100/180MM DISTRIBUTED GRAPHIC RECORDER: USER GUIDE
HA029324
Issue 11 Oct 14
User Guide
Page 296
8.4.4 GROUP DATA (Cont.)
GROUP 2
Grp2 Trend type
Trend enhancements
Enum
Read only
A74B (42827)
1
0 = Interpolation enabled
1 = Adaptive recording enabled
Grp2 Trend rate
Trend update rate in milliseconds
Uint32
Read only
A74C (42828)
2
Grp2 Archive rate
Archive (to
fl
ash) rate in milliseconds
Uint 32
Read only
A74E (42830)
2
Grp2 Descriptor
Group descriptor (20 characters max.)
String_20
Read only
A750 (42832)
10
Spare
A75A
(42842)
10
Grp2 Channels in group 16 Registers holding the group contents, as follows:
(16)
Register 1
Uint16
Read only
A764 (42852)
1
Bit 0: 0 = Point 1 not in group; 1 = Point 1 is in group
Bit 1: 0 = Point 2 not in group; 1 = Point 2 is in group
Bit 2: 0 = Point 3 not in group; 1 = Point 3 is in group
Etc.
Bit 15: 0 = Point 16 not in group; 1 = Point 16 is in group
Register 2 - as register 1, but for points 17 to 32
Uint16
Read only
A765 (42853)
1
Register 3 - as register 1, but for points 33 to 48
Uint16
Read only
A766 (42854)
1
Register 4 - as register 1, but for points 49 to 64
Uint16
Read only
A767 (42855)
1
Register 5 - as register 1, but for points 65 to 80
Uint16
Read only
A768 (42856)
1
Register 6 - as register 1, but for points 81 to 96
Uint16
Read only
A769 (42857)
1
Register 7 - as register 1, but for points 97 to 112
Uint16
Read only
A76A(42858)
1
Register 8 - as register 1, but for points 113 to 128
Uint16
Read only
A76B (42859)
1
Register 9 - as register 1, but for points 129 to 144
Uint16
Read only
A76C (42860)
1
Register 10 - as register 1, but for points 145 to 160
Uint16
Read only
A76D (42861)
1
Register 11 - as register 1, but for points 161 to 176
Uint16
Read only
A76E (42862)
1
Register 12 - as register 1, but for points 177 to 192
Uint16
Read only
A76F (42863)
1
Register 13 - as register 1, but for points 193 to 208
Uint16
Read only
A770 (42864)
1
Register 14 - as register 1, but for points 209 to 224
Uint16
Read only
A771 (42865)
1
Register 15 - as register 1, but for points 225 to 240
Uint16
Read only
A772 (42866)
1
Register 16 - as register 1, but for points 241 to 256
Uint16
Read only
A773 (42867)
1
Grp2 Text length
Identi
fi
es the length of a text message to be read
Uint16
Read/Write A774 (42868)
1
Grp2 Text time stamp
Time stamp of the text message to be read (UTC format) Double
Read only
A775 (42869)
4
Grp2 Read text
Read text string from instrument display
String_60
Read only
A779 (42873)
30
Reserved
A797
(42903)
30
Grp2 Write text
Write a text string to instrument display
String_60
Write only
A7B5 (42933)
30
Reserved
A7D3
(42963)
30
Grp2 Batch start
Boolean Flag. Value 0001 starts new batch
Boolean
Write only
A7F1 (42993)
1
Grp2 Batch stop
Boolean Flag. Value 0001 stops current batch
Boolean
Write only
A7F2 (42994)
1
Grp2 Batch running
Batch status
fl
ag: 1 = Running; 0 = Not running
Boolean
Read only
A7F3 (42995)
1
Grp2 Text
fi
eld 1
Batch
fi
eld 1 text string (max. 60 characters)
String_60
Read/Write A7F4 (42996)
30
Reserved
A812
(43026)
30
Grp2 Text
fi
eld 2
Batch
fi
eld 2 text string (max. 60 characters)
String_60
Read/Write A830 (43056)
30
Reserved
A84E
(43086)
30
Grp2 Text
fi
eld 3
Batch
fi
eld 3 text string (max. 60 characters)
String_60
Read/Write A86C (43116)
30
Reserved
A88A
(43146)
30
Grp2 Text
fi
eld 4
Batch
fi
eld 4 text string (max. 60 characters)
String_60
Read/Write A8A8 (43176)
30
Reserved
A8C6
(43206)
30
Grp2 Text
fi
eld 5
Batch
fi
eld 5 text string (max. 60 characters)
String_60
Read/Write A8E4 (43236)
30
Reserved
A902
(43266)
30
Grp2 Text
fi
eld 6
Batch
fi
eld 6 text string (max. 60 characters)
String_60
Read/Write A920 (43296)
30
Reserved
A93E
(43326)
30
Spare
A95C
(43356)
100
Parameter name
Description
Type
Access
Start Addr
Hex (Dec)
Register
Length
See
table 8.3
for
point types