counting by enabling disa...

Page 150: ...al places Number of decimal places 0 to 9 Uint16 Read only 8EE2 36578 1 used by all scaled parameters except where stated Colour Channel colour 0 to 55 See Annex B for definitions Enum Read only 8EE3 36579 1 Units Units string up to five characters String_5 Read only 8EE4 36580 3 Spare 8EE7 36583 2 Open string Open Digital Input string up to eight characters String_8 Read only 8EE9 36585 4 Spare 8EE...

Page 151: ...larm 3 inactive 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare IEEE 32 BIT CONFIGURATION DATA The following table gives addresses for the specified...

Page 152: ...f 6 Overflow 2 Over range 7 Bad PV 3 Under range 8 No data 4 Hardware error Counter 1 Alarms Alarm information Uint16 FC4A 64586 1 Bit 0 0 Alarm 1 inactive 1 Alarm 1 active Read only Bit 1 0 No alarm 1 Ack required 1 Ack required Read only Bit 2 1 Acknowledge alarm 1 Read Write Bit 3 Spare Bit 4 0 Alarm 2 inactive 1 Alarm 2 active Read only Bit 5 0 No Alarm 2 Ack required 1 Ack required Read only B...

Page 153: ...t at 30 seconds past each hour Note Times are not adjusted for Daylight Saving changes Thus if the timer is set to trigger on a daily weekly etc basis then during Summer Time the trigger will occur an hour late i e at 01 00 hrs instead of at midnight The full range of jobs is available as described in section 4 7 Timer Active is defined as an internal event trigger section 4 3 6 CONFIGURATION Figur...

Page 154: ...rom a picklist of 1 to 23 Midnight and Any Minute allows a minutes number to be entered from a picklist of 0 to 59 and Any Seconds allows a seconds value to be entered from a picklist of 0 to 59 and Any Duration Allows the user to enter a count down time period in seconds Repeat after Allows the user to enter a repeat rate It should be noted that the repeat value in cludes the duration time For ex...

Page 155: ... s serial communications port to be used as Modbus master or Modbus slave When acting as a master the unit can communicate with up to either 16 slaves standard or 32 slaves op tion Use of the Serial port is complementary to the use of Ethernet connections Note When configuring a unit as a Modbus slave it is recommended that the Instrument and Point Configurations give easily identifiable instrument a...

Page 156: ...Communications configuration menu ASCII input Apply Discard 250 Baud Rate Stop Bits Parity Data Bits Timeout First Start Char Second Start Char First End Char Second End Char Group 1 Group 2 Group 3 Group 4 Group 5 Group 6 19200 1 None 8 ms 0 13 Select required Baud rate Select 1 or 2 Select None Odd or Even Select 7 or 8 Enter required Timeout value Enter decimal ASCII value between 0 and 127 0 no...

Page 157: ...ic redundancy check CRC error The Reset Error Count key is used to reset the count to zero PROTOCOL ASCII input Modbus Slave Modbus Master can be selected Master or Slave selections must match the switch settings for the relevant port as shown in table 2 2 2b CONNECTION Only EIA485 available as transmission standard Three wire or Five wire working is selected by means of a switch accessed from the...

Page 158: ...r to section 9 3 3 GROUP SELECTION For ASCII input protocol this allows groups to be deselected selected for receipt of the messages A checked box indicates that the associated group will receive the messages ENABLE ERROR CODE B For Modbus Master only If enabled this causes an error code B to be generated in the event of a timeout or a Cyclic Redundancy Check CRC error ENABLE TALK THROUGH For Modb...

Page 159: ...f message characters are configured but neither end characters nor timeout have been con figured then this is an invalid configuration Should this configuration be a requirement if the same characters are entered as end of message characters instead then each message will be sent to the groups when the next message is received 5 If no start or end of message characters are entered and no timeout value...

Page 160: ...e instrument Once the remote unit has been recognised by the master the master and slave units can be configured to carry out the following 1 By setting a master input channel to Type Master Comms selected parameters can be read by the master from a selected slave This master channel can then be included in display groups can have alarm setpoints run jobs etc independently of the original channel I...

Page 161: ...cted as Network type Appear only if Login Required is selected Figure 4 3 16a Master Comms configuration menu CONFIGURABLE PARAMETERS Priority intervals This allows three levels of update rate to be entered These rates are used in point configuration to define how often a value is read In order to optimise the perform ance of the serial link it is recommended that the slowest rate consistent with req...

Page 162: ...nt configuration section 4 3 1 For other instrument the documentation supplied with those instruments should be referred to Profile A pick list of supported instrument types Third party is used as a default and for non listed instrument types This field is updated automatically if the slave is Detected Timeout Allows a timeout period to be set for the read write process See Retry below and Disable Re...

Page 163: ...list in the Master Comms configura tion page If Overwrite existing slaves is enabled then newly found instruments will temporarily over write instruments previously configured there The list becomes per manent when the Modbus configuration page Apply key is operated but any of the slaves can be edited if required prior to this Timeout The search for a slave is aborted if it does not respond within th...

Page 164: ...mps 1 at 149 121 130 211 1 Furnace Temps 2 at 149 121 130 211 2 Instrument at 149 121 130 232 1 Instrument at 149 121 130 236 1 2747 at 149 121 130 237 1 Abort Start Discard Apply Re Scan If Overwrite existing slaves is not enabled AND the number of detected slaves is greater than the number of free slots then this text reads Please select a maximum of N slave devices where N is the differ ence be...

Page 165: ...ilar situation except that master 2 is not just a gateway but is a meas uring device in its own right In such a case Socket 1 is used for high speed communications between master 1 and master 2 and Socket 2 is used to link master 1 to the slaves individually In this case Share Sockets should be disabled for master 2 and enabled for all other devices Slave 1 IP 123 123 1 2 Modbus Address 1 Slave 2 ...

Page 166: ...efined has been selected as Parameter In such a case the user must determine the required register number from the documentation supplied with the slave Note For completeness figures 4 3 16e 4 3 16f and 4 3 16g show all possible configuration fields The fields that actually appear are slave model and parameter dependent RECORDER DATA ACQUISITION UNIT CONFIGURABLE PARAMETERS Channel Number Value Input T...

Page 167: ...alue 65 535 Hex FFFF with intermediate values having proportionate values For example the value 15 would be represented as 32 767 7FFF for a channel scale 0 to 30 as would a value of 50 for a channel scaled 0 to 100 and a value of 45 for a channel scaled 30 to 60 In order to convert this reading to an understandable value a scaling factor must be entered If the low and high scale entries match the...

Page 168: ...dium Priority Unadjusted Select Required slave 1 Numeric 0 1 0 100 4 0 Units Read 1 1 Trigger 1 Read 1 0 4670 Master Comms 1 Furn 1 Control Working Setpoint Select Required slave parameter Select required loop Select iteration rate for parameter update Units Units Reflects descriptor entry Channel Number Value Input Type Slave Digital Parameter Loop Number Process Value PV Format Span Low Span Hig...

Page 169: ...aves in the Master Comms Configuration described above Digital Allows data to be read into a digital input Parameter Allows the user to select a specific parameter table 4 3 16a shows a typical set or User defined to be selected User defined allows a decimal register address to be entered see User defined below Loop number Allows the user to enter a Loop Number for the parameter read Process Value Allo...

Page 170: ...e 0 for Absolute low 1 for absolute high 2 for Deviation in 3 for Deviation out 4 for Rate of change high or 5 for Rate of Change low Channel Number Value Input Type Slave Digital Parameter Function Code Register Data Type Scaling Decimal Places Process Value PV Format Span Low Span High Zone Low Zone High Decimal digits UInteger 16 Bit Unadjusted Select required slave Decimal Places 0 1 0 100 1 R...

Page 171: ...vant data types is given in section 8 4 Scaling Whether Scaling appears or not is Model and Parameter dependent If scaling is required the choice may be Decimal Places or High Low again according to Model Decimal Places allows a dividing factor to be entered An entry of 1 divides the returned value by 10 An entry of 2 divides by 100 etc for successful implementation there must be a sufficient numbe...

Page 172: ...6 Not used Always zero 64 7 Channel status 0 No failures 1 Channel failure 128 Bit Item being tested Status Value Figure 4 3 16h Default Open Closed depictions STATUS BITS This allows the user to view the value of a bit in a status word such as Instrument Status Channels in Group etc The relevant Register is accessed by entering its decimal number into the Register field which appears when User Defi...

Page 173: ...Bit Position Process Value Zone Low Zone High Colour Open String Descriptor Alarm Number 75 100 0 Card in 1 Trigger Discard Apply 1 Card in Card in Master Comms 1 Recorder User Defined 22 Function Code Read input reg 4 Bit from register Medium Priority 3 Card in Closed String Card out Digital Card out Dwell 0 s Job Number 1 Enable Type Active when Category Message Send Message s to All Groups Firs...

Page 174: ...has been completed with Remote devices 1 2 and 3 set up as Furn1 Control Furn1 Record and Furn2 control respectively b all recorders are of the type described in this manual Other types of slave may need more inputs or different inputs to be entered EXAMPLE see figure 4 3 16j to Read Loop1 PV from Controller 1 to Channel 1 of Recorder 1 the master Read Channel 1 from Recorder 2 to Channel 2 of the ...

Page 175: ...een entered The span zero and span high values should match those of the PV being read Medium Priority Unadjusted 1 Numeric Low Priority 0 100 0 100 4 0 Units Furn1 PV1 1 Trigger 1 Furn1 PV1 33 2453 Master Comms 1 Furn1 Control Process Value Units Units Channel Number Value Input Type Slave Digital Parameter Loop Number Process Value PV Format Span Low Span High Zone Low Zone High Max Decimal Digi...

Page 176: ...umber Value Input Type Slave Digital Parameter Point Type Point Number Process Value PV Format Span Low Span High Zone Low Zone High Max Decimal Digits Colour Units Descriptor Configuration Data Alarm Number Enable Medium Priority Unadjusted 1 Numeric Low Priority 0 1000 0 100 4 1 Units Furn1 Temp 1 1 Trigger Discard Apply 2 Furn1 Temp1 658 3654 Master Comms 2 Furn1 Record Process Value Channel Un...

Page 177: ...Descriptor Source Default On Error Write Default 1 Furn1 Temp 1 Discard Apply Master Comms 3 Furn2 Record Comms Channel Channel Medium Priority 2 Furn1 Temp1 0 1 Furn1 PV1 Channel Number Value Input Type Scale Low Scale High Unadjusted 0 1000 1 Furn1 Temp1 658 3654 Slave Comms Deg C Deg C Units Deg C Scale Type Linear Scale Divisions Major Scale Divisions Minor 10 1 Descriptor Furn1 Temp 1 A B Swi...

Page 178: ... incremented If not successful one or more of the error box values is incremented Figure 4 3 16p shows a typical page Slave 1 Furn recorder 1 Reset Diagnostics Initiate Comms Test Archive System Save Restore Config Security Network Clock Locale Upgrade Master Comms Diagnostics Ethernet diagnosticcs Actual High Priority Modbus Address Slave Status Seconds Actual Medium Priority Actual Low Priority ...

Page 179: ... Master Comms Slave Select the slave to be written to Parameter Select required parameter from picklist varies according to slave type model Scaling If this field appears depends on slave type the Low and High scaling should match that of the slave Channel being written to Point Type Allows a point type to be chosen from a picklist Picklist items vary according to slave type model Point Number For ...

Page 180: ...register location WRITING TO A KNOWN DEVICE Figure 4 3 18a shows the configuration page for writing a value from the master unit to a known slave unit Enable Demand Type Status Master Comms Apply Discard Write number 1 Write_1 Select the Write num ber to be configured Select Master Comms or Off OK Demand Write Slave 1 Furn 1 Recorder Select destination slave Parameter Alarm setpoint 2 Select parame...

Page 181: ... Descriptor Allows a descriptor to be entered for the Write Source Allows the source of the Write to be chosen from a picklist containing Constant plus all points in the recorder Default Allows a value to be entered for use as a default to be written to the destination point Appears if Source Constant or for any other source if the On Error Write Default checkbox see below is enabled Allow Constan...

Page 182: ...ple reg 16 Float 32 Bit Figure 4 3 18c Demand Writes to specific register CONFIGURABLE PARAMETERS This contains details of parameters unique to Demand Writes to specific registers Other parameters are as described above Function Code Allows the Modbus function code 6 or 16 to be selected See the documentation supplied with the slave for a list of supported Modbus codes for this instrument see sectio...

Page 183: ...es For example the value 15 would be represented as 32 767 7FFF for a chan nel scale 0 to 30 as would a value of 50 for a channel scaled 0 to 100 and a value of 45 for a channel scaled 30 to 60 In order to convert this reading to an understand able value a scaling factor must be entered If the low and high scale entries match the slave channel s scale the master reading will be the same as the sla...

Page 184: ...bedded values alarm status batch status etc as described in section 4 3 8 E MAIL CONFIGURATION The figure below shows the e mail configuration page using fictitious names for email server address information Mail Server Port Number Sender Errors To Retry Time Recipient List Descriptor Rcpt1 Rcpt2 Rcpt3 Rcpt4 Rcpt5 Rcpt6 Rcpt7 Rcpt8 Rcpt9 Rcpt10 Email Number Descriptor Protocol Subject Text Include Me...

Page 185: ...allow 10 recipients e mail addresses to be entered for the selected list The first valid address appears in the To part of the e mail header subsequent valid addresses appear in the Cc part of the e mail header note 2 Email Number Allows an e mail to be selected for configuration Descriptor Allows a descriptor to be entered for the e mail This appears in the list of e mails when setting up a job and...

Page 186: ... to the generating instrument or local to the recipient de pending on the recipient s mail host configuration The header is important in the prevention of spamming The instrument adheres to the RFC2822 stand ard with respect to e mail headers Some servers are stricter than others and it is not guaranteed that an e mail generated by the instrument will not be interpreted as a spam message by the rec...

Page 187: ...onfiguration page for the e mail and List N is the recipient list to whom the e mail was sent 3 Access to e mails is restricted to users with Full Configuration permission 4 Signing Authorizing restrictions can be applied only to e mails generated by Event button opera tion as part of the Event button s configuration section 4 3 7 5 The instrument implements the Simple Message Transfer Protocol SMTP ...

Page 188: ...gure 4 3 20a Reports Configuration REPORT Allows the user to select the required report number for configuration DESCRIPTOR A name for the Report can be entered here NUMBER OF FIELDS Select 0 to 10 for the number of items to be included in the report FIELD N TYPE N 1 to the number of fields selected in the previous item Date Time Causes the time and date of report generation to be included in the rep...

Page 189: ...N Cont STYLE Normal always used for this implementation regardless of selection POINT Allows a point to be chosen when Process value has been selected as Field Type The point is selected from a pick list containing all the input channels derived channels totalisers etc in the instrument LINE FEED Not implemented ...

Page 190: ...uration as necessary MESSAGING Ethernet IP uses two forms of messaging UNCONNECTED MESSAGING This is used in the connection establishment process and for infrequent low priority messages The unconnected resources in a device are called the Unconnected Message Manager UCMM CONNECTED MESSAGING This uses resources within each node that are dedicated in advance to a particular purpose such as fre quen...

Page 191: ...which is to be read or written Input tables can be completed by importing a suitable previously configured table by en tering individual parameters into each field by using the Wizard key or by using the Default table and editing it as necessary See Table entry Wizard key and or De fault table below for further details Output tables cannot be edited Input output 2 to 200 As for input output 1 above ...

Page 192: ... n spanhi The Span High value for maths channel n where n 1 to 100 Math n spanlo The Span Low value for maths channel n where n 1 to 100 Math n dp Number of decimal places for maths channel n where n 1 to 100 ERROR MESSAGES If an error is made during editing a brief description of the error can be viewed by operating the Show Errors key Out of Range this means that the channel or maths number is g...

Page 193: ...s decimal places values not supported for channels 76 to 100 Start New Table If ticked default the existing list is deleted and replaced by the Wizard items when configure is operated If not ticked the selected items are appended to the existing table using any empty spaces If there are no spaces the new entries are ignored If there are insufficient spaces the available spaces are filled using lowest...

Page 194: ... 82 pv Channel 82 process value Scaled Read only FCD1 64721 1 Channel 83 pv Channel 63 process value Scaled Read only FCD4 64724 1 Channel 84 pv Channel 64 process value Scaled Read only FCD7 64727 1 Channel 85 pv Channel 65 process value Scaled Read only FCDA 64730 1 Channel 86 pv Channel 66 process value Scaled Read only FCDD 64733 1 Channel 87 pv Channel 67 process value Scaled Read only FCE0 6...

Page 195: ... BETWEEN WINDOWS AND THE PLC NETWORK 1 Click on Start All Programs Rockwell soft ware RSLinx RSLinx Classic The RSLinx Classic window opens 2 Click on Communications and select Configure Drivers When the Configure Drivers window opens select RS232 DF1 devices in the Available Drive Types pull down menu figure 4 3 21d Figure 4 3 21d Configure drivers 3 Click on Add New and enter a suitable Driver Name ...

Page 196: ...or the process to complete and to be vali dated 3 When the update process is complete close the Who Active window Figure 4 3 21f Who active window COMPLETING THE LINK 1 In the File menu select New or click on the New Tool icon The New Controller window opens figure 4 3 21g 2 Select the relevant PLC from the drop down menu Enter a name if required and click on OK After some seconds the selected cont...

Page 197: ...ow 8 Left click on the Program icon figure 4 3 21j and select Go OffLine from the menu which appears Figure 4 3 21i Module Properties Figure 4 3 21j Click on Program icon 9 Download either from Who Active or from the Program icon 10 Connect the PLC to the Ethernet port RJ45 of the PC 11 Restore the RSLinx window In the communications menu Configure Drivers window select Ether Net IP Driver Click on ...

Page 198: ...le item figure 4 3 21n and click on OK or double click on the selected item 4 In the Parameters page that appears figure 4 3 21p enter a name for the module and set the follow ing values Comm Format Data INT Address Host name The IP address of the recorder from Operator Network Address menu Input 100 size 200 Output 112 size 200 Configuration 1 size 0 5 Tick click on the Open Module Properties checkb...

Page 199: ...are set up is a similar way section 4 3 11 4 Set scale units etc to appropriate values Note For the EtherNet IP application the number of decimal places is set to zero by default Editing this value may lead to loss of resolution in the values displayed 5 Configure the EtherNet IP input table as required described earlier in this section 7 Ensure that the PLC is connected to the recorder either dire...

Page 200: ...hannels reverts to that configured before Trial mode was invoked 2 When disabling Trial mode all configuration for the trial features is lost Should the user decide to purchase a trial feature then it is recommended that the trial configuration be saved see section 4 2 so that it may be restored once the purchased trial feature is fitted and enabled keycodes cannot be entered in Trial Mode 3 Trial mod...

Page 201: ...below The Simulation option is not ena bled in Trial Mode TREND FREEZE When this Trend category job section 4 7 10 is initiated the displays are held at their values at the time of initiation When the recorder is unfrozen the displays switch to their current values and the clock will re start from where it stopped No blue line is drawn across the trace to indicate time discontinuity Time change re...

Page 202: ... Login Disabled Edit Own Password Change Alarm Setpoints Acknowledge Alarms Edit Maths Constant Reset maths Preset Totalisers Preset Counters Start reset Timers Set Clock Archiving Control Save Restore Paste Delete Files Full Configuration Full Security Batch Control Can Sign Can Authorize Perform Upgrades Event Permission 1 Event Permission 2 Event Permission 3 Event Permission 4 Event Permission...

Page 203: ...for which the password param eters and login disabled items do not appear Note If the Security management option is fitted and Centralised Security is enabled in the Security Management system sec tion 4 4 2 permissions are Read Only i e not editable at the recorder In such a case permissions can be changed only by using the Security Management software Frederick Bloggs Access when Domain New Passw...

Page 204: ... User The password must also be entered in the Re type Password field If the two differ a warning message Passwords did not match appears when the APPLY key is operated and password entry must be repeated If the pass word does not comply with the minimum length requirements in Security Management if fitted section 4 4 2 a warning message Invalid Password appears when the Apply key is operated and pa...

Page 205: ...vice centre for advice EDIT OWN PASSWORD Allows each user with this permission enabled to edit his her password CHANGE ALARM SETPOINTS Allows each user with this permission enabled to edit alarm parameters under Configuration Channel ACKNOWLEDGE ALARMS Allows each user with this permssion enabled to acknowledge alarms section 3 1 4 EDIT MATHS CONSTANT For recorders fitted with the Maths option only ...

Page 206: ...o the other permissions set for the login providing the security management system Require Authorization is not enabled If it is changes can be made only if the correct password for a user with Can Authorize permission is entered See section 4 4 2 for details CAN AUTHORIZE This appears only if the Auditor 21CFR11 option is fitted If the field is enabled it allows the user to change the configuration ...

Page 207: ...No Auth Reqd Note where Auto Mode is the descriptor associated with the demand write and 19 37 is the value written FORCE CHANGE OF PASSWORD When this checkbox is enabled for a user it means that that user will have to change password at his her next login At next log in a pop up dialogue box requests that a new password be entered If a new password is not entered login is denied Entering the new ...

Page 208: ...utes This field appearsonly if Login timeout is non zero Password Change on Expiry Centralised Security This field appears only if Require Signing is enabled Login By User List This item appears only if the Securiy Management option is fitted If enabled all other security fields can be edited only via Security Management software This item appears only if one or more of Security Management Audit t...

Page 209: ... 06 13 20 42 User Frederick Bloggs login disabled invalid password In order to re enable the login a user with Engineer access level must dese lect Login Disabled in the Access menu described in section 4 4 1 above Passwords expire For Active Directory users this parameter is configured at the Active Directory and the value set at the instrument is ignored For other users this field allows the user ...

Page 210: ...l Note cannot be empty Ok Password Config Pop up appears only if Ok is operated without an operator note having been entered Figure 4 4 2b Signature page Enable Audit trail For either Auditor option if this field is enabled then all changes to configuration are displayed on the chart and become part of the history file for each enabled group The following is an example of how these changes would appe...

Page 211: ...confirmed will the user be able to access the recorder configuration Security Management Option The new password is not written to the Security Man ager until the next deploy after which the expiry period configured for the user with in Security Management is restored The interim expiry period is set to 24 hours and the deploy must be carried out within this period or password expiry will recur Chang...

Page 212: ...e Security manage ment option is fitted When enabled the normal login window appears with a pull down list of users Once a user has been selected the correct password for that user must be entered in order to log in When disabled the user must enter a user name and associated password in order to log in Select the required access level and enter the password if required User ID Logged out Logged ou...

Page 213: ...cters in length If such an entry is made the Password fields described below do not appear and the user must use a network login assigned by the IT department or by the network administrator The domain name appears in the Access menu and can be edited there if required once the Add User pro cedure is complete If Centralised Security section 4 4 2 is enabled this Domain name can be edited only using...

Page 214: ...cts Network logins which would normally be under the control of the user s IT department or Network Administrator Changing the pass word may cause conflicts within the network thus preventing its efficient operation 2 If Active Directory security is set to None section 4 5 1 Network Address menu any at tempted changes to the password will be rejected That is only passwords on a Transport Layer Secur...

Page 215: ...tory server is unavailable the next time the user attempts to log in then if the password is in the cache the login will proceed without further authen tication CLEAR PASSWORD CACHE If necessary the password cache can be cleared by using the Clear Password Cache button confirmation required The cache is also cleared whenever a new user is added to the user list section 4 4 3 or if the login for an ...

Page 216: ...main Controller Active Directory area of the Manage your Server screen click on Man age users and computers in Active Directory Figure 4 4 7b Manage users 2 Right click on the relevant Domain name symbol and select New then Organizational Unit Enter a name for the Unit and click OK Figure 4 4 7c Create new Organizational Unit Continued ...

Page 217: ...boxes are enabled disabled as required Figure 4 4 7d User details screens 4 Once the new user has been created right click anywhere in the screen and select Properties or double click on the user When the Properties page opens click on the Member Of tab figure 4 4 7e 5 Click on the Add key and enter the new group name Click OK 6 The user is now part of the group and should be able to log in using t...

Page 218: ...ble Appear only if Security Manager option enabled Appears only for Get from BootP Server Address Name EuroPRP server enable Active Directory server 123 456 234 1 Active Directory security TLS port 636 Select specify an IP address Get from BootP Server or Get from DHCP Server Password Cache expiry Apply Discard Days 0 Figure 4 5 1 Network addressing INSTRUMENT NUMBER MAC ADDRESS Unique numbers set...

Page 219: ...SNTP CLIENT ENABLE This tickbox allows time synchronisation from a Simple Network Time Protocol SNTP server to be ena bled and disabled When enabled the instrument time is updated every 15 minutes SNTP SERVER If Obtain from BootP server or Obtain from DHCP server is selected as the IP address look up see above then this address appears automatically Otherwise this area allows an IP address to be e...

Page 220: ... is connected to the same network as the server users with a domain configured will be able to login using their normal network login password If Domain name Service is enabled section 4 5 2 then a domain name may be entered here instead of an IP address ACTIVE DIRECTORY SECURITY This item appears only if the Security Manager option is enabled If set to None default then any at tempt to change a pa...

Page 221: ...worked units which contains the recorder Non editable DOMAIN NAME SERVICE DNS Enables the mapping of host names to IP addresses and vice versa PRIMARY SECONDARY DNS SERVER IP addresses supplied by IT department or the Domain manager or Supervisor Notes 1 Any one or more of the above items may be overwritten if IP address lookup is set to Obtain from BootP Server or Obtain from DHCP server as descr...

Page 222: ...on enabled EtherNet IP Clients IP address remains for five seconds after message activity ceases after which appears instead Instrument Number Key Code 8203 WC8N 9F5E 1D41 Apply Discard Key Code File Source Files From Remote FTP Site Upgrade Add new options U p g r a d e s o f t w a r e Language Country Time Zone Use Summertime DST Start at on the in End at on the in Locale Section 4 6 2 English U...

Page 223: ...ction 4 6 9 Copy Now Channel 1 Furnace Temp 1 2 Channel 2 5 Channel 5 Source Type Copy From Copy To Include alarm data Include job data Copy Section 4 6 6 Archive Save Restore Config Security Network System Search Now All Sections Totaliser Preset Section Job Category Job Action Job Search Section 4 6 7 Desktop Data Entry Background Selection Fixed Text Active Text Disabled Text Title Bar Backgrou...

Page 224: ... and end of summertime can be entered using picklists see figure 4 6a Notes 1 Date format DD MM YY or MM DD YY is defined by the language and country selected Time format e g 12 24 hr clock is defined by the country selected 2 When using Bridge software the host PC s locale information and the recorder locale informa tion should match or the displayed time will not be correct Note For more informatio...

Page 225: ... section 5 below for more details Source Files From Allows the user to select Remote FTP site or Local Media Upgrade Initiates upgrade once the upgrade source has been defined see figures below Figure 4 6 3b Remote upgrade details Figure 4 6 3c Local upgrade details CAUTION Power to the recorder must be maintained during the upgrade process or the recorder might not power up If such a situation aris...

Page 226: ...P Clients IP address remains for five seconds after message activity ceases after which Offline appears instead Waiting In Progress Host Reachable Ping Error in value Request Timed Out Host Unreachable Unknown error The default status displayed on power up Displayed whilst waiting for a response from the host A device was found at the specified address Host refused to allow socket connection on th...

Page 227: ... address remains on display for five seconds after which Offline appears instead 4 6 6 Copy This facility allows the user to copy a point or group configuration from one point group etc to one or more others The user may choose whether or not to include alarm and if applicable job data when copying point configurations Descriptors and colour selections are not copied Figure 4 6 6 shows a typical config...

Page 228: ...which support jobs If this box is selected then jobs data is included in the copy For source types that support both alarms and jobs it is not possible to include job data without including alarm data as well Once the copy is complete the user should enter the configuration area of the items that have been cop ied and edit apply the changes etc COPY RULES 1 The first channel on any input card may no...

Page 229: ...ion Job Category Job Action Figure 4 6 7a Job search Section Allows the user to select a point type for the search For example selecting Maths causes the search to be restricted to Maths channels All Sections causes all enabled point types to be included in the search Job Category Allows a job category e g Totaliser to be selected for the search Job Action This depends on the job category For exam...

Page 230: ...text items including key top text menu text scale data title bar legends etc Active Text The colour of all non fixed text such as selectable menu items Disabled Text This allows the user to choose a colour for the text associated with disabled items For example key top legends on the Goto Group menu for groups that are not display enabled Title Bar background The colour of the title bar block at th...

Page 231: ...ll of the different font sizes available except Auto which picks a font size considered appropriate for the size of screen Archive Save Restore Config Security Network System Archive Save Restore Config Security Network System Archive Save Restore Config Security Network System Archive Save Restore Config Security Network System Very small Small Large Very Large Figure 4 6 8b Font sizes ...

Page 232: ...ncluding all items within the menu structures of the Config and Network keys and includes User Screens It does not include those items associated with the Security key Config Revision is printed on the chart at power up and if either Auditor option or if the Batch option is fitted Config Revision is included in the messages associated with these options Notes 1 Config Revision can be used as an input t...

Page 233: ...at e g 15 001 see section 4 4 2 SUPPORT FILE If the unit is not performing as it should e g it resets itself unexpectedly the Support File key allows the user to save critical system files into a single file SupportInfo uhq for despatch to the manufacturer for analysis This file may be saved to the instrument s Compact Flash card or using Bridge Full software to a remote PC For security reasons this ...

Page 234: ...On becoming inactive On acknowledgement 4 7 1 No Action This means that no job action is configured for the trigger source 4 7 2 Totaliser category If the Totaliser option is fitted section 4 3 12 the following jobs become available Preset Loads the selected totaliser with the value set up in Preset in the totaliser s configura tion menu Preset Group Loads all the totalisers in the specified group wit...

Page 235: ...t Sets the selected maths channel value to zero Disable Stops historical functions such as Fvalue Stopwatch and Rolling Average from accumulating fur ther values When the function is subsequently re enabled the function re starts from its pre disabled value Disable has no effect on other functions Switch to B Causes the relevant maths channel to copy source B instead of its normal source A see sec...

Page 236: ...Active Inactive or Acknowledgement Select Preset Disable Increment Decrement Preset group Disable Group Job Number Action Category Group On 1 Group 1 1 Counter Preset Group Acknowledgement Select Required Group Select Active Inactive or Acknowledgement Figure 4 7 5 Clock job menu layout Notes 1 Whenever a time change occurs a green line is drawn across the chart in vertical trend mode 2 The clock ...

Page 237: ...ent via MODBUS TCP section 8 If a batch is already running it will be restart ed In Batch configuration if Scope Group then a specific group can be selected for the batch job to act on if Scope Instrument the Group selection field does not appear Figure 4 7 8 Batch job menu layout Job Number Action Category Timer On Timer 1 1 Timer Reset Active Select Reset Start or Disable Select Required Timer Sele...

Page 238: ...ory is erased only if Simulation option section 4 3 22 is enabled but see also note four Notes 1 The group in question will be recorded only if Recording Enable selected in group Configura tion section 4 3 2 and the job is active 2 If Audit Trail section 4 4 2 is enabled then in order to preserve the audit trail messages will be saved in the group s history files even when recording is not enabled b...

Page 239: ...ed Interval B for as long as the job is active Note If a B value has not been set the default A value will be used instead If the Simulation option section 4 3 22 is enabled the following additional Trend jobs become available Freeze Freezes process variables and trend displays and stops the recorder clock see note When the job deactivates the process values are updated to their current values and...

Page 240: ...g as a mod bus master Job Number Action Category Output On 1 Output Disable Write Active 1 Output 1 Select Active Inactive or Acknowledgement Select required output Job Number Action Category Acyclic On 1 Demand writes Write Active 1 Write 1 Select Required Write number Select Active Inactive or Acknowledgement Figure 4 7 11 Output Job menu layout 4 7 12 Demand Writes category Applies only to reco...

Page 241: ...llow a job to be used to trigger an archive to the instrument s mass storage medium or to a host computer using FTP transfer The following jobs are available Archive Last Hour Last Day Last 7 Days or Last 31 days to FTP Bring FTP archive up to date Cancel Archive to FTP Archive Last Hour Last Day Last 7 Days or Last 31 days to Local device Bring Media Archive up to date Suspend Archive to Media Ca...

Page 242: ...t to Group Report On Select Group or printer if fitted If destination Group select destination group Select the report to be sent Select Active Inactive or Acknowledgement Figure 4 7 16 Report category job menu SEND REPORT TO Group is the only report destination GROUP Allows the destination group to be defined If a group descriptor has been entered Furnace 3 in the figure above then this descriptor ...

Page 243: ...ote The open folder and close folder key functions are the same as the down arrow and up arrow key functions respectively 5 1 FILER OPTION MENU KEYS These keys appear in a pop up menu when the option key is pressed This menu appears only when an actual file has been selected i e it does not appear if a directory folder or volume is selected Cut and paste functions are available only to users with t...

Page 244: ...656 124715008 user Flash 1390592 1361920 Engineer 13 35 59 11 07 06 Hide No batch In Progress mediacard history Name Type Date Bytes group1 Folder 11 07 06 11 40 56 Select volume Select folder Open Folder Root Key Home Operator File Remove Media Goto View Goto Group Root Menu Filer Options New Delete Cut Copy Paste Refresh Engineer 13 36 49 11 07 06 No Batch In Progress mediacard history group1 00...

Page 245: ... example if the first file name is Furnace1 Temp 20051012 80155F2601000120 uhh then the subdirec tory name will be 20051012 80155F2601000120 If there are more than 32 files the next subdirectory name is 20051012 80155F2601000140 assuming the file names are contiguous SD or Flash card history group 4 group 3 group 6 group 5 group 2 group 1 First 32 group 1 history files sub directory 1 sub directory n ...

Page 246: ...order can be accessed simul taneously by a maximum of 10 PCs but one PC can look at only N recorders where N depends on how much memory is available at the PC For example a minimum specification computer section 6 1 1 run ning Windows NT can look at up to three recorders simultaneously 3 A single PC connected via a telephone line to a remote recorder This manual does not describe network setup in ...

Page 247: ...um PC requirements 1 P90 running Windows NT 2000 XP Home XP Pro Server 2003 2 32MB RAM 3 50MB free hard disk space 4 Graphics drive capable of displaying 256 colours recommended 5 Sound card required for audible alarms feature section 6 5 SUPPORTED PDA CONFIGURATION PDA not supported this issue of software ...

Page 248: ...mputer suppliers etc has an associated telephone number and can also have a security password system Both the telephone number and any password s must be known to the PC user before any attempt at communication is made The PC can be set up to dial the number automatically or the number may be dialled manually Reference should be made to the computer documentation or help pages if necessary Once co...

Page 249: ...enu If the Bridge level displayed does not match the currently value if displayed operation of the Autoconfig ure key will add the option to the database If all options are correctly entered the Currently fields and the Autoconfigure key do not appear Figure 6 4 2 Options menu Trial Mode Disabled Trial Time Remaining 30 day s Fitted channels 0 Virtual channels 36 Maths 12 Totalisers 12 Counters 7 ...

Page 250: ...ed correctly This name and password are required when establishing connection with the host computer Notes 1 If the Auditor 21CFR11 option is fitted the minimum password length is that set in the Security Management menu described in section 4 4 2 For all recorders the maximum password length is 20 characters 2 For maximum security it is recommended that the remote password and the local password ...

Page 251: ...match that set in the recorder System Lo cale or the displayed time will be incorrect 4 If an attempt is made to start the program whilst another user is configuring the recorder a Fea ture Locked message appears Another client instrument has locked this feature Retrying until successful appears As soon as the other client Saves the new recorder configuration this message disappears and the progra...

Page 252: ...s each user to choose a sound including none suited to the local environment The sound runs for as long as any point alarm is active and unacknowledged Bridge software supplies a range of sounds as listed below In addition eight bit mono μLaw format AU sound files can be imported to install location Series6000 startup sounds Once a sound has been im ported create or edit the profile UHV file The n...

Page 253: ...ts of the screen The up down arrow keys allow the enabled display modes to be cycled through and the root menu Goto View menu allows a specific display mode to be chosen for the current group The Home display page can be returned to at any time by operating the Root Menu key followed by the Home key Note Any changes to the recorder s group configuration are reflected immediately at the Host PC s s...

Page 254: ... HOST Similar to the timeout message above but with the additional cause incorrect host address UNABLE TO RESOLVE HOSTNAME Caused by an incorrect host address or network failure FAILED TO AUTHENTICATE THE USER NAME Caused by incorrect user name or password MAXIMUM NUMBER OF BRIDGE SESSIONS ALREADY RUNNING ON An attempt is being made to establish more than the maximum number of Bridge sessions to t...

Page 255: ...ed such screens can be copied or moved to one or more of screens 1 to 24 thus becoming accessible at the instrument s operator interface Each enabled user screen appears as a selection key in the Goto View menu It is therefore recommended that the number of Bridge Screens is set to the number actually needed in order to reduce the number of More operations Notes 1 User screens are not supported fr...

Page 256: ...mport Screen Export Screen File Name User Screen Import See section 4 2 for descriptions of other Save Restore functions Import User Linearisation Export User Linearisation User Screen 1 screen Import Printer Driver Select Home display mode for instrument or for selected group Enabled Home Time out Home Group Scope Group Display Enable Home Page Vertical Trend Horizontal Trend Vertical Bargraph Ho...

Page 257: ... allow a more sophisticated fine tuning of the appearance of the components Note X is horizontal increasing rightwards Y is vertical increasing downwards Top left corner is 0 0 As implied in figure 7 2 3a screen component position and dimensions can be specified as percentage ab solute pixels or relative pixels Percentage is percentage of screen size Absolute pixels allow position and or dimension...

Page 258: ...ntal bargraph 0 0 50 30 20 Channel numeric 0 0 50 20 20 Channel vertical bargraph 0 0 10 40 20 Dialogue action 0 0 10 10 10 Event Button 0 0 10 10 10 Group horizontal bargraph 0 0 50 50 30 Group horizontal trend 0 0 50 50 30 Group numeric 0 0 50 50 30 Group vertical bargraph 0 0 50 50 30 Group vertical trend 0 0 50 50 30 Image 0 0 10 10 10 Line 0 0 10 10 10 Main 0 0 100 100 1 Navigation action 0 0...

Page 259: ...ages KEY DESCRIPTIONS UPPER KEYS Add Calls the Component selection list Del Deletes after confirmation the component in the Identifier field except the Main pane which cannot be deleted Copy Used to copy the current component to the pasteboard Greyed for Main as this cannot be Copied Paste Used to paste the copied component to the screen The copied item is placed 1 to the right of and 1 below the ...

Page 260: ...ccessing user pages using Bridge software Calls a browser screen allowing the user to select a path name to which to Export the current screen Goto Canvas The Component Property Editor page disappears and the screen is shown with the current component highlighted Click and Drag techniques on the highlight handles allow the component to be re sized and its aspect ratio to be edited Clicking and dra...

Page 261: ... Batch status page can be called by touching the Page Name area at the top of the screen as an alternative to the option menu Quick entry has no effect on screens other than user screens Use Last properties If selected then all the common attributes e g position size colours etc of the most recently edited object are applied to the next component to be added Positioning Grid Causes a grid to appea...

Page 262: ...dentifier field then enter the name Group 1 Ok using the pop up key board which appears 7 In Group Number select 1 Group 1 8 Title bar is selected on yes as required 9 Enter the X 25 and Y 48 co ordinates using the same technique as was used for the Identifier field in step 6 The default dimen sions 50 x 50 are as required 10 The Draw order is as required 11 Press Save Component Property Editor Sc...

Page 263: ...4 using the appropriate Y values 24 and 36 and Channel selection 3 and 4 21 Finally press Save then Close to reveal the display page ch_hor_bar_2 2 Identifier Bar 1 Last Error X Position 0 Y Position Width Height Foreground Colour Component Type 1 10 100 0 Channel Horizontal Bargraph ch_hor_bar Channel 1 Channel 1 Background Colour 1 Draw Order 20 Add Del Copy Paste Component Property Editor Scree...

Page 264: ...4187 C Channel 1 1 0000 0 0000 0 3316 C Channel 2 1 0000 0 0000 0 1427 C Channel 3 1 0000 0 0000 0 6293 C Channel 4 13 59 02 11 07 06 0 0000 0 2000 0 4000 0 6000 0 8000 1 0000 Channel 1 0 4187 C Group 1 0 8 16 24 32 40 48 1 9 17 25 33 41 49 2 10 18 26 34 42 50 3 11 19 27 35 43 51 4 12 20 28 36 44 52 5 13 21 29 37 45 53 6 14 22 30 38 46 54 7 15 23 31 39 47 55 Shift Caps BSpc Ovr Ok Cancel Colour li...

Page 265: ...screen width Background colour The fill colour of solid objects the background colour for the main page trend charts text mes sages etc For Bargraphs the colour behind the bar Button Text For operator buttons Dialogue Action and Navigation Action Allows button text to be entered Event button text is defined in Event Button Configuration described in section 4 3 7 Channel Allows a channel to be sel...

Page 266: ...igation action buttons allows a screen to be selected When the button is operated the instrument will switch to the selected display screen Show Title Bar When set to Yes group displays e g Group Vertical Trend display a title bar across the top of the component giving the selected group s descriptor Selecting Show Title Bar to No re moves the title bar from the display Start Angle For Arcs only d...

Page 267: ... digital value and alarm indication above Default Vertical Bargraph Produces a colour bar with a scale System Vertical Bargraph Produces a colour bar with a scale Horizontal Bargraph Produces a colour bar with scale with descriptor digital value and alarm indication above Best Fit Font Enabled Disabled For Channel numeric only Applies only if Custom selected as Face plate style If enabled the disp...

Page 268: ...larm two clears component reverts to Amber and so on Background quartile Background colour represents the value of the colour channel Colour 0 appears for values below 25 colour 1 for values between 25 and 50 colour 3 for values between 50 and 75 and colour 4 for values above 75 Foreground colour is default 1 Foreground quartile As background quartile but for the foreground colour Background colou...

Page 269: ...s Allows the posi tion of the faceplates to be dynamic appears at best position for the number of channels or to be located above North below South to the right East or to the left West of the bargraphs Also allows faceplates to be turned off altogether For group trend displays these faceplates are in addition to the current channel faceplate which al ways appears above the chart across the full w...

Page 270: ... the component area in the screen background colour thus rendering the component invisible PV Error Colour Background Default Allows a colour to be selected for background use when the relevant PV is in an error state Overrides other selections PV Error Colour Foreground Default Allows a colour to be selected for foreground use when the relevant PV is in an error state Overrides other selections R...

Page 271: ...tral pixel For example a padding value of 2 would produce traces 5 pixels wide Applies to all channels in the group Units Font List of fonts For Channel Numeric displays only if Faceplate Style is set to Custom then Units Font allows the Channel Units font to be selected from a picklist Update when Value changes Action is taken when the value associated with the component changes Always The compon...

Page 272: ...arison is made between the in stantaneous value of the point selected in Visible Channel and the value entered in Visible Value below For example when using the Greater than operator the component is visible whenever the Visible Channel s value is greater than the Visible Value Visible Value Default For When Visible below is selected as Channel Value Visible Val ue allows a value to be entered to ...

Page 273: ...y Bargraph For Horizontal trending only allows the vertical bargraph display to be switched on and off Display Pens Allows the pen icons at the edge of the chart to be switched on and off Horizontal Faceplate Allows the current channel faceplate to be switched on and off 7 4 2 Group vertical bargraph Produces a vertical bargraph for a selected group in a format defined by Bargraph Style and Scale ...

Page 274: ...al horizontal bargraph For a specified channel this produces a dynamic horizontal or vertical bargraph display of channel value in a format defined by Bargraph Style and Scale style described in table 7 3 2 7 4 6 Channel Numeric For a specified channel allows the channel faceplate to be displayed in one of a number of formats as de scribed in Faceplate Style in table 7 3 2 above 7 4 7 Channel data...

Page 275: ... Any signing or authorizing that normally applies to the item being edited also applies when changes are being made by means of the Operator button 7 4 11 Event Button This displays a pushbutton to be used as a source for an event The button name its action latching or unlatching and whether or not the operation of the button needs signing or authorizing are set up in Event Button configuration de...

Page 276: ... a rectangle described in section 7 4 15 but offers the user the opportunity to draw rectangles with curved corners The horizontal and vertical curve angles are specified separately and the aspect ratio of the screen should be taken into account when working in percentage units Note The rounded rectangle will draw incorrectly if either of the arc height width settings is greater than half the rect...

Page 277: ...ld be remembered that vertical percentage units are only 2 3 the size of horizontal percentage units this affecting the appearance of the drawn item Example To draw an old fashioned electronic resistor icon Units Absolute pixels X position 400 Y position 236 Foreground colour 0 X points 0 10 15 25 35 45 55 65 75 85 90 100 Y points 0 0 10 10 10 10 10 10 10 10 0 0 Press Apply then Close to produce a...

Page 278: ...ting the appearance of the drawn item Example To draw a left pointing solid arrow positioned with its point at the centre of the screen Access the component page as described in section 7 2 3 select polygon closed area and press Ok In the properties page carry out the following configuration units X position 50 Y position 50 Background colour 22 Foreground colour 30 Draw edge Yes Fill area Yes X p...

Page 279: ...eight 2 3 width if measuring in percent X position Y position Height Width X position width Y position height Figure 7 4 19a Line definitions EXAMPLE To draw an approximation to a St Andrew s cross saltire Access the component property editor page as described in section 7 2 3 Select Advanced Edit level then in the component property editor page 1 touch the Add key at the top of the screen In the ...

Page 280: ... 2 Height 2 3 width if measuring in percent 3 Arcs cannot be filled the shading in the figure is included for clarity only Figure 7 4 20a Arc dimension definitions EXAMPLE An arc definition of X position 50 Y position 50 Width 50 Height 50 Start angle 0 Arc angle 270 would produce the curve depicted in figure 7 4 20b below Figure 7 4 20b Sample arc X Y Position 1 2 Width 1 2 Height Arc Start point...

Page 281: ...ysical display screen area available for user screens is approximately 100 mm across and 72 mm high This area can be divided into a 100 x 100 array for percentage measurement or into a pixel array 320 across by 210 vertically Thus horizontally 10 mm 10 32 pixels or 1 1 mm 3 2 pixels or 10 pixels 3 2 mm and Vertically 10 mm 13 29 pixels or 1 72 mm 2 4 pixels or 10 pixels 3 4 mm Centre of screen is ...

Page 282: ...f MODBUS messaging in an intranet or internet environment using TCP IP protocols Much of the MODBUS detail in this manual is derived from the document openmbus doc available at http www modbus org default htm The above mentioned document also includes implementation guidelines for users 8 2 1 Function Codes MODBUS function codes 3 4 6 8 and 16 defined in table 8 2 1a below are supported and are fu...

Page 283: ... Strings of limited size can be transferred across Modbus TCP in ASCII format using a single non multi plexed set of consecutive registers DATA ENCODING MODBUS uses what is called a Big endian representation for addresses and data items This means that when a numerical quantity larger than a single byte is transmitted the most significant byte is sent first For example a 32 bit hex value of 123456...

Page 284: ...LL Uchar eKeys 4 Ulong ipAddress Convert ip address to an unsigned long value so that we can manipulate each of the 4 bytes to be used as our private keys ipAddress inet_addr ipAddr Now split the bytes up by copying the IP address into a byte array memcpy eKeys ipAddress sizeof Ulong From the 4 bytes of the IP address create two exclusive keys key1 eKeys 0 eKeys 3 key2 eKeys 1 eKeys 2 Calculate th...

Page 285: ...l the last byte in the array should never change for ibyte 0 ibyte dataLen 1 ibyte encryptedData ibyte encryptedData ibyte encryptedData ibyte 1 Now add all the bytes together to get a 16 bit value result for ibyte 0 ibyte dataLen ibyte byteResult encryptedData ibyte Return the encrypted string as a 16 bit value return byteResult Notes 1 If login is accepted a standard response is sent to the mast...

Page 286: ...e 2 Byte 3 Byte 4 Byte 5 10 CC Start address high Start address low No of regis ters high No of reg isters low 30 00 06 Byte 7 Byte 8 Byte 9 Byte 10 Byte 11 Byte 12 Byte 13 Byte 14 Byte 15 Byte 16 Byte 17 Byte 18 Byte 19 Byte 20 Byte count excluding CRC ASCII E Hex 45 0C ASCII n Hex 6E ASCII g Hex 67 ASCII i Hex 69 ASCII n Hex 6E Null Password High Byte ASCII e Hex 65 ASCII e Hex 65 ASCII r Hex 72...

Page 287: ...is ters high No of re ters lo CC 30 00 05 Byte 0 Transaction identifier Transaction identifier Protocol identifier Protocol identifier Byte 1 Byte 2 Byte 3 Byte 4 Number of bytes follow ing hex Byte 5 Always 00 Byte 6 Recorder Modbus address Byte 7 Modbus function code MSB set hex 00 00 00 00 00 04 01 Byte 8 Exception code 90 02 8 2 4 SECURITY Cont TO SEND A LOGIN REQUEST Cont Response Figures 8 2...

Page 288: ...oup data to read the message and it must also reset the Text Length parameter to zero This causes the recorder to look for any further messages in the queue and if there are it will load the latest message into the area accessed by Read Data and then set Text Length to the length of the new message If the host fails to set Text Length to zero after reading a message no new messages will be read If...

Page 289: ...34 2F 30 34 2F 30 32 31 36 3A 33 31 3A 30 35 20 20 20 20 20 20 20 20 6F 6E 20 6C 19 20 21 22 23 25 26 27 28 29 30 31 33 34 35 36 37 38 39 41 42 44 45 46 47 49 50 51 52 53 54 55 1 2 3 4 5 6 7 8 10 11 12 13 14 15 16 17 9 18 24 32 40 43 48 56 57 58 59 60 69 6E 65 20 33 20 73 65 63 74 69 6F 6E 20 31 37 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 0...

Page 290: ...egion 32 bit data access area F8C3 F8C2 FD08 FD07 Addresses FCBF to FD07 EtherNet IP Point run time data Point config data 32 bit run time data 32 bit config data EtherNet IP Option Addresses FC47 to FCBE Counters Addresses FB7F to FC46 Totalisers Addresses F9EF to FB7E Maths Addresses F8C3 to F9EE Input channels Addresses F48B to F8C2 Counters Addresses ED83 to F48A Totalisers Addresses DF73 to E...

Page 291: ...0 M71 M72 M73 M74 M75 M76 M77 M78 M79 M80 M81 M82 M83 M84 M85 M86 M87 M88 M89 M90 M91 M92 M93 M94 M95 M96 M97 M98 M99 M100 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 T13 T14 T15 T16 T17 T18 T19 T20 T21 T22 T23 T24 T25 T26 T27 T28 T29 T30 T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 T41 T42 T43 T44 T45 T46 T47 T48 T49 T50 C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21 C22 C23 C24...

Page 292: ...s a 16 bit value which can be transmitted accu rately 8 4 1 Instrument data Parameter name Description Type Access Start Addr Hex Dec Register Length Instrument type Instrument type number Uint16 Read only 0001 1 1 Instrument descriptor Instrument descriptor up to 20 characters String_20 Read only 0002 2 10 Reserved Not used 000C 12 10 Instrument status Uint16 Read only 0016 22 1 Bit 0 Not used va...

Page 293: ...cters String_8 Read only 0087 135 4 Spare 008B 139 4 Ch1 Close string Closed Digital Input string up to eight characters String_8 Read only 008F 143 4 Spare 0093 147 4 Ch1 Descriptor Channel descriptor up to 20 characters String_20 Read only 0097 151 10 Spare 00A1 161 10 Ch1 No of alarms Number of alarms on this channel Uint16 Read only 00AB 171 1 Ch1 PV format Enum Read only 00AC 172 1 0 Numeric ...

Page 294: ...Closed Digital Input string up to eight characters String_8 Read only 0131 305 4 Spare 0135 309 4 Ch2 Descriptor Channel descriptor up to 20 characters String_20 Read only 0139 313 10 Spare 0143 323 10 Ch2 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 014D 333 1 Ch2 PV format Enum Read only 014E 334 1 0 Numeric 1 Digital strings Spare 014F 335 60 Ch2 Alarm 1 enable Alarm 1 ...

Page 295: ...Closed Digital Input string up to eight characters String_8 Read only 01D3 467 4 Spare 01D7 471 4 Ch3 Descriptor Channel descriptor up to 20 characters String_20 Read only 01DB 475 10 Spare 01E5 485 10 Ch3 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 01EF 495 1 Ch3 PV format Enum Read only 01F0 496 1 0 Numeric 1 Digital strings Spare 01F1 497 60 Ch3 Alarm 1 enable Alarm 1 ...

Page 296: ...Closed Digital Input string up to eight characters String_8 Read only 0275 629 4 Spare 0279 633 4 Ch4 Descriptor Channel descriptor up to 20 characters String_20 Read only 027D 637 10 Spare 0287 647 10 Ch4 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 0291 657 1 Ch4 PV format Enum Read only 0292 658 1 0 Numeric 1 Digital strings Spare 0293 659 60 Ch4 Alarm 1 enable Alarm 1 ...

Page 297: ...Closed Digital Input string up to eight characters String_8 Read only 0317 791 4 Spare 031B 795 4 Ch5 Descriptor Channel descriptor up to 20 characters String_20 Read only 031F 799 10 Spare 0329 809 10 Ch5 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 0333 819 1 Ch5 PV format Enum Read only 0334 820 1 0 Numeric 1 Digital strings Spare 0335 821 60 Ch5 Alarm 1 enable Alarm 1 ...

Page 298: ...igital Input string up to eight characters String_8 Read only 03B9 953 4 Spare 03BD 957 4 Ch6 Descriptor Channel descriptor up to 20 characters String_20 Read only 03C1 961 10 Spare 03CB 971 10 Ch6 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 03D5 981 1 Ch6 PV format Enum Read only 03D6 982 1 0 Numeric 1 Digital strings Spare 03D7 983 60 Ch6 Alarm 1 enable Alarm 1 enable E...

Page 299: ... Digital Input string up to eight characters String_8 Read only 045B 1115 4 Spare 045F 1119 4 Ch7 Descriptor Channel descriptor up to 20 characters String_20 Read only 0463 1123 10 Spare 046D 1133 10 Ch7 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 0477 1143 1 Ch7 PV format Enum Read only 0478 1144 1 0 Numeric 1 Digital strings Spare 0479 1145 60 Ch7 Alarm 1 enable Alarm 1...

Page 300: ... Digital Input string up to eight characters String_8 Read only 04FD 1277 4 Spare 0501 1281 4 Ch8 Descriptor Channel descriptor up to 20 characters String_20 Read only 0505 1285 10 Spare 050F 1295 10 Ch8 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 0519 1305 1 Ch8 PV format Enum Read only 051A 1306 1 0 Numeric 1 Digital strings Spare 051B 1307 60 Ch8 Alarm 1 enable Alarm 1...

Page 301: ... Digital Input string up to eight characters String_8 Read only 059F 1439 4 Spare 05A3 1443 4 Ch9 Descriptor Channel descriptor up to 20 characters String_20 Read only 05A7 1447 10 Spare 05B1 1457 10 Ch9 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 05BB 1467 1 Ch9 PV format Enum Read only 05BC 1468 1 0 Numeric 1 Digital strings Spare 05BD 1469 60 Ch9 Alarm 1 enable Alarm 1...

Page 302: ...igital Input string up to eight characters String_8 Read only 0641 1601 4 Spare 0645 1605 4 Ch10 Descriptor Channel descriptor up to 20 characters String_20 Read only 0649 1609 10 Spare 0653 1619 10 Ch10 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 065D 1629 1 Ch10 PV format Enum Read only 065E 1630 1 0 Numeric 1 Digital strings Spare 065F 1631 60 Ch10 Alarm 1 enable Alarm...

Page 303: ...igital Input string up to eight characters String_8 Read only 06E3 1763 4 Spare 06E7 1767 4 Ch11 Descriptor Channel descriptor up to 20 characters String_20 Read only 06EB 1771 10 Spare 06F5 1781 10 Ch11 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 06FF 1791 1 Ch11 PV format Enum Read only 0700 1792 1 0 Numeric 1 Digital strings Spare 0701 1793 60 Ch11 Alarm 1 enable Alarm...

Page 304: ...igital Input string up to eight characters String_8 Read only 0785 1925 4 Spare 0789 1929 4 Ch12 Descriptor Channel descriptor up to 20 characters String_20 Read only 078D 1933 10 Spare 0797 1943 10 Ch12 No of alarms Number of alarms on this channel 0 to 2 Uint16 Read only 07A1 1953 1 Ch12 PV format Enum Read only 07A2 1954 1 0 Numeric 1 Digital strings Spare 07A3 1955 60 Ch12 Alarm 1 enable Alarm...

Page 305: ...3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 2 Parameter name Description Type Access Start Addr Hex Dec Register Length Parameter name Description Type Access Start Addr Hex Dec R...

Page 306: ...e 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 4 Ch4 value Current process value PV Scaled See note A1E2 41442 1 Ch4 status Channel stat...

Page 307: ...e 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 6 Ch6 value Current process value PV Scaled See note A1E8 41448 1 Ch6 status Channel stat...

Page 308: ...e 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 8 Ch8 value Current process value PV Scaled See note A1EE 41454 1 Ch8 status Channel stat...

Page 309: ...1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 10 Ch10 value Current process value PV Scaled See note A1F4 41460 1 Ch10 status Channel sta...

Page 310: ...e 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 12 Ch12 value Current process value PV Scaled See note A1FA 41466 1 Ch12 status Channel s...

Page 311: ... but for points 161 to 176 Uint16 Read only A4F9 42233 1 Register 12 as register 1 but for points 177 to 192 Uint16 Read only A4FA 42234 1 Register 13 as register 1 but for points 193 to 208 Uint16 Read only A4FB 42235 1 Register 14 as register 1 but for points 209 to 224 Uint16 Read only A4FC 42236 1 Register 15 as register 1 but for points 225 to 240 Uint16 Read only A4FD 42237 1 Register 16 as ...

Page 312: ... Read only A76F 42863 1 Register 13 as register 1 but for points 193 to 208 Uint16 Read only A770 42864 1 Register 14 as register 1 but for points 209 to 224 Uint16 Read only A771 42865 1 Register 15 as register 1 but for points 225 to 240 Uint16 Read only A772 42866 1 Register 16 as register 1 but for points 241 to 256 Uint16 Read only A773 42867 1 Grp2 Text length Identifies the length of a text...

Page 313: ... Read only A9E4 42492 1 Register 13 as register 1 but for points 193 to 208 Uint16 Read only A9E5 42493 1 Register 14 as register 1 but for points 209 to 224 Uint16 Read only A9E6 42494 1 Register 15 as register 1 but for points 225 to 240 Uint16 Read only A9E7 42495 1 Register 16 as register 1 but for points 241 to 256 Uint16 Read only A9E8 43496 1 Grp3 Text length Identifies the length of a text...

Page 314: ... Read only AC59 44121 1 Register 13 as register 1 but for points 193 to 208 Uint16 Read only AC5A 44122 1 Register 14 as register 1 but for points 209 to 224 Uint16 Read only AC5B 44123 1 Register 15 as register 1 but for points 225 to 240 Uint16 Read only AC5C 44124 1 Register 16 as register 1 but for points 241 to 256 Uint16 Read only AC5D 44125 1 Grp4 Text length Identifies the length of a text...

Page 315: ... Read only AECE 44750 1 Register 13 as register 1 but for points 193 to 208 Uint16 Read only AECF 44751 1 Register 14 as register 1 but for points 209 to 224 Uint16 Read only AED0 44752 1 Register 15 as register 1 but for points 225 to 240 Uint16 Read only AED1 42253 1 Register 16 as register 1 but for points 241 to 256 Uint16 Read only AED2 44754 1 Grp5 Text length Identifies the length of a text...

Page 316: ... Read only B143 45379 1 Register 13 as register 1 but for points 193 to 208 Uint16 Read only B144 45380 1 Register 14 as register 1 but for points 209 to 224 Uint16 Read only B145 45381 1 Register 15 as register 1 but for points 225 to 240 Uint16 Read only B146 45382 1 Register 16 as register 1 but for points 241 to 256 Uint16 Read only B147 45383 1 Grp6 Text length Identifies the length of a text...

Page 317: ... for further features CC81 52353 100 8 4 6 Indirection tables The standard MODBUS protocol allows block register reads and writes This is efficient only if data is grouped contiguously or nearly so Indirection tables are a means by which widely spaced register addresses can in effect be grouped offering the host the ability to access a block of user defined data in one single read write request Tw...

Page 318: ...ata area CCE5 CCE6 CEE6 CEE5 D0E5 D0E6 D0E7 D2E7 D2E6 D4E6 No of R W entries No of Read Only entries Read only area Read Write area 8 4 6 INDIRECTION TABLES CONT Table 8 4 6a shows the overall arrangement of the indirection table area Figures 8 4 6b and 8 4 6c show simple examples of Read only and Read Write addressing for tables with 6 entries Table 8 4 6a Indirection table areas ...

Page 319: ...d data addresses here Read values from here address hex 200 32 bit IEEE channel D0E6 0006 D0E7 D0E8 D0E9 D0EA D0EB 00EB 018D 022F 02D1 0373 0415 Chan 1 Alarm 1 setpoint Chan 2 Alarm 1 setpoint Chan 3 Alarm 1 setpoint Chan 4 Alarm 1 setpoint Chan 5 Alarm 1 setpoint Chan 6 Alarm 1 setpoint D0EC Number of Read Write entries D2E7 Ch1 Alarm1 Sp Ch2 Alarm1 Sp D2E8 Ch3 Alarm1 Sp D2E9 Ch4 Alarm1 Sp D2EA C...

Page 320: ... setpoint Trigger setpoint Note 2 for alarm 2 Note 2 Float Read Write D4F1 54513 2 Ch1 Alarm 3 setpoint Trigger setpoint Note 2 for alarm 3 Note 2 Float Read Write D4F3 54515 2 Ch1 Alarm 4 setpoint Trigger setpoint Note 2 for alarm 4 Note 2 Float Read Write D4F5 54517 2 Spare D4F7 54519 20 CHANNEL 2 Ch2 span high Upper span value display full scale Float Read only D50B 54539 2 Ch2 span low Lower s...

Page 321: ...rm 4 Note 2 Float Read Write D561 54625 2 Spare D563 54627 20 CHANNEL 5 Ch5 span high Upper span value display full scale Float Read only D577 54647 2 Ch5 span low Lower span value display zero Float Read only D569 54649 2 Ch5 Zone high Zone upper value of chart width Float Read only D57B 54651 2 Ch5 Zone low Zone lower value of chart width Float Read only D57D 54653 2 Ch5 Alarm 1 setpoint Trigger...

Page 322: ... Ch8 Zone high Zone upper value of chart width Float Read only D5E7 54759 2 Ch8 Zone low Zone lower value of chart width Float Read only D5E9 54761 2 Ch8 Alarm 1 setpoint Trigger setpoint for alarm 1 Note 2 Float Read Write D5EB 54763 2 Ch8 Alarm 2 setpoint Trigger setpoint for alarm 2 Note 2 Float Read Write D5ED 54765 2 Ch8 Alarm 3 setpoint Trigger setpoint for alarm 3 Note 2 Float Read Write D5...

Page 323: ...h11 Zone high Zone upper value of chart width Float Read only D653 54867 2 Ch11 Zone low Zone lower value of chart width Float Read only D655 54869 2 Ch11 Alarm 1 setpoint Trigger setpoint for alarm 1 Note 2 Float Read Write D657 54871 2 Ch11 Alarm 2 setpoint Trigger setpoint for alarm 2 Note 2 Float Read Write D659 54873 2 Ch11 Alarm 3 setpoint Trigger setpoint for alarm 3 Note 2 Float Read Write...

Page 324: ...ss is Read only 8 4 8 IEEE Area Channel run time data The following tables show the hexadecimal addresses for the specified 32 bit floating point values for channels 1 to 12 Generally Parameter address for channel N Parameter address for channel 1 4 N 1 decimal CHANNEL 1 Parameter name Description Type Access Start Addr Hex Dec Register Length Parameter name Description Type Access Start Addr Hex ...

Page 325: ...active 1 Alarm 3 active Read only Bit 9 0 No alarm 3 Ack required 1 Ack required Read only Bit 10 1 Acknowledge alarm 3 Read Write Bit 11 Spare Bit 12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 4 Channel 4 value Current process value PV Float See note F8CF 63695 2 Channel 4 sta...

Page 326: ...12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 6 Channel 6 value Current process value PV Float See note F8D7 63703 2 Channel 6 status Channel status Enum Read only F8D9 63705 1 0 Good PV 5 Ranging error 1 Channel off 6 Overflow 2 Over range 7 Bad PV 3 Under range 8 No data 4 Ha...

Page 327: ...12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare Channel 7 value Current process value PV Float See note F8DB 63707 2 Channel 7 status Channel status Enum Read only F8DD 63709 1 0 Good PV 5 Ranging error 1 Channel off 6 Overflow 2 Over range 7 Bad PV 3 Under range 8 No data 4 Hardware err...

Page 328: ... 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 10 Channel 10 value Current process value PV Float See note F8E7 63719 2 Channel 10 status Channel status Enum Read only F8E9 63721 1 0 Good PV 5 Ranging error 1 Channel off 6 Overflow 2 Over range 7 Bad PV 3 Under range 8 No data 4 H...

Page 329: ...12 0 Alarm 4 inactive 1 Alarm 4 active Read only Bit 13 0 No Alarm 4 Ack required 1 Ack required Read only Bit 14 1 Acknowledge alarm 4 Read Write Bit 15 Spare CHANNEL 12 Channel 12 value Current process value PV Float See note F8EF 63727 2 Channel 12 status Channel status Enum Read only F8F1 63729 1 0 Good PV 5 Ranging error 1 Channel off 6 Overflow 2 Over range 7 Bad PV 3 Under range 8 No data 4...

Page 330: ...in hex followed by the relevant data bytes the number and content of which depend on the function code as described in subsequent sections Figure 8 5 MODBUS package Notes 1 The transaction identifier has no active function the recorder just copies the bytes from the re quest message to the response message 2 The protocol identifier bytes are always zero FUNCTION CODES AND EXCEPTION CODES Refer to ...

Page 331: ...ex ASCII c Hex ASCII r Hex 69 70 74 6F 72 ASCII i Hex ASCII p Hex ASCII t Hex ASCII o Hex ASCII r Hex 8 5 1 Function code 03 REQUEST The bytes after the 7 byte prefix described above are Function code 03 1 byte Register start address 2 bytes Word count Total number of registers 1 to 125 decimal 1 to 7D hex 2 bytes Thus to read Channel 5 descriptor start address 031F 10 registers altogether the fol...

Page 332: ... Function code 06 REQUEST This is used to write a value to a single register The bytes after the 7 byte prefix described in section 8 5 above are Function code 06 1 byte Register address 2 bytes Value to be written 2 bytes Thus to write a value of 80 degrees as Alarm 1 setpoint for channel 3 register address 022F the following request as detailed in figure 8 5 3 would be transmitted to the recorde...

Page 333: ...yte 7F 00 07 Word count High byte Word count Low byte 8 5 5 Function code 16 Hex 10 REQUEST This is used to write values to multiple registers The bytes after the 7 byte prefix described in section 8 5 above are Function code 10 1 byte Register Start address 2 bytes Word count Total number of registers to be written 1 to 100 decimal 1 to 64 hex 2 bytes Byte count B 2 x word count 1 byte Values to ...

Page 334: ... 9 2 1 Serial communications ports The printer is connected to one of the Serial communications ports configured for EIA232 standard using the Rx Tx and common signal lines Printer Tx must be connected to recorder Rx Printer Rx must be connected to recorder Tx Figure 9 2 1 shows the location of and user connections for the recorder ports See also sec tion 2 2 Serial Port 1 Serial Port 2 EIA232C Pi...

Page 335: ...pply Discard Port Online Protocol EIA232 9600 1 Even Star TSP600 0 Star TSP600 0 Not Responding 1 Group 1 Serial 1 ASCII Printer Figure 9 3 1a Serial communications configuration menu PORT This allows serial port 1 or serial port 2 to be selected for printer configuration Separate independently configurable printers can be connected to the two ports or if only one printer is to be connected any of...

Page 336: ...TEST Operating this button causes a test printout to appear at the printer as shown in figure 9 3 1b PRINT MESSAGES FROM The user can select a group for message printing These messages are printed as they occur and are not dependent on job action Only those messages in the enabled categories see Messages to Print below are printed MESSAGES TO PRINT This set of enable boxes allows the user to selec...

Page 337: ...uration REPORT Allows the user to select the required report number for configuration DESCRIPTOR A name for the Report can be entered here NUMBER OF FIELDS Select 0 to 10 for the number of items to be included in the report FIELD N TYPE N 1 to the number of fields selected in the previous item Date Time Causes the time and date of report generation to be included in the report Text Allows the user...

Page 338: ...put Filtering An enhancement has been added to the ASCII input feature in instruments with software versions 5 4 up wards This feature provides a number of text filters each with their own timeouts to be applied to the ASCII input so that only specific text strings are recognised The feature has been designed for use in particular with GPS systems to allow only relevant data to be logged TEXT FILT...

Page 339: ...l respond to incoming messages which contain the characters GPGLL as set in Filter 1 and GPZDA as set in Filter 2 Filter 3 is not being used as it is a blank string Note The supported characters for filter strings are ASCII 0x20 to 0x7F exluding the and characters When used with an unprogrammable receiver which is generating GPS messages typically every second the Timeout parameter will typically ...

Page 340: ...ecord required messages every 10 min utes Timeout can be set to different rates for each filter in which case the data will be recorded at the rates set for each filter When the instrument reboots the filter timeouts will reset so the first message received will be recorded in a new history file the timeouts will then come into effect Filter timeouts will also be reset when the instrument is recon...

Page 341: ...r a recorder When using a PC as the operator interface the detailed appearance of the Host PC browse window depends on the Windows version in use File Name Import Printer_Driver uhi Save Restore New Text Archive System Save Restore Config Security Network Import Screen Export Screen Import User Linearisation Export User Linearisation Import Printer Driver Save Cancel FileName Printer_Driver uhi Hi...

Page 342: ...ured are in their factory default state Con figuration items not mentioned in the example e g Scale Low should be left at their default values 9 5 1 Group Configuration Refer to section 4 3 2 as necessary GROUP NUMBER 1 Descriptor Colour mix Alarm message Disable Deselect all points except Channels 1 to 4 9 5 2 Channel configuration Refer to section 4 3 3 as necessary CHANNEL 1 Input Type Test Sca...

Page 343: ...required printer Report 1 report 1 On Active 9 5 4 Report Configuration Descriptor Paint Low Number of fields 8 Field 1 Type Text Text Paint Low Warning Style Banner Field 2 Type Line Feed Line Feed 2 Field 3 Type Date Time Style Normal Field 4 Type Process Value Point Red Style Normal Field 5 Type Process Value Point Blue Style Normal Field 6 Type Process Value Point Green Style Normal Field 7 Ty...

Page 344: ...he example above the event trigger is Unacknowledged alarm This means that once the first channel alarm becomes active and the relevant report printed then no further reports will be initiated until the alarm is acknowledged no matter how many other channel alarms go active If however an unlatched alarm becomes inactive this is the equivalent of its being acknowledged as far as report printing is ...

Page 345: ...d as shown in figure 9 6b See SW1 SW2 details in the TSP600 User s guide for details DSW1 DSW2 DSW1 DSW2 Figure 9 6a DIP switch access Figure 9 6b DIP switch element configuration DSW3 Figure 9 6c SW3 location Figure 9 6d SW3 settings The illustrated switch settings segments 4 5 and 6 Off all other segments On give the following parameter values Baud Rate 9600 Data bits 8 Parity Even Handshake Xon...

Page 346: ...ct has been designed to conform to BS EN61010 installation category II and pollution degree 2 These are defined as follows Installation category II The rated impulse voltage for equipment on nominal 230V ac mains is 2500V Pollution degree 2 Normally only non conductive pollution occurs Occasionally however a temporary conductivity caused by condensation shall be expected ...

Page 347: ...screens Security Manager Simulation History Maintenance Environmental Performance Temperature limits Operation 0 to 50 C Storage 20 to 60 C Humidity limits Operation 5 to 80 RH non condensing Storage 5 to 90 RH non condensing Altitude maximum 2000 metres Protection Bbezel display IP65 for a recorder mounted in a panel Sleeve IP20 Shock BS EN61010 Vibration 10 Hz to 150Hz 1g peak Physical Panel mou...

Page 348: ...ppm per year Touch screen Colour TFT LCD with cold cathode backlighting fitted with resistive analogue touch panel Screen specification Small frame 1 4 VGA Resolution 320 x 240 pixels Large frame XGA Resolution 1024 x 768 pixels Update information Input sample rate 8 Hz Display update 8 Hz Archive sample value Latest value at archive time Trended displayed value Latest value at display update time E...

Page 349: ... tested to domestic information technology standards BS EN55022 with category C performance Some USB peripherals designed for use in domestic or office environments can be susceptible to lock up in environments containing high electromagnetic field strengths In order to recover from such lock up situations the peripheral must be disconnected and then recon nected Recorder operation is not affected O...

Page 350: ...ERENCE B1 DIAGNOSTICS DISPLAY B1 1 MAIN DIAGNOSTIC DISPLAY At power up continuously hold a finger in contact with the screen until the main diagnostic display ap pears as shown in figure B1 1 Special Modes Display Test Touch Calibration System Summary Diag Summary Quit Figure B1 1b Top level diagnostic display ...

Page 351: ...n sales demo mode B1 3 DISPLAY TEST Selecting this option allows the user to check the display by flooding the screen with single colours Repeatedly touching the screen scrolls through the following colour sequence Black White Red Green Blue Cyan Magenta Yellow A further operation of the touch screen returns the main diagnostic screen B1 4 TOUCH CALIBRATION Touching this key calls a selection scree...

Page 352: ... the display and keep touching it until the next target appears 3 Continue the process according to the directions appearing on the screen Once all the targets have been accepted the recorder returns to the diagnostic display Figure B1 4 1 Initial calibration display B1 4 2 Touch screen verify This allows the user to check the accuracy of the touch screen without having to carry out the calibratio...

Page 353: ...in Menu None None None BATTERY LOCKAB 00 00 00 Serial 2 N N Serial 1 MAC address Option boards Input boards Software version None Figure B1 6 Diag Summary small frame recorder large frame similar B1 6 1 MAC Address Each instrument is allocated a unique hex address as a part of the manufacturing process The display at the top left of the display screen shows the final 6 characters of this address Th...

Page 354: ...he relevant serial port The test will result in the legend S1 2 Passed or S1 2 Failed replacing Serial 1 or Serial 2 on the ap propriate key B1 6 4 Battery This area normally green flashes red white when the battery needs to be replaced section B2 Battery status is checked once every 15 minutes B1 6 5 Lockable Not applicable to this recorder model B1 6 6 Option boards Always shows None B1 6 7 Input...

Page 355: ...stylus sup plied only The use of sharp or pointed implements such as pens keys and fingernails to oper ate the instrument must be avoided or irreparable damage will be done to the surface mate rial When cleaning the touch screen a moist cloth should be used if necessary with a minimal amount of mild soap solution ALCOHOLS SUCH AS ISOPROPYL ALCOHOL MUST NEVER BE USED ON THE SCREEN B2 2 MAINTENANCE S...

Page 356: ...m construction and should be disposed of according to local regulations covering this type of battery 1 Remove the screw securing the access cover to the rear of the instrument and carefully remove the cover 2 The battery can now be replaced Access cover BR2330 Cover retaining screw location Battery Figure B2 2 1a Access cover location large frame unit Figure B2 2 1b Battery location small frame u...

Page 357: ...ECTION The following table gives RGB values and decimal and hex numbers for the available channel colours Normally this table is necessary only when communicating over the Modbus link Note Colour representation varies from screen to screen For this reason it is unlikely that the colour on a PC will match those on these pages or those on the recorder display ...

Page 358: ...lue 0 0 102 6 06 Jade 0 95 0 7 07 Magenta 255 0 102 8 08 Dusky Rose 255 95 51 9 09 Yellow 255 255 255 10 0A Powder Blue 85 63 255 11 0B Dark Red 170 0 0 12 0C Avocado 0 233 102 13 0D Indigo 85 0 102 14 0E Dark Brown 85 63 0 15 0F Ægean 0 63 51 16 10 Cyan 0 255 255 17 11 Aubergine 85 0 51 18 12 Dark Orange 255 63 0 19 13 Pale Yellow 255 255 51 20 14 Hyacinth 170 0 51 21 15 Dark Green 0 63 0 22 16 S...

Page 359: ... 51 34 22 Sea Blue 85 159 255 35 23 Ginger 255 159 0 36 24 Aqua Pool 0 63 255 37 25 Pale Red 255 63 51 38 26 Pale Blue 85 127 255 39 27 Lilac 170 0 255 40 28 Sky Blue 85 191 255 41 29 Wild Moss 0 127 0 42 2A Turquoise 0 127 153 43 2B Pale Green 85 255 153 44 2C Coffee 170 127 0 45 2D Wicker 255 255 191 46 2E Black 0 0 0 47 2F Dark Dark Grey 48 48 48 48 30 Dark Grey 64 64 64 49 31 Grey 128 128 128 ...

Page 360: ...one involved in setting up firewalls which may be used selectively to block incoming or outgoing access to specific ports PORT Usage 20 File Transfer Protocol data 21 File Transfer Protocol control 25 E mail SMTP 80 Web access 123 SNTP server 502 Modbus TCPIP communications 1264 Bridge communications general 2222 EtherNet IP communications 44818 EtherNet IP communications 50010 Bridge communications...

Page 361: ...S 28 1C GS 29 1D RS 30 1E US 31 1F Space 32 20 33 21 34 22 35 23 36 24 37 25 38 26 39 27 40 28 41 29 42 2A 43 2B 44 2C 45 2D 46 2E 47 2F 0 48 30 1 49 31 2 50 32 3 51 33 4 52 34 5 53 35 6 54 36 7 55 37 8 56 38 9 57 39 58 3A 59 3B 60 3C 61 3D 62 3E 63 3F 64 40 A 65 41 B 66 42 C 67 43 D 68 44 E 69 45 F 70 46 G 71 47 H 72 48 I 73 49 J 74 4A K 75 4B L 76 4C M 77 4D N 78 4E O 79 4F P 80 50 Q 81 51 R 82 ...

Page 362: ...Lahore time 17 00 5 IST India standard time 17 30 5 5 BST Bangladesh standard time 18 00 6 VST Vietnam standard time 19 00 7 CTT China Taiwan time 20 00 8 JST Japan standard time 21 00 9 ACT Australia Central time 21 30 9 5 AET Australia Eastern time 22 00 10 SST Solomon standard time 23 00 11 NST New Zealand standard time 24 00 12 MIT Midway Islands time 01 00 11 HST Hawaii standard time 02 00 10...

Page 363: ...ion 4 3 22 1 Recorders fitted with this option come complete with a file called HMT TXT in the user area of the filing system accessed as described in section 5 2 Highlight this file and copy it using the Filer Options menu Copy key 3 With a memory device e g Memory stick inserted use the Filer Options menu Paste key to save the file into the removable media area 4 Move the storage device from the reco...

Page 364: ...as 1 11 07 06 08 50 28 Batch Field 3 Operator s name was Batch field 3 11 07 06 08 50 28 Batch Field 2 Customer was Batch field 2 11 07 06 08 50 28 Batch Field 1 Batch number was Batch field 1 11 07 06 08 50 28 Batch Batch fields 3 was 1 11 07 06 08 50 50 Config Signed Engineer Authorized Engineer New batch fields 10 07 06 16 42 11 Alarm s off 2 1 10 07 06 16 32 50 Alarm s off 1 1 10 07 06 16 31 0...

Page 365: ... Last 7 Days Archive Last 31 Days Archive All Suspend Archiving Cancel Archive Bring Archive Up To Date 23 08 05 11 32 18 Media mediacard Select Media card or USB port System ork Local e Figure B9l m Bytes Bytes Archive Transfer Media Size Free Space Inactive 31954944 28786688 Media Full 08 09 2006 00 34 57 ...

Page 366: ...en Export screen File Name Network Data Screens Data Security Data Configuration Data Restore File Name Save Save as File Name 1 UserL User linearisation userlin Import User Linearisation Export User Linearisation 6100 Save Restore section 4 2 rchive System Save Restore Config Security Network Save Restore New Text Import Screen Export Screen Import User Linearisation Export User Linearsation Appe...

Page 367: ...p Scope Group Display Enable Home Page Vertical Trend Horizontal Trend Vertical Bargraph Horizontal Bargraph Numeric Page User Screen 1 User Screen 2 User Screen 3 User Screen 4 1 Group 1 Apply Discard 0 Group 1 Group 1 Circular Trend Channels Section 4 3 3 Job Number 1 Category No Action Value 50 002 Input Type Slave Comms Scale Low 0 Scale High 100 Units Offset 0 Descriptor Channel 1 Spanned A S...

Page 368: ...value of 1 2 3 4 5 Source Descriptor Source Value Totaliser 1 Specified Descriptor Totaliser 1 Specified Value Config Revision Blank Apply Discard Replace 7 with Button Number Descriptor Type Text Latched Text Require Signing Require Authorisation Apply Discard 1 Button 1 Button 1 Latched Off Text On Text Event Buttons Section 4 3 7 r Linearisation Descriptor Format mber of Points X1 Y1 X2 Apply D...

Page 369: ...ale Type Zone low Zone high Max Decimal Digit Colou Alarm Numbe Enabl Job Numbe Category Maths Numbe Valu PV Forma Temperature interva Unit Scale high A B Switching Maths Section 4 3 11 Totalisers Section 4 3 12 Apply Discard Counter number Enable Select Alarm number Alarm Number Enable Job Number Category Select Off Unlatched Latched Trigger Select Job number Select Job category Value Units Prese...

Page 370: ...ASCII input Section 4 3 15 Protocol ASCII input Apply Discard Baud Rate Stop Bits Parity Select required Baud rate Select 1 or 2 Select None Odd or Even Protocol Link Error Count Reset Error Count Connection Port Select port 19200 1 None Modbus Slave 0 EIA4XX Serial 1 Modbus Slave Section 4 3 15 Port Serial 1 Select port Connection EIA4XX Instrument Groups Channels Views Archive Events Event Butto...

Page 371: ...Type Slave Parameter Scaling Scale Low Scale High Point Type Point Number Process Value Descriptor Source Default On Error Write Default Detect All Slaves Discard Apply Scaling item for some sla Output channels Section 4 3 17 Enable Demand Type Status Apply Discard Write number Demand Write Slave Parameter Point Type Point Number Descriptor Source Default ow Constant Edits Disable Retries end On P...

Page 372: ...Line Feed 1 1 Report 1 Date Time Normal Text Report 1 6 Banner Archive System Save Restore Config Security Network Figure B9b Figure B9c Fig B9j Figure B9k Figure B9l m Figure B9e Figure B9f Figure B9h Figure B9g Figure B9d Import Table Export Table Status I O Table Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 200 eiptable eiptable Online Inputs Server Client Channel 1 pv Channel 2 pv Cha...

Page 373: ...it Output Channel Default Action Demand Writes Force Change of Password Perform Upgrades Enter Batch Data Allow web server Operator Apply Discard Add Name ser ID Name sword sword ed On Add user section 4 4 3 Access section 4 4 1 ser User Full Name Apply Discard Remove Record Logins th unapplied changes mum Password Length Enable Audit Trail Require Authorization Apply Discard Login Timeout Passwor...

Page 374: ...DNS S Secondary DNS S Loca D Name Address Name Figure B9b Archive System Save Restore Config Security Network Figures B9d to B9i Figure B9j Network Section 4 5 Figure B9l m Figure B9c Name appears only when IP address lookup is set to Get from BootP server or to Get from DHCP Server ...

Page 375: ...stics Initiate Comms Test Actual High Priority Modbus Address Slave Status Seconds Actual Medium Priority Actual Low Priority Seconds Seconds 2 1 Master Rejects 0 0 125 Slave Failures 04 1 1 Successful Comms Tests Online 0 Last Transaction Status OK Serial Link Error Count 4 Total Requests Retried requests 1308 10 Bad requests Timed out requests 10 0 Good requests Gateway Target Fail 11 1298 0 Ill...

Page 376: ...Font set Auto Default Apply Discard System Section 4 6 In Figure B9b Archive System Save Restore Config Security Network Figure B9c Figures B9d to B9i Figure B9j Figure B9k Figure B9l Job C Job Clock Locale Upgrade Input Adjust Output adjust Master Comms Diagnostics Ethernet Diagnostics Copy Job Search Customise About Copy section 4 6 8 Customise section 4 6 10 Job Search section 4 6 9 About secti...

Page 377: ...100 180 MM DISTRIBUTED GRAPHIC RECORDER USER GUIDE This page is de ...

Page 378: ...ads Document Library Search take the user to vari ous areas of the manufacturer s web site C3 ACCESS TABS Most of the information displayed in the pages described below is updated every 20 seconds The ex ception is the Trend page refresh rate which can be edited as shown in figure C3 2 by typing in the new value and then either clicking on Set or using the computer Enter key Because of the processi...

Page 379: ...trend Figure C3 2 1 shows a horizontal trend display for an imaginary group Furnace Temps 1 with two chan nels Stack 1 and Stack2North Figure C3 2 1 Horizontal trend example As shown in the figure the group process values appear as though being traced on a chart which is roll ing from right to left i e the oldest sample is at the left edge of the chart and the latest sample is at the right edge of ...

Page 380: ...larm messages for a group called Fur nace Temps 1 Show me the last minutes of data 20 Set Instrument History Home Trends Message Logs Group 1 2 3 4 5 6 7 8 9 10 11 12 Furnace Temps 1 All Messages 19 04 06 11 21 26 CO2 OK 19 04 06 11 21 26 SO2 OK 19 04 06 11 21 26 CO OK 19 04 06 11 21 26 Alarm s off1 1 19 04 06 11 21 26 Alarm s off2 1 19 04 06 11 11 13 CO2 over limit 19 04 06 11 11 13 SO2 over limi...

Page 381: ...st having been unzipped Size Last Modified 391 Kb 01 05 06 16 20 10 391 Kb 01 05 06 20 20 10 Home Instrument About File Name Group 1 20060501 00204B26000001C4 uhh Group 1 20060501 00204B26000001C5 uhh Click here to select all files for sav ing to a user specified location Click on individual files to save to a user specified location C3 4 History file display C3 5 ABOUT Clicking on this tab display...

Page 382: ... 248 Bargraph Channel 257 Displays Horizontal 40 Vertical 38 Group Horizontal 256 Vertical 256 Style 250 Based on 196 Symbols 3D effect 250 10 to the power maths function 100 in message 86 87 n source 87 Out of Range 175 Syntax Error 175 uhh files 352 uhq file 216 uht files 176 A About 215 347 Absolute high low 70 A B Switching 61 69 Access Configuration menu 344 Levels 186 To configuration 26 when 187...

Page 383: ...nning the program 234 Software installation 232 Start as Lite 234 Brightness control 57 Bring archive up to date 47 BSpc 27 Button Text 248 C Calibration coefficients 320 Can Authorize 189 Can Sign 189 Caps 27 Centralised security 194 Change Alarm setpoint permission 188 Battery Indicator 11 Procedure 327 Constant value 188 Password 197 Time R of C alarms 71 Change Password 185 Channel Alarm indica...

Page 384: ...to 343 Messages 86 Network 201 Offset 66 Options 183 Output channels 162 Reports 171 Scale 66 Security 185 Serial Communications 140 Span 69 Summertime 207 Time and date 207 Timers 137 Time zone 207 Totaliser 128 Trace Colour 69 User linearisation tables 89 Views 74 Zone Chart 69 Time 207 Connected messaging 173 Connect from Remote 187 Connections 139 Contents of group 64 Continuous batch selectio...

Page 385: ... 224 All Alarms job 224 Counter 219 Login 188 Maths channel 218 Retries 164 Timer 220 Totaliser 217 Warning Dialogs 58 Discard Ethernet IP Table 174 Discard key 243 Disk Icon 11 Size 79 Display Alarms 251 Bargraph 252 Batch Dialogue 97 Brightness 57 Calibration 322 Colour Configuration menu 347 Descriptor 252 Messages 252 Mode 27 Enable disable 75 Home selection 74 Horizontal Bars 40 Horizontal Tre...

Page 386: ... Failed to authenticate user name 237 Feature 248 Changed 229 Identification table 300 Locked 229 Field 1 to 6 Batch 93 Field 1 Type 171 File 226 Formats archiving 80 81 Key 22 Name character limitation 50 Structure 228 Transfer FTP facility 48 Filer Option menu 226 Fill Area 248 First Start End Char 141 First switch on 25 Flash size 78 Folder keys 22 Font Size 214 Style 252 Force change of passwor...

Page 387: ...User linearisation 51 Include message 168 Increment counter job 219 Indirection tables Modbus 300 Input Configuration 66 Type selection 66 Input 1 to 200 174 Inrush current 5 Installation Category 317 Electrical 5 Mechanical 2 Inst cal corr n 124 Inst calibration points 124 Inst cal temp n 124 Instrument Alarm Definition 10 Event source 83 Indicator 10 Summary 13 Configuration 57 Configuration menu 33...

Page 388: ...91 Configuration menu 344 Manual archive Local 46 To host computer 48 Mass flow Linear 100 104 Saturated Steam 110 Square root 100 106 Master Comms 143 Configuration menu 342 Diagnostics 160 Example configuration 157 Slave Failure Event source 83 Master Slave Connection 6 Selection 6 Maths channel Configuration 98 Menu 340 Modbus data 125 32 bit IEEE 126 Copy 211 Failure 10 Function selection 99 Jobs 2...

Page 389: ...nfiguration menu 345 Boot failure 10 Configuration 201 Connection has timed out 237 Ethernet Serial selection 145 Key menu 345 Name 204 Scanning tool 203 Specification 319 New Chart 34 61 Configuration 50 Domain name 196 Full User Name 196 Key 226 Password 187 196 User ID 196 User Screen key 243 No action 217 No chart grid 62 Nominal height width 253 NONE 84 NOR 84 Normal View 35 Notes 253 No Text 254...

Page 390: ... 25 Preset Clock Job 219 Counter 133 219 Group 219 Permission 188 Totaliser 128 Job 217 Permission 188 Pressure unit conversion 111 Preventive maintenance 326 Primary DNS Server 204 Login Name 80 Remote Host 80 Printed keys 22 Process value 171 Update rate 150 152 Process Value 176 Profile Modbus slave 145 Properties page User screens 242 Protocol 141 168 PV Error Colour 253 Format 69 102 Q Questio...

Page 391: ...ype 66 Scaled tick box 66 Scaling 150 154 166 Scientific display 69 Scope 92 Display modes 74 Screen Builder option 238 See also User screens Calibration 322 Importing Exporting 51 Number 249 Saver 57 184 Size 264 Secondary DNS Server 204 Login 80 Password 80 Remote Host 80 Second Start End Char 141 Security Configuration 185 Key menu 344 Levels 186 Modbus 266 Revision 25 91 194 216 Select Display m...

Page 392: ...setup 207 Supply voltage Requirements 5 Wiring 5 Support file 216 Suspend Archiving 47 Switch 100 Symbols used on labels 1 Synchronisation by SNTP 202 Syntax Error 175 System Key 205 Menu 346 Summary 324 T Tag Channel 69 T C cal corr n 124 T C cal temp n 124 Termination and biassing 139 Text 168 171 249 Messages Modbus 271 Save and Restore 50 Size 214 347 String entry 27 User screens 259 There appe...

Page 393: ...n menu 346 Permission 189 USB Connector 7 Lock up 320 Over current 11 Port specification 320 Unsupported 11 Use Counter batch number 93 Last properties 244 Text batch number 93 User Adding and removing 196 Defined 153 Defined descriptor 122 Linearisation table Configuration 89 Configuration menu 339 Importing Exporting 51 Units selection 66 89 Logged in Event Source 83 Login account disabled 83 Name Em...

Page 394: ...s 265 Serial comms 6 Supply voltage 5 With unapplied changes 192 Wizard Ethernet IP Ethernet IP 174 Write Enable 164 To register 165 X XOR 84 X points 249 X position 249 Y You are already running message 229 237 You are authenticating Full Bridge message 237 Y points 249 Y position 249 Z Z Factor 105 106 Zirconia probe 101 118 Zone B select job 222 Chart area 69 Time List of 333 Selection 207 ...

Page 395: ...100 180 MM DISTRIBUTED GRAPHIC RECORDER USER GUIDE User Guide Page 379 HA029324 Issue 11 Oct 14 This page is deliberately left blank ...

Page 396: ......

Page 397: ... aid in operating the equipment to which the document relates without the prior written permission of Invensys Eurotherm Limited Eurotherm Limited pursues a policy of continuous development and product improvement The specifications in this document may therefore be changed without notice The information in this document is given in good faith but is intended for guidance only Eurotherm Limited wil...

Reviews: