100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
Page 135
HA029324
Issue 11 Oct 14
4.3.13 COUNTERS (Cont.)
RUN-TIME DATA
This table shows addresses for counter 1. Generally: Counter N address = counter 1 a 3(N-1)
(decimal)
COUNTER 1
Note: If an alarm’s Setpoint Source (
section 4.3.3)
is set to anything other than ‘Constant’ the value
returned will be the previously confi gured constant value.
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
Value
Current process value (PV)
Scaled
Read/Write A47C (42108)
1
Status
Channel status
Enum
Read only
A47D (42109)
1
0 = Good PV
5 = Ranging error
1 = Channel off
6 = Overfl ow
2 = Over range
7 = Bad PV
3 = Under range
8 = No data
4 = Hardware error
Alarms
Alarm information
Uint16
-
A47E (42110)
1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active
Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required
Read only
Bit 2: 1 = Acknowledge alarm 1
Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active
Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required
Read only
Bit 6: 1 = Acknowledge alarm 2
Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active
Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required
Read only
Bit 10: 1 = Acknowledge alarm 3
Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active
Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required
Read only
Bit 14: 1 = Acknowledge alarm 4
Read/Write
Bit 15: Spare
IEEE 32-BIT CONFIGURATION DATA
The following table gives addresses for the specifi ed 32-bit fl oating-point values, for Counter 1. Gener-
ally, Parameter address for counter N = Parameter address for counter 1 + 36(N-1) (decimal).
COUNTER 1
Span high
Upper span value (Display full scale)
Float
Read only
F48B (62603)
2
Span low
Lower span value (display ‘zero’)
Float
Read only
F48D (62605)
2
Zone high
Zone upper value (% of ‘chart’ width)
Float
Read only
F48F (62607)
2
Zone low
Zone lower value (% of ‘chart’ width)
Float
Read only
F491 (62609)
2
Alarm 1 setpoint
Trigger setpoint for alarm 1 (see note)
Float
Read/Write F493 (62611)
2
Alarm 2 setpoint
Trigger setpoint for alarm 2 (see note)
Float
Read/Write F495 (62613)
2
Alarm 3 setpoint
Trigger setpoint for alarm 3 (see note)
Float
Read/Write F497 (62615)
2
Alarm 4 setpoint
Trigger setpoint for alarm 4 (see note)
Float
Read/Write F499 (62617)
2
Spare
F49B
(62619)
20
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length